Voltage
Power Size
Clearance a/b
200–240V
0.25–3.7kW 0.33–5HP
100mm / 4in
5.5–22kW 7.5–30HP
200mm / 8in
> 22kW / 30HP
225mm / 10in
380–480V
0.37–7.5kW 0.5–10HP
100mm / 4in
11–45kW 15–60HP
200mm / 8in
> 45kW / 60HP
225mm / 10in
525–600V
0.37–7.5kW 0.5–10HP
100mm / 4in
11–45kW 15–60HP
200mm / 8in
> 45kW / 60HP
225mm / 10in
525–690V
all
225mm / 10in
Table 3.1 Minimum Airflow Clearance Requirements
3.3.2 Lifting
•
Check the weight of the unit to determine a safe
lifting method
•
Ensure that the lifting device is suitable for the
task
•
If necessary, plan for a hoist, crane, or forklift with
the appropriate rating to move the unit
•
For lifting, use hoist rings on the unit, when
provided
3.3.3 Mounting
•
Mount the unit vertically
•
The drive allows side by side installation.
•
Ensure that the strength of the mounting location
will support the unit weight
•
Mount the unit to a solid flat surface or to the
optional backplate to provide cooling airflow (see
and
•
Improper mounting can result in overheating and
reduced performance.
•
Use the slotted mounting holes on the unit for
wall mounting, when provided.
Illustration 3.2 Proper Mounting with Backplate
Item A is a backplate properly installed for required airflow
to cool the unit.
Illustration 3.3 Proper Mounting with Railings
NOTE
Backplate is needed when mounted on railings.
Installation
AF-650 GP Quick Guide
4
DET-759A
3
3