background image

OPM_NPE_19X_600_1K5_2GB_V030

3

GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

g

GE Digital Energy 

2.2

Installation Procedure

1.

Remove the transport screws (A, fig. 1) and store them in the free holes (B, fig.1). Mount the

NetPro 19”

 UPS in the 19” rack. The module must be supported by mounting rails, do not mount

it by using the front brackets only. The front brackets allow mounting of handles (not included).

2.

Make sure that the air vents in the side panels of the module are not blocked by the mounting

rails or the side panels of the 19” rack.

3.

1000VA model only:

Battery extension module(s) can be installed to

increase the battery runtime. Connect the DC

connector of the battery module (7, fig. 2) to the DC

socket of the UPS (2, fig. 1/2). You will hear a click

when the cable is properly installed. Block the DC

connector: install the small locking plate (7a, fig. 2)

that came with the battery module, and fasten it with

the screw provided. Using the DC connector of the

battery module (not shown) you can install a second,

third, etc. module. See also section 5.1.

4.

Switch off your computer, and unplug it from the

socket-outlet.

5.

Disconnect the power cord from the computer

(rating 250Vac/10A) and connect this cord to the

mains input socket (5, fig. 1) of the UPS. See fig. 4.

6.

Using the output cord(s) provided, connect the

computer(s) to the appliance outlet(s) (1, fig. 1) of

the UPS. Spread the loads over the appliance

outlets as equally as possible. If you use a

distribution box to connect more than one appliance

per outlet, please note that the maximum AC-current

rating of each appliance outlet is 10Amps. See fig. 3.

7.

Connect the mains cord of the UPS to a working,

grounded AC wall socket outlet. See fig. 4. The

green LED 'on' (8, fig. 6) will blink now: mains power

is available and the batteries are charging. If the

LED does not blink but illuminates continuously

instead, press ‘0’ for one second.

8.

For best results, allow the UPS to recharge the batteries during a period of approx. 2 hours. It is

acceptable to use the UPS without first charging the battery, but the runtime may be reduced.

9.

For advanced communication possibilities, the RS232 interface port (6, fig. 1) can be connected

to a computer system and/or optional interface cards (3, fig. 1) can be added. See chapter 4.

7a

2

7

6

5

1

3

2

4

A

B

fig. 3

fig. 4

fig. 1

fig. 2

Содержание 600 - 1500 VA

Страница 1: ...anufactured by GE Digital Energy General Electric Company Telephone 41 0 91 850 51 51 CH 6595 Riazzino Locarno Fax 41 0 91 850 51 44 Switzerland Website www gedigitalenergy com GE Digital Energy Technology for the Digital World ver 3 0 GB NetPro 19 UPS g ...

Страница 2: ...tions 3 2 2 Load indication 3 2 3 Auto off no load shutdown 3 2 4 Automatic bypass switch 3 2 5 Switching off 3 3 Use Status and Alarm Indications 3 3 1 Charger on 3 3 2 On line normal operation 3 3 3 On battery 3 3 4 Battery low end of runtime 3 3 5 On bypass 3 3 6 Bypass out of limits 3 3 7 Overload 3 3 8 Overtemperature 3 3 9 Replace battery 3 3 10 Programmed shutdown 3 4 Use Setup Mode 3 5 Bat...

Страница 3: ...se note that with completely discharged batteries the UPS will not start at all External charging or replacement of the batteries will be necessary The shipping box contains a NetPro 19 UPS two IEC male female power cords a data cable a CD ROM and this manual Inspect the UPS for damage after unpacking If any damage is present please immediately notify the carrier and place of purchase IMPORTANT Be...

Страница 4: ...4 Switch off your computer and unplug it from the socket outlet 5 Disconnect the power cord from the computer rating 250Vac 10A and connect this cord to the mains input socket 5 fig 1 of the UPS See fig 4 6 Using the output cord s provided connect the computer s to the appliance outlet s 1 fig 1 of the UPS Spread the loads over the appliance outlets as equally as possible If you use a distribution...

Страница 5: ...h off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will automatically turn on again when mains power is restored The default setting of the no load shutdown function is activated Changing of the setting is described in 3 4 3 2 4 Automatic bypass switch The UPS is equipped with an automatic bypass sw...

Страница 6: ...ld be taken Indicators on front panel Situation on alarm on by pass progr shutd repl batt on batt buzzer o Charger on 3 3 1 o Normal operation 3 3 2 On battery 3 3 3 1x 8 s Battery low 3 3 4 1x s On bypass 3 3 5 1x s Bypass out of limits 3 3 6 1x 8s Overload 3 3 7 1x s High temperature 3 3 8 1x s Replace battery 3 3 9 o Progr shutdown pending 3 3 10 1x 8s o Progr shutdown in progress 3 3 10 Operat...

Страница 7: ... also 3 2 2 If 4 yellow LEDs and the red LED illuminate bypass operation is caused by an overload If only yellow LEDs illuminate the red LED is off during load indication bypass operation is caused by overtemperature Take appropriate measures reduce load and or temperature 3 3 6 Bypass out of limits The mains voltage or mains frequency are outside bypass input tolerance but inside UPS input tolera...

Страница 8: ... failure occurs during the sleep period and the battery capacity eventually drops below 80 of the normal capacity the UPS will automatically switch off in order to save battery power When the mains returns the UPS will start up automatically The programmed sleep time however is lost The programmed shutdown in progress can be cancelled x press keypad I for at least 5 seconds to cancel shutdown and ...

Страница 9: ...battery test to be initiated through the UPS software via the RS232 port checks the actual battery capacity in order to ensure accurate runtime prediction During a deep battery test the batteries will be discharged until battery low alarm level Please note that immediately after a deep battery test the expected runtime is very short allow the UPS to recharge its batteries For details please refer ...

Страница 10: ...s no longer guaranteed due to other circumstances than already indicated by pin 6 7 9 Output converter overload Overtemperature pre alarm High charger voltage Bypass out of limits Inverter shutdown due to inverter failure or batt failure 4 2 Relay Interface Card option The card is equipped with potential free change over contacts for the following alarms mains failure general alarm battery low byp...

Страница 11: ... free take care of proper environmental conditions and keep air inlets outlets free of dust Please read 2 1 6 2 Batteries 6 2 1 General The service life of the battery is from 3 to 6 years depending on the operating temperature and on the number of discharge cycles As a healthy battery is critical to the performance of the UPS an automatic quick battery test is performed regularly to ensure failsa...

Страница 12: ...ttery compartment Use a screw driver or pen as a lever 3 Remove the two screws that hold the battery drawer 4 Disconnect the DC connectors Use a screwdriver as a lever 5 Remove battery drawer Be careful heavy weight 6 Remove clamp two screws and replace the batteries 7 Reinstall battery clamp do not pinch or clamp the wires 8 Slide in the battery drawer 9 Connect the DC connectors a small spark is...

Страница 13: ...Line cord not connected Read 2 2 Connect line cord Dead wall socket outlet or mains voltage out of limits Contact qualified electrician UPS overtemperature See 3 3 8 Allow UPS to cool down UPS will not switch on without using battery start and the output has been off for a few secs see also 3 2 5 Tripped Thermal Circuit Breaker See above UPS will not switch on after installation LED on remains off...

Страница 14: ...ut voltage range 195 264 V Frequency tracking rate 2 Hz sec Frequency tracking range nominal 10 Phase difference 7º Typical transfer time msec 4 Overload capability Fully protected against overload and short circuits Overload behaviour battery operation 110 during 5 minutes 150 during 5 seconds Overload behaviour during depends on rating of thermal circuit breaker bypass operation typical 125 of T...

Отзывы: