11

knob to spring back out.

2. Insert screwdriver into slot in indicator knob (Figure 11). Press in and rotate knob 

COUNTERCLOCKWISE

 until arrow points directly to the word 

BACKWASH

.

3. Fill resin tank with water.

a. With water supply off, place the bypass valve(s) into the “

NOT IN BYPASS

” position.

b. Open water supply valve very slowly to approximately the 1/4 open position.

IMPORTANT: 

If opened too rapidly or too far, resin may be lost. In this position, you 

should hear air escaping slowly from the drain line.

c. When all of the air has been purged from the tank (water begins to flow steadily from the 

drain), open the water supply valve all the way.

d. Allow water to run to drain until clear.
e. Turn off water supply and let the unit stand for about five minutes. This will allow all trapped 

air to escape from the tank.

4. Add water to brine tank (initial fill).

With a bucket or hose, add approximately 4 gallons (15 liters) of water to brine 
tank. If the tank has a salt platform above the bottom of the tank, add water until 
the level is approximately 1 inch (25 mm) above the platform.

*Clorox is a trademark of the Clorox Company.

 

Содержание 400 Series

Страница 1: ...rand 255 Valve 400 Series Controls Water Conditioning Control System Home Owner Installation Operation and Maintenance Manual For sales or service questions please contact your local dealer Your Local...

Страница 2: ...ng installation of unit This system is not intended to be used for treating water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after the system This s...

Страница 3: ...g Connection Probe Connection Slot Tank Thread 2 1 2 inch 8 male Inlet Connection 3 4 inch or 1 inch NPT or BSPT Drain Connection 3 8 inch or 1 2 inch NPT or BSPT Outlet connection 3 4 inch or 1 inch...

Страница 4: ...tank The brine is then directed down through the resin bed and up through the riser tube to the drain The hardness ions are displaced by sodium ions and are sent to the drain The resin is regenerated...

Страница 5: ...into the unit control valve Hot water can severely damage the conditioner A 10 foot 3 m total pipe run including bends elbows etc is a reasonable distance to help prevent this possibility A positive...

Страница 6: ...lves Figure 5 Though both are similar in function the 256 Autotrol bypass offers simplicity and ease of operation Figure 4 Autotrol Series 256 Bypass Valve Figure 5 Typical Globe Valve Bypass System D...

Страница 7: ...ain sewer line or trap Always allow an air gap between the drain line and the wastewater to prevent the possibility of sewage being back siphoned into conditioner Figure 6 Note Standard commercial pra...

Страница 8: ...f control unit Overflow line must be a direct separate line from overflow fitting to drain sewer or tub Allow an air gap as per drain line instructions Figure 6 Figure 7 Low Voltage Transformer Use on...

Страница 9: ...ition during normal use a conditioner may become fouled with organic matter or in some cases with bacteria from the water supply This may result in an off taste or odor in the water Thus your conditio...

Страница 10: ...y without dissolving before use 1 Dosage a Two grains approximately 0 1 ounce per cubic foot 2 Brine tank conditioners a Backwash the conditioner and add the required amount of hypochlorite to the bri...

Страница 11: ...hear air escaping slowly from the drain line c When all of the air has been purged from the tank water begins to flow steadily from the drain open the water supply valve all the way d Allow water to...

Страница 12: ...OCKWISE until arrow points to the center of the BRINE SLOW RINSE position d With the conditioner in this position check to see if water is being drawn from the brine tank The water level in the brine...

Страница 13: ...ow points to the actual time of day Release timer knob Note With the time of day properly set the conditioner will regenerate at about 2 30 a m If you prefer to have the unit regenerate at an earlier...

Страница 14: ...hours are indicated by a light next to the letters PM on the display window Note The use of a small needle nose pliers will aid in moving the jumper Note The unit is factory set to regenerate at 2 00...

Страница 15: ...he Suggested Salt Dial Settings table Return the jumper to the top set of pins next to the word TIME and replace the access door The jumper must NOT be left on any pins other than the top pair next to...

Страница 16: ...are as follows Salt Dial Adjustment These models may be adjusted to produce maximum to minimum conditioning capacities by setting the salt dial which controls the amount of salt used per regeneration...

Страница 17: ...mal liquid level Do not overload the brine tank with salt Guest Cycle Manual Regeneration When abnormally high water usage exhausts your water conditioner s capacity ahead of schedule an extra regener...

Страница 18: ...clean 6 Using a needle nose pliers pull injector straight out 7 Flush water into the injector screen recess of the valve body to flush debris out through the injector recess 8 Clean and flush the inje...

Страница 19: ...19 Replacement Parts for Autotrol Brand 255 Control Valve Body 19 21 18 6 5 4 3 2 1 7 8 9 10 11 12 7 16 15 13 23 22 22 23 21 21 22 17 22 inlet outlet drain 20 14 Tank Adapter Module...

Страница 20: ...1000214 No 13 4 1 gpm 15 5 Lpm 1000215 No 14 4 8 gpm 18 2 Lpm 7 1030502 Ball Flow control 2 8 Brine Refill Control 1 1034261 1 to 10 lbs Salt 1034263 3 to 19 lbs Salt 9 Injector Assembly with O Rings...

Страница 21: ...es not use Flow Control Ball 1030502 21 1001404 O Ring Group Tank Adapter 1010117 1 1010407 1 1010410 4 22 1040459 O Ring Group Piping Boss 1010431 1 1010411 2 23 1041010 13 16 Rubber Insert Optional...

Страница 22: ...9AM 6AM 3AM NOON MID NIG HT BACKWASH START CONDITIO NED WATER FAST RINSE REFILL BRIN E DAY SLOW RIN SE 440i 460i Meter Adapter Piping Boss 256 Bypass Valve Note Do not use pipe joint compound when thr...

Страница 23: ...ch BSPT Brass 3 8 inch BSPT Drain 1040282 1 inch BSPT Brass 1 2 inch BSPT Drain 1040279 3 4 inch NPT Noryl 1 2 inch NPT Drain 1040280 1 inch NPT Noryl 1 2 inch NPT Drain 1040283 3 4 inch BSPT Noryl 1...

Страница 24: ...C Tube Adapter Kit 1 1001615 25 mm CPVC Tube Adapter Kit 1 1001769 3 4 inch NPT Plastic Pipe Adapter Kit 1 1001603 1 inch NPT Plastic Pipe Adapter Kit 1 1001604 3 4 inch BSPT Plastic Pipe Adapter Kit...

Страница 25: ...resin or other debris a Remove brine control to clean ball and seat b Check all connections in brine line for leaks Refer to instructions c Clean drain control 2 Flowing or dripping wateratdrain or br...

Страница 26: ...er Manually position control to brine slow rinse to clean controller after so doing position control to purge to remove brine from tank 3 Intermittent or irregular brine draw a Low water pressure b De...

Страница 27: ...ousing c Remove meter housing free up turbine and flush with clean water Turbine should spin freely If not replace meter Contact dealer d Replace meter cable Contact dealer 2 Continuous regeneration C...

Страница 28: ...Copyright 2007 General Electric Company Printed in the USA P N 1018075 Rev L For service or parts please contact your local professional water treatment dealer...

Отзывы: