background image

1040972B • February 2007

Copyright © 2007, GE Security Inc.

8-Area LCD RAS • AL-1103, AL-1108

Installation Instructions

Introduction

This is the GE 

8-Area LCD RAS Installation Instructions

 for 

models AL-1103 and AL-1108. The RAS is the primary user 
interface for navigating system programming, doing simple data 
entry, and controlling the Alliance system alarm and access 
control functions. The scrolling text, Liquid Crystal Display 
(LCD) displays data entry, system status messages, programming 
menus, and function options. These can be accessed and selected 
through the alphanumeric digital keypad (

Figure 1

). The         

AL-1108 model is also fitted with a card reader option.

Figure 1. RAS components

The LCD is backlit and the keypad is low-level illuminated, or in 
case of poor lighting conditions, may be programmed for high-
level illumination. The LCD backlight remains illuminated for 
30 seconds after the last key press. The keypad high-level illumi-
nation remains active for four minutes after the last key press.
You can program the eight red area LEDs (four on each side of 
the keypad) in 

Figure 2

 to indicate the status for areas 1 to 8 or 

areas 9 to 16. The four larger status LEDs indicate power (green), 
system trouble (yellow), alarms red), and access (blue).

Figure 2. Cover LEDs

You can mount the RAS up to 5,000 ft. (1.5 km) from the control 
panel. If the distance between the RAS and the control panel 
does not exceed 328 ft. (100 m), you can power the RAS using 
the +12V and 0V terminals from the control panel. When the 
distance exceeds 328 ft. (100 m), use the AUX PWR terminal 
from a DGP or an auxiliary power supply. If you use AUX PWR, 
you must connect the 0V from the control panel to the 0V on the 
DGP or auxiliary power supply.

Installation

To install the unit, do the following:
1.

Locate the cover lock screw on the bottom of the unit and 
unscrew it until you can lift the cover off the mounting plate 
(

Figure 1

).

2.

Use the mounting plate to locate and install mounting 
anchors where needed (

Figure 3

).

Figure 3. Mounting plate

3.

Pull the wiring through the cable entry and screw the 
mounting plate to the wall. If a pry-off tamper is required, 
use a screw in the tamper hole on the mounting plate 
(

Figure 3

).

4.

Wire the circuit board. Turn off all power to the control 
panel before wiring the unit. See 

Wiring

 on page 2.

5.

Set the DIP switches as needed. See 

DIP switch settings

 on 

page 3.

6.

Insert the cover in the guides at the top of the mounting 
plate (

Figure 3

), pull the cover down, and tighten the cover 

lock screw at the bottom of the unit (

Figure 1

).

7.

Refer to your Alliance system programming documentation 
for keypad operation and system programming.

Mounting plate

Cover

LCD

Keypad

Door

Cover lock screw

Powe

r Fault

Alarm

Access

Status LEDs

Area LEDs

Area
LEDs

CAUTION:  

You must be free of static electricity 
before handling circuit boards. Wear a 
grounding strap or touch a bare metal 
surface to discharge static electricity.

Tamper
  screw

 Cover

guides

Mounting holes

Mounting holes

Cable entry

Отзывы: