GE 60-362 Скачать руководство пользователя страница 2

Door/Window & Long Life Door/Window Sensors

Installation Instructions

2

Fig 2.   Continued from Page 1

5.

Mount the sensor base. Next, remove the magnet from the 
base and mount it no more than 3/8” from the sensor base 
(see Figure 3).

Figure 3.

Sensor Base and Magnet Mounted on a Door and Door Frame

Note:

Mount the magnet so that it does not interfere with door or 
window openings. Do not use double-sided tape or other 
adhesive products.

6.

Connect the circuit board to the base.

7.

Replace the sensor cover.

Connecting External Switches

Door and window sensors can be connected to normally open 
(close on alarm) or normally closed (open on alarm) external 
switches. For normally open switches, wire multiple sensors in 
parallel; for normally closed switches, wire multiple sensors in 
series.

Do not use both a built-in reed switch and an external switch on 
the same door/window sensor. For high-security installations, 
remove 

both 

reed switches when external switches are connected 

to sensor terminals.

Note:

For UL-listed installations, use only a normally closed 
configuration.

Materials Needed

• Sealed, external reed switches with a minimum 250 mS 

open or close on alarm.

• Stranded, 22-gauge wire.

Installation Guidelines

• Do not use solid-core wire or mechanical switches.
• For remote device connections, do not use a sensor’s built-

in reed switches.

• Do not connect fast pulse devices such as a Window Bug to 

a door or window sensor.

• Do not exceed a wire length of 25 feet for 22-gauge, 

stranded wire runs. For UL-listed installations, do not 
exceed a wire length of three feet between a sensor and 
external device.

• Do not exceed a length of six feet for untwisted wire pairs.
• Connect up to five switches and one alarm screen to a door/

window sensor.

• Do not route wire runs parallel to other electrical wires. If a 

parellel wire run cannot be avoided, ensure a minimum 
distance of 18” exists between the nearest electrical wiring.

• When necessary, cross electrical wires at a 90° angle.

Programming

The following provides a general guideline for programming a 
door/window sensor into panel memory. Refer to specific panel 

Installation Instructions

 for complete programming details.

1.

Set panel to 

Program Mode.

2.

Enter the 

Learn Sensors 

menu. Next, select the appropriate 

sensor group and number assignments.

3.

Set external switches to 

Alarm 

(open for normally closed 

circuits; closed for normally open circuits).

4.

Remove sensor cover. The sensor tamper switch trips.

5.

Exit 

Program Mode.

6.

Replace sensor cover.

Testing

The following provides a general guideline for testing a door/
window sensor. Refer to the specific panel 

Installation Instruc-

tions

 for complete testing details.

1.

Set panel to 

Sensor Test Mode.

2.

Trip the sensor. Listen for interior siren beeps to determine 
appropriate responses (refer to the panel 

Installation 

Instructions

).

The Long Life Door/Window Sensor has a built-in power saving 
feature that automatically turns on when a sensor is tripped two 
or more times within a four minute period.

When the power saving feature is on and a sensor is tripped, the 
sensor transmits only half of the regular data rounds.

Tamper Switch

3.6V Battery

Reed Switch

Jumper

Terminals

60-641 (New)

Tamper Switch

Terminals

3.6V Battery

Reed Switch

60-632 (New)

Alignment Marks

Magnet

Sensor

Door

Door Frame

Отзывы: