Object Id
Object Name
Read/Write
Changeable De-
scription
Non volatile ram
Store
Drive Par.
Alarm
notifi-
cation
Triggers Bus Time-
out
BO:30
Reserved output
E-90/30*
W/R
No
No
E-90/30
No
Yes
BO:31
Reserved output
E-90/31*
W/R
No
No
E-90/31
No
Yes
BO:36
Reserved output
E-90/26*
W/R
No
No
E-90/26
No
Yes
BO:37
Reserved output
E-90/27*
W/R
No
No
E-90/27
No
Yes
BO:38
Reserved output
E-90/28*
W/R
No
No
E-90/28
No
Yes
BO:39
Reserved output
E-90/29*
W/R
No
No
E-90/29
No
Yes
Table 5.7: Binay outputs cont.
*) Reserved for future options!
Object ID
Object Name
Read / Write
Changeable De-
scription
Non volatile ram
Store
Drive Par.
Alarm
notifi-
cation
Triggers Bus
Timeout
BV:0
Com. Fault
R
No
NA
BACnet option
Yes
No
BV:1
Start
W/R
No
No
CTW
No
Yes
BV:2
Coasting
W/R
No
No
CTW, Bit 3 =0
No
Yes
BV:3
CW/CCW
W/R
No
No
CTW bit 15=1
No
Yes
BV:4
Jog
W/R
No
No
CTW bit 0 =1
No
Yes
BV:5
Reset
W
No
No
CTW bit 07 = 1
No
Yes
BV:6
Reset Kwh Counter
W
No
No
ID-06
No
NO
BV:7
Reset Running Hours
Counter
W
No
No
ID-07
No
NO
BV:10
Drive Ready
R
No
NA
STW Bit 01
No
No
BV:11
Reverse
R
No
NA
STW Bit 15
No
No
BV:12
Speed = reference
R
No
NA
STW Bit 08
No
No
BV:13
Bus control
R
No
NA
STW Bit 09
No
No
BV:14
Tripped
R
No
NA
STW Bit 03
Yes
No
BV:15
Triplock
R
No
NA
STW Bit 06
Yes
No
BV:16 -20
Reserved
R
No
Table 5.8: Binary values
24
5