GEH-15398  Types  AB  and  DB  Ammeters  and  Voltmeters 

dimensions  of  the  external  resistors  are  given  in  Fig. 

10,  11,  and  12. 

D-C  AMMETERS 

D-e  ammeters  designed  for  current  measurement 

above  60  amperes  necessitate  the  use  of  shunts  which 

are  to  be  connected  to  the  ammeter  by  means  of  the 
leads  provided.  In  the  event  that  leads  are  supplied 
by  the  purchaser,  their  resistance  should  agree  with 
the value  stamped  on the  instrument  nameplate.  Any 
change  in  the  resistance  of  these  leads  will  introduce 
an  error  in  the  reading.  General  Electric  shunts  of 
the  same  ampere  rating  and  millivolt  drop  are  inter­
changeable. 

Warning: 

All  ammeter. shunts  should  be  connected 

in the  grounded  side  of the  line  when possible.  When 

this  is  not  possible,  or  the  circuit  cannot  be  grounded, 
the  metal  parts  of  manually  operated  contact  devices 
or  auxiliary  pointer  knobs  which  project  through  the 
cover  are at  line  potential.  When  the  cover  is  remov­
ed,  also  remember  that  the  instrument  windings,  as 

well  as  the  scale  and  pointer,  are  at  line  potential. 

Use  caution  to  avoid  contacting  this  potential. 

As  the  resistance  of  the  shunt  leads  used  in  certain 

applications  cannot  be  predetermined  at  the  factory, 
it  has  been  found  desirable  to  furnish  some  d-e  am­
meters  with  an  internal  rheostat  to  adjust  for  non­

standard  lead  resistances. 

The  nameplate  on the  instrument has  an  INSTRU­

MENT 

LEAD  RESIS.  value  stamped  upon  it. 

This  value  is  to  be  that  of  the  total  circuit,  which  is 
considered  to  include  the  resistance  of  the  instrument 

and  its  leads  with  the  shunt  disconnected.  This  total 

circuit  resistance  must  be  adjusted  correctly  in  order 

to  attain  the  specified  accuracy  of  the  instrument. 

To  adjust  the  rheostat  for  a  given  lead  resistance. 

proceed  as  follows: 

If  a  resistance  bridge  is  available,  connect  it  across 

the  shunt  end  of  the  leads  (shunt  disconnected)  and 
the  instrument  across  the  opposite  end.  Set  the  re­

sistance  bridge  for  the  INSTRUMENT 

� 

LEAD 

RESIS.  value  stamped  on  the  instrument  nameplate. 

Loosen  the  lock  nut  (located  under  the  nameplate). 
and  turn  the  rheostat  shaft  (which  projects  through 

the  nameplate)  until  a  zero  deflection  is  secured  on 
the  bridge  galvanometer.  After  the  correct  setting 
has  been  obtained,  retighten  the  lock  nut. 

If  a  resistance  bridge  is  not  available.  adjustment 

may  be made by  connecting  a standard  millivoltmeter 
across the  shunt end  of the  leads  (shunt  disconnected) 
and  the  instrument  across  the  opposite  end.  Apply 

a  low  adjustable  d-e  voltage  across  the  shunt  end 
of the  leads  and adjust  this  voltage  until  the  indication 

on  the  standard  millivoltmeter  agrees  with  the  full-

scale  millivolts  (marked  FULL  SCALE  MV)  on  the 
instrument  nameplate.  Loosen  the  lock  nut  (located 
under  the  nameplate),  and  turn  the  rheostat  shaft 

(which  projects  through  the  nameplate)  until  the 

ammeter  reads  full  scale.  Retighten  the  lock  nut. 

Note: 

The  maximum  lead  resistance  is  about  1 ohm 

for a  100-millivolt  instrument  and about 0.26 ohm for 

a  50-millivolt  instrument. 

D-C  VOLTMETERS 

D-e  voltmeters  designed  for  use  on  circuits  above 

750  volts  and  d-e  ground  detectors  for  voltages  up  to 

and  including  750  volts  are  furnished  with  external 

resistors  and  are  connected  directly  to  the  circuit  to 

be  measured. 

