• Control Keypad
4.7
Overview of All Mode Pages and Factory Defaults
Appears
only
in
Maximized
Display Page
Main Settings
- ****
-
Start Settings
- **** -
Stop Settings
- **** -
DUAL Settings
Parameters
Function & Default
Function & Default
Function & Default
Function & Default
Function & Default
Motor Current
0
Starter Current
58 AMP.
Soft Start Curve
0(Standard)
Soft Stop Curve
0(Standard)
Starting VOLT-2
30%
Line Voltage
0 Volt
Motor Current
58 AMP.
Kickstart Time
0 SEC.
Ramp DOWN TIME
10 SEC.
Starting CURR-2
100%
Thermistor Input.
3.1 Kohm
LINE/DELTA Conf.
Line
Starting Voltage
30 %
End Torque
0 (MIN.)
Current Limit-2
300% of Im
Undercurrent FLT
0% of Im
Starting Current
100 %
Store Settings
Stop Settings
Ramp UP-2
10 SEC.
Undercurrent DLY
10 SEC.
Current Limit
400% OF Im
Ramp DOWN-2
10 SEC.
O/C JAM Fault
850% OF Im
Ramp UP Time
10 SEC.
Motor Current-2
31 AMP.
O/C JAM Delay
0.5 Sec.
Max. Start Time
30 SEC.
Store Settings
Dual Settings
Overload Class
IEC CLASS 10
Number of Starts
10
Overload Protect
Enabled
Duty Cycle Time
30 Min.
Undervoltage FLT
300 Volt
Start Lockout
15 Min.
Undervoltage DLY
5 SEC.
EOR Relay Delay.
5 Sec.
Overvoltage FLT
480 Volt
Store Settings
Start Settings
Overvoltage DLY
2 SEC.
Store Settings
Main Settings
16
Refer to section
5.5.1 on page 49 for changing mode from Minimized Mode to Maximized Mode.