GE 400 Series Скачать руководство пользователя страница 2

 
 
 
 

 

 
 
 

 

Ref.No 

Description 

Catalog 

Number 

Quantity 

Required 









10 
11 

Coil retainer assembly 
Overload relay (3-heater, non-compensated form, 1 NC contact) 
Overload relay (3-heater, non-compensated, 1 NO-1 NC contacts) 
Set of stationary and movable contacts with springs and screws for 3 poles  
Molded cover for stationary and movable contacts 
Return spring for movable contact support 
Molded movable contact support for 2, 3 poles 
Armature and frame (magnet) with retainer 
Operating coil for 2-and 3-pole forms 
Spring retainer for armature 
Cross electrical interlock 

 546A780G052 

CR324D310F 
CR324D360F 

546A780G051 
546A780G054 
547A524G001 
188D700P001 
546A780G053 

15D22G*** 

546A627P001 

CR305X200C 











CHECK FOR WELDED CONTACTS IN 
OVERLOAD RELAY

  

This feature permits the maintenance 
man to check for welded relay contacts 
by simply depressing the white operator 
located at the top of the overload relay 
contact housing. When the relay is in the 
reset condition, an audible “click” will be 
heard when the operator is depressed, 
indicating that the contacts are 
operating normally. A continuity check 
can also be made by disconnecting the 
control wiring from the terminals of the 
relay and placing a bell set or a 
resistance measuring instrument in the 
circuit. Connecting either of these across 
the relay terminals will indicate the relay 
contact is closed until the contact-check 
operator is depressed, opening the 
circuit.  
The exclusive manual contact operation 
check gives positive assurance that 
contacts have not welded due to short 
circuits in the control wiring. 

SIMPLE MAINTENANCE

  

300/400-Line starters and contactors require 
virtually no corrective maintenance. Preventive 
maintenance will assure many years of 
dependable on-line service.  

1.

Always remove power from device before

performing any maintenance.

2.

Keep magnet mating surfaces free of

accumulated dirt or dust.

3.

DO NOT OIL OR GREASE the magnet mating

surfaces.

4.

Contacts are carefully designed for

maximum life. They need only be replaced
when nearly all the silver tip is gone and the
contact tip support is ex posed. DO NOT FILE
the contacts. Filing or otherwise dressing the
contacts only results in lost tip material and
reduces contactor or starter life.

5.

The ultimate tripping current of the installed

relay heater can be adjusted ±10% by using
adjustment dial.

Accessory Kits 

1 st NO aux. cont. (rt.side mtg)………………..CR3O5X200A 
1 st NC aux. cont. (rt.side mtg)…………………CR3O5X200B 
1 st NO-NC aux. cont.for (rt.side mtg)……CR3O5X200C  
Additional NO aux. cont. for all forms……CR3O5X100D 
Additional NC aux. cont. for all forms ….CR3O5X100E  
Pushbutton………………………………………………….. CR305X220N  
Selector switch, H—O—A. …………………………CR305X230N  
Selector switch, OFF—ON. ……………………… CR305X230D 
Indicating light. …………………………………………  CR305X250N  
Fifth pole.(for adding to  
4-pole form only)………………………………………. CR3O5X211B  
Control circuit fuse……………………………………. CR305X241A, B, C, D

  

*** 

Coil Data

 

 

For three-pole device, order Catalog Number 
15D22G plus number in table below.

 

Frequency 

115V 

200/ 

208V 

230V 

460V 

575V 

600V 

60Hz 

002 

023 

003 

004 

005 

006 

Frequency 

110V 

220V 

380V 

440V 

550V 

600V 

50Hz 

007 

008 

064 

009 

010 

011 

*** Add suffix numbers for particular coil rating required. See COIL TABLE above

 

1.

Perform steps 1 through 5

under “Coil Removal”.

2.

Remove magnet from

molded cover and movable
arm.

3.

Remove return spring from

center of movable arm.

4.

Remove molded cover from

movable arm.

5.

Depress and slide movable

contact, spring, and spring
seat from movable arm.

6.

Remove screws holding

stationary contacts in place
and remove stationary
contacts

PRINCIPAL RENEWAL PARTS 

Use 022 for 120V, 60 Hertz/110V, 50Hertz coil. 

7.

Reassemble device by reversing

procedure.

NOTE:

 Do not attempt to remove or replace

arc traps in arc chute cover.

      When reassembling, note that the arc 

chute cover will only fit one way and is 
marked “TOP” in upper right hand corner. 
Magnet and movable arm will fit either way 
but will be quieter if reassembled the same 
way they were taken apart.  

2

 

ABB Inc. 

 

305 Gregson Drive

 

Cary, NC 27511. 

electrification.us.abb.com

  

 

We reserve the right to make technical 
changes or modify the contents of this 
document without prior notice. With 
regard to purchase orders, the agreed 
particulars shall prevail. ABB Inc. does not 
accept any responsibility whatsoever for 
potential errors or possible lack of 
information in this document. 

We reserve all rights in this document and 
in the subject matter and illustrations 
contained therein. Any reproduction or 
utilization of its contents – in whole or in 
parts – is forbidden without prior written 
consent of ABB Inc.  
Copyright© 2019 ABB  
All rights reserved 

 

GE is a trademark of GE. Manufactured 
by ABB Inc. under license from GE. 

1SQC912002M0201

 GEH-4776

C

January 2020