2

PRELIMINARY 10/29/03

Connecting External Switches

External switches used with Door/Window Sensors allow 
you to protect doors and windows when there is inadequate 
room for directly mounting the sensor or when you want to 
locate the Door/Window Sensor in an adjacent but less visi-
ble place.

Figure 4.  External Switch Terminal

Materials and Tools Needed

Hermetically sealed external switches (sealed reed 
switch) that supply a minimum 250 millisecond open on 
alarm (only normally closed circuits can be used on this 
sensor)

4.7 k ohm EOL resistor

Stranded 22-gauge wire

Small wire cutters

Installation Guidelines

1. Install the magnet on the opening edge of the door or 

movable part of a window.

2. Position the switch on the door or window frame within 

2.5 cm of the magnet.

3. Install a 4.7 k ohm EOL resistor in series with the exter-

nal switch at the switch location, not at the sensor.

4. Remove the sensor cover.

5. Pass the wires on the external switch through the rear 

opening at the bottom of the sensor.

6. Attach each wire to one side of the screw terminal. Use 

no more than 3 meters of wire.

7. Press the screw terminal over the wire posts.

8. Mount the sensor.

Programming

The following steps describe the general guidelines for pro-
gramming (learning) the sensor into panel memory. Refer to 
the specific panel installation instructions or reference man-
ual for complete programming details.

1. Set the panel to program mode.

2. Proceed to the LEARN SENSORS menu.

3. Trip the sensor tamper switch by removing the sensor 

cover.

4. Select the appropriate sensor group and sensor number 

assignments.

5. Exit program mode.

Sensor Test

The sensor test verifies good communication between the 
detector and panel.

1. Put panel/receiver into sensor test mode (see panel/

receiver installation instructions).

2. Open the door the sensor is protecting. The sensor 

transmits a test signal.

3. Listen for siren beeps to determine appropriate response 

(refer to the panel/receiver 

Installation Instructions

).

4. Close panel cover.

Specifications

Model No.: 

60-xxx

Frequency: 

900 MHz

Compatibility: 

GE Interlogix 900 MHz AM Control Panels/

Receivers

Battery Type:

 3.0 V, 1300 mAh lithium (1 or 2)

Recommended Battery:

 Duracell DL123A, Panasonic CR123A, 

Sanyo CR123A

Typical Standby Current (µA):

 3

Estimated Battery Life (at 20° C):

 8 years (one battery);

15 years (two batteries)

Supervisory Interval:

 6.5 minutes

Typical RF Output Power (mW):

 250

Operating Temperature:

 0° to 49° C (32° to 120° F)

Storage Temperature:

 -34° to 60° C (-30° to 140° F)

Relative Humidity:

 0 - 90% non-condensing

Dimensions (mm):

 45 x 115 x 31 (L x W x H)

Weight (g):

 88

Notices

This device complies with FCC Rules Part 15. Operation is 
subject to the following two conditions.

This device may not cause harmful interference.

This device must accept any interference that may be 
received, including interference that may cause undesired 
operation.

Changes or modifications not expressly approved by GE 
Interlogix can void the user’s authority to operate the equip-
ment.