INSTALLATION 

MOUNTING 

The  appropriate  dimension  drawings  shown  in  this 

book  should  be  followed  when  drilling  the  switch­
board.  All  drilling  and  all  wiring  on  the  switchboard 

should  be  completed  before mounting the  instruments. 

Supporting  studs  are  provided  for  mounting  on  the 

switchboard.  Mount  the  instruments  in  a  level  posi­

tion. 

These  instruments  are  practically  uneffected  by 

stray  fields,  but  it  is  advisable  to  keep  transformers 
and  wires  carrying  heavy  current  as  far  as  possible 

from  all  indicating  instruments. 

When  there  is  no  current  flowing  through  the  in­

strument  and  it  is  properly  leveled,  the  pointer  should 
indicate  zero.  Any  deviation  from  zero  should  be 
corrected  by  means  of  the  zero  adjustor. 

TERMINAL  CONNECTIONS 

The  threads  on  the  terminal  studs  and  nuts  should 

be  clean  and  bright.  The  contact  surfaces  of  nuts. 
busbars. and  cable terminals  must  be thoroughly  clean 
to  insure  good  contact.  If  a  nut  turns  hard,  it  should 
be  run  over  a  tap  of  the  proper  dimensions;  otherwise. 
the  threads  on  the  stud  may  be  ruined  or  the  stud 

turned  in  the  instrument,  thereby  breaking  the  con­
nection.  After  the  instrument  has  been  connected. 
tighten  the  nuts  sufficiently  to  insure  good  contact. 

Do  not  overtighten. 

The  nuts  and  studs  used  in  these  instruments  are 

U. 

S.  standard. 

Connect the  instrument  as  shown  in the  appropriate 

diagram.  The  numbers  in  these  connection  diagrams 
correspond  to  the  numbers  stamped  on  the  instrument 
terminals. 

On  instruments  manufactured  prior  to  1951,  the 

terminal  studs  are  stamped  with  letters  instead  of 

www . ElectricalPartManuals 

. com 

www 

. ElectricalPartManuals 

. com 

Содержание AB Series

Страница 1: ...RUCTIONS GEH 15398 Supmedes GEH 1539A TYPES AB AND DB AMMETERS AND VOLTMETERS 150 GENERAL ELECTRIC w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 2: ...nd DB 10 ammeters and voltmeters and DB 10 ground dete ctors PANEL SIDE MOUNTING STUD f 28 THO BACK 3 32 t PRESENT ON VOLTMETERS ONLY GROUNDING STUD 6 40 TAP FIG 2 DIMENSIONS OF TYPES AB 12 AND 13 AND TYPES D B 12 MID 3 AMMETERS VOLTMETERS AND GROUND DETECTORS STUD INSTRUMENT LOCATION D e Ammeters CD D c Voltmeters AB D e Ground Detector CD A c Ammeters AB A c Voltmeters AB 3 3 3 4 4 3 DIA 1 32 NO...

Страница 3: ...ment nameplate A C VOLTMETERS When the circuit exceeds 750 volts a potential transformer of the ratio indicated on the instrument nameplate must be used The transformer must have a frequency rating which corresponds to that on the instrument nameplate An external Form 3 resistor must be used when so indicated on the instrument nameplate The table below gives the number of tubes in the resistor sup...

Страница 4: ...er across the shunt end of the leads shunt disconnected and the instrument across the opposite end Apply a low adjustable d e voltage across the shunt end of the leads and adjust this voltage until the indication on the standard millivoltmeter agrees with the full 4 scale millivolts marked FULL SCALE MV on the instrument nameplate Loosen the lock nut located under the nameplate and turn the rheost...

Страница 5: ...PERATION The d e instruments utilize a permanent magnet moving coil mechanism adapted for the longscale in strument design Current passing through the mov ing coil produces a magnetic field which interacts with the field produced by the permanent magnet thus supplying the deflecting torque The moving system deflects until counterbalanced by the instru ment control springs The a c instruments excep...

