Illustration 3.14 Control card wiring path for the 61/63. Control
card wiring for the 62/64 use the same path.
In the Chassis (IP00) and NEMA 1 units it is also possible to
connect the network from the top of the unit as shown in
the following pictures. On the NEMA 1 unit a cover plate
must be removed.
Illustration 3.15 Top connection for network.
Installation of field installed 24 Volt external DC Supply
option module (OPC24VPS)
Torque: 0.5 - 0.6 Nm (5 in-lbs)
Screw size: M3
No.
Function
35 (-), 36 (+)
24V external DC supply
24V DC external supply can be used as low-voltage supply
to the control card and any I/O or network option cards
installed. This enables full operation of the keypad
(including parameter setting) without connection to mains.
Please note that a warning of low voltage will be given
when 24 VDC has been connected; however, there will be
no tripping.
WARNING
Use 24 VDC supply of type PELV to ensure correct galvanic
isolation (type PELV) on the control terminals of the
frequency converter.
3.1.20 Access to Control Terminals
All terminals to the control cables are located beneath the
keypad. They are accessed by opening the door of the
Nema 1 / Nema 12 or removing the covers of the IP00
Open Chassis version.
3.1.21 Electrical Installation, Control
Terminals
To connect the cable to the terminal:
1.
Strip insulation by about 9-10mm
2.
Insert a screwdriver
1)
in the square hole.
3.
Insert the cable in the adjacent circular hole.
4.
Remove the screwdriver. The cable is now
mounted in the terminal.
To remove the cable from the terminal:
1.
Insert a screw driver
1)
in the square hole.
Electrical Installation
AF-600 FP High Power Operating Instructions
32
3
3