36
• Control Keypad
4.7.5
DUAL Settings Parameters
– Page 4
When
D.Set: Generator Parameters
is required, do the following:
Program PROG. Input #8 to
DUAL Settings
(this is its default setting). Refer to section
Set dip switch #3 to ON (refer to section
Connect control inputs voltage to input terminal 8.
The following display appears:
D.Set: Generator
Parameters
Function &
Default
Range
Unit
Description
Starting VOLT-2
30%
10-50%
After
reaching
50% the
display
changes to:
Starting
CURR-2
100-400%.
% of mains
voltage
Starting CURR-2
100%
Sets the motor’s Starting Voltage in DUAL Setting
mode. (Motor’s torque is directly proportional to the
square of the voltage)
Refer to section
Starting Voltage
Current Limit-2
300% of Im
100-700%.
% of Motor
Current
Sets the motor’s highest current during starting in
DUAL Setting mode.
Refer to section
Current Limit
.
Ramp UP-2
10 SEC.
1-30
sec.
Sets Ramp UP-2 time of the motor in DUAL Setting
mode.
Refer to section
Ramp UP Time
.
Ramp DOWN-2
10 SEC.
1–30
sec.
Sets Ramp DOWN-2 time of the motor in DUAL Setting
mode.
Refer to section
Ramp DOWN time
.
Motor Current-2
31 Amp.
50-100% of
STARTER
Current.
A.
Sets the motor’s Full load Ampere, Im, in DUAL Setting
mode.
Refer to section
Motor
Current.
Note:
Motor Current-2
can be set to an equal
or lower value than
Motor Current
set
in
Main Settings
page.
Store Settings
DUAL Settings
Same
as
Store Settings Main Settings
33
Displays in MINIMIZED MODE and MAXIMIZED MODE.
34
The range of the Starting Voltage can be extended to 10-80% by using the EXPANDED SETTING as described in section
5.5.5
page 50.
35
The range of the Ramp UP-2 time can be extended to 1-90 sec. by using the EXPANDED SETTING as described in section
5.5.5
page 50.
36
The range of the Ramp DOWN-2 time can be extended to 1-90 sec. by using the EXPANDED SETTING as described in section
5.5.5 page 50.
Содержание ASTAT XT QT 0008U Series