Страница 6: ...NT LOCATION X y D e Ammeters CD 3 9 16 2 31 32 D e Voltmeters AB 3 9 16 2 31 32 D e Ground Detector CD 3 9 16 2 31 32 A c Ammeters AB 4 15 32 3 7 8 A c Voltmeters AB 4 15 32 3 7 8 A c Voltmeters expanded scale AB 5 29 32 5 5 16 Fig 4 D1mens1ons of Types AB 1 4 1 5 and 19 and Types DB 1 4 15 and 1 9 ammeters and voltme ters and g round dete ctors FRONT SIDE MOUNTING PANEL STUD f zs THO 1 c I I 15 1...

Страница 7: ... BELOW FRONT STUD DIMENSIONS INSTRUMENT LOCATION X y D e Ammeter CD 3 5 16 2 27 32 D e Vo tm ter AB 3 5 16 2 27 32 D e Ground Detector CD 3 5l16 2 27 32 A c Ammeter AB 4 7 32 3 3 4 A c Ammeter double rated AB EF 4 7 32 3 3 4 A c Voltmeter AB 4 7 32 3 3 4 A c Voltmeter expanded scale AB 5 21 32 3 3 16 Fig 6 Dimensions of Types AB 16 and DB 16 ammeters voltmeters and ground detectors SIDf BAC 1 f l ...

Страница 8: ...oltmeter AB 3 11 32 2 31 32 D e Ground Detector CD 3 11 32 2 31 32 A c Ammeter AB 4 1 4 3 7 8 A c Ammeter double rated AB EF 4 1 4 3 7 8 A c Voltmeter AB 4 1 4 3 7 8 A c Voltmeter expanded scale AB s 11 16 S S 16 Fig 8 Dimensions of Types AB 18 and DB 18 ammeters voltmeters and ground detectors FRON T SIDE 9 1 6 L 1 NAMEPLATE RHEOSTAT 332 32 USE AS GROUNDING STUD IN ACCORDANCE WITH EXTERNAL CONNEC...

Страница 9: ...th external shunt SOURCE FUSES Fig 18 D e voltmeter ra ted above 750 volts with external resistor SOURCE LOW HIGH LOAD Fig 15 Low range on double rated d e ammeter FUSES L 0 AO Fig 19 Double rated d e voltmete r illustrating use of swit ch to sele ct range SOURCE Fig 16 High range on double rated d e ammeter SOURCE F SES LOAD Fig 19a D e ground de te ctor for voltages up to and in cluding 750 volt...

Страница 10: ...OURCE Fig 24 High range an double rate d a c ammete r SOURCE LOAD Fig 27 A c v o Itm e t e r Types AB 10 12 and 1 3 only with potential tran s former SOURCE Fig 22 A c a m m e t e r Types AB 14 15 16 1 8 and 19 only with current transformer SOURCE FUSES I LOAD Fiy 25 Self contained a voltmete r SOURCE FUSES H1 X1 sn LOAD Fig 28 A c v o It m e t e r Types AB 14 15 16 18 and 19 only with poten tial ...

Страница 11: ...i 3 8000 c 15 6 13 10 1g 6 A2 3 i 3 10000 c 17X 8 15 i 12 5 3 J l 1 v 2 2 2 3 Y Y K J i J i J i A A 2 3 i l 1 l 1 Jl 2 L J i J i J i A A 3 i l1 23 12 v X X u u u u I Connection Stripe Each End 1 1 1 I I I I 1 1 I 1 2 2 3 3 4 4 5 5 5 7 7 For current values above 10 000 amp the best arrangement is to use two or more shunts in parallel with a separate set of leads for each shunt The Form 15 shunts fo...

Страница 12: ...Ore Cascade B dg 1170 Pearl St Evansville 19 Ind 123 N W Fourth St Fairmont W Yo 310 Jacobs Bldg P O Box 1626 Fergus Falls Minn I 08N Court Ave P O Box 197 Flint 3 Mich 653 S Saginaw St Fort Wayne 6 Ind 3606 So Calhoun St Fort Worth 2 Tex 408 W Seventh St Fort Worth Tex Fresno 1 Calif Grand Rapids 2 Mich Greensboro N C Greenville S C Gulfport Miss Hagerstown Md Hartford 5 Conn Houston 1 Te x os In...

Отзывы: