2.2.1 Start-up of the Frequency Converter
Use the frequency converter keypad mounted either on the drive or remote. Use the Extended Menu key to access the O-## group parameters (Options / Comms).
The settings shown below are typical. Some settings may be changed to meet the application requirements. The settings below will serve as a good starting
reference. Refer to the operating instruction manual for instructions on changing parameters and programming the drive.
Examples of typical settings. Program the following:
Parameter:
Setting:
par. O-30
Protocol
[3] Metasys N2
par. O-31
Address
1 (Default)
par. O-32
Drive Port Baud Rate
[2] 9600 Baud (fixed at 9600 for N2 protocol)
par. O-50
Coasting Select
[3] Logic OR
par. O-52
DC Brake Select
[3] Logic OR
par. O-53
Start Select
[3] Logic OR
par. O-54
Reversing Select
[0] Digital input
par. O-55
Set-up Select
[3] Logic OR
par. O-56
Preset Reference Select
[3] Logic OR
par. O-94
Bus Feedback 1
0
par. O-95
Bus Feedback 2
0
NB!
Send an F command to begin communications between the master and the drive!
Example 1:
F command
Setting:
Device address
XX
Char1 command
F
Checksum
YY
Message code:
>XXFYY <CR>
Issue a run command through the master, to the device:
Example 2:
Network start, BO override command:
Setting:
Device address
XX
Char1 command
7
Char1 subcommand
2
Char2 region
04
Char2 object number (NPA)
04 (Start)
Char2 override value
01 (Active)
Checksum
YY
Message code:
>XX72040401YY <CR>
Issue a frequency reference through the master, to the device:
16
2