1200-2000 Series Fire Panels, Repeaters, and Emulators 
Interconnection and Wiring Guide 

10

3.3 

Sounder board connections 

Figure 5: Location of jumpers on sounder board 

 

1. 

Sounder board 

2. 

Programmable relays (A = OUT8, B = OUT7, C = OUT6, D = OUT5) 

3. 

Fault routing (OUT4) 

4. 

Fire protection device (OUT3) 

5. 

Fire routing device (OUT2) 

6. 

Fire alarm device (OUT1) 

7. 

General input (IN8) 

8. 

Fault routing fault input (VdS mode only) (IN7) 

9. 

Fire protection fault input (VdS mode only) (IN6) 

10. 

Fire routing feedback input (VdS mode only) (IN5) 

Содержание 1200 Series

Страница 1: ...GE Security 1200 2000 Series Fire Panels Repeaters and Emulators Interconnection and Wiring Guide...

Страница 2: ...E software supplied with GE products is proprietary and furnished under license and can be used or copied only in accordance with the license terms THE ENCLOSED PROGRAM IS FURNISHED SUBJECT TO THE TER...

Страница 3: ...nded cable 8 3 2 Loop card connections 8 3 3 Sounder board connections 10 3 4 Auxiliary input connections 15 3 5 Power supply connections 16 3 6 Network connections 22 3 7 Null modem cable 25 4 First...

Страница 4: ...used in this document Menu items and buttons Bold Emphasis of an instruction or point special terms Italic File names path names windows panes tabs fields variables and other GUI elements Titles of b...

Страница 5: ...a domestic environment WARNING 2 1 About this document This manual explains how to install 1200 and 2000 series analogue addressable fire panels repeaters and emulators The manual is intended as a gu...

Страница 6: ...000 series panels 1 FEP board 2 Power supply board 3 Loop card 4 Sounder board 5 Programmable relays 6 Fault routing 7 Fire protection 8 Fire routing 9 Fire alarm devices 10 General input 11 Fault rou...

Страница 7: ...2 Power supply board 3 Loop card 4 Sounder board 5 Programmable relays 6 Fault routing 7 Fire protection 8 Fire routing 9 Fire alarm devices 10 General input 11 Fault routing return input 12 Fire pro...

Страница 8: ...le Twisted and screened cable is required for all installation cabling The cable screen should be connected to the earth stud in the panel 3 2 Loop card connections Connect the loop card as shown belo...

Страница 9: ...d Wiring Guide 9 3 2 1 Loop Class and jumper selection Figure 4 Location of loop card jumpers for loop Class selection A Jumper selection for up to 2 x Class A loops B Jumper selection for up to 4 x C...

Страница 10: ...on sounder board 1 Sounder board 2 Programmable relays A OUT8 B OUT7 C OUT6 D OUT5 3 Fault routing OUT4 4 Fire protection device OUT3 5 Fire routing device OUT2 6 Fire alarm device OUT1 7 General inpu...

Страница 11: ...onnections 1 Programmable relay 4 OUT8 2 Programmable relay 3 OUT7 3 Programmable relay 2 OUT6 4 Programmable relay 1 OUT5 5 Output 8 switched LED indication 6 Output 7 switched LED indication 7 Outpu...

Страница 12: ...rvised relay output s connection on SD2000 common I O board 1 Fault routing OUT4 Termination resistor 3k3 Polarity non reversed Active in normal position 2 Fire protection device OUT3 Termination resi...

Страница 13: ...T2 and OUT3 Output Configuration 1 Configuration 2 Comment J12 in J12 out J18 out OUT1 Sounders J13 out J13 in J19 out J2 in J2 out J18 out OUT2 Fire brigade J3 out J3 in J19 out J4 in J4 out OUT3 Fir...

Страница 14: ...EN NEN and EP operation mode these inputs have no dedicated function and are freely programmable through I O logic Figure 10 Supervised input connections 1 General input IN8 2 Fault routing fault inpu...

Страница 15: ...de 15 3 4 Auxiliary input connections FP2000 series panels only Note Figure 11 Auxiliary inputs FEP board 1 Auxiliary input 1 IN1 2 Auxiliary input 2 IN2 3 Auxiliary input 3 IN3 4 Auxiliary input 4 IN...

Страница 16: ...ction and Wiring Guide 16 3 5 Power supply connections 3 5 1 24 VDC power supply FR2000 Figure 12 FR2000 24 VDC power supply connection 1 24 VDC termination board 2 24 VDC 3 24 VDC 4 Earth 5 Charger f...

Страница 17: ...VAC power supply FP2000 Figure 13 FP2000 panels 230 VAC power supply connection 1 230 VAC 2 Live 3 Neutral 4 Earth 5 To M5 earth stud mounted on back panel 6 24 VDC power to ancillary fire panel equip...

Страница 18: ...in the distribution board This group should have a bi polar disconnect device clearly marked and only used for fire detection equipment The recommended mains cable is 3 x 1 5 mm live neutral earth Tw...

Страница 19: ...2 Neutral 3 Ground 4 Live 5 Mains switch with fuse 6 To ground stud on panel 7 Temperature compensation terminal 8 V out 9 V out 10 Transformer TRF1200 11 Power supply PS1200S77 12 V in 13 Bat 14 Bla...

Страница 20: ...er supply and fault relay connection 1 Black 2 Link 3 Red 4 12 V Batteries 5 Host CPU connection 6 BAT connection 7 V in connection 8 VR3 LCD contrast adjuster 9 Modem MOD2000 connection 10 Start up b...

Страница 21: ...lay connection Figure 17 FP1200 panel power supply fault relay connection on PS1200 board 1 Normally open NO 2 Common C 3 Normally closed NC Fault output NC Jumpers default position A J10 pins for pos...

Страница 22: ...twork interface and associated connection 1 Repeater mode selection 2 NC2011 RS485 3 Jumper J1 Termination end of line see Figure 19 4 Jumper J2 Earth connection see Figure 19 5 Channel A 6 Channel B...

Страница 23: ...e 23 Figure 19 NE2011 network extension module 1 NE2011 T Termination A side Not terminated B side Terminated S Screen A side Not earthed B side Earthed 3 6 2 Serial communication network LON2000 Figu...

Страница 24: ...Service switch 3 LON device 4 LON device 5 Data D 6 Data D 7 Termination Jumper in terminated T position serial communication port is terminated into 120 Jumper removed serial communication port is n...

Страница 25: ...1200 2000 Series Fire Panels Repeaters and Emulators Interconnection and Wiring Guide 25 3 7 Null modem cable Figure 22 DB9 panel side female to DB9 PC side female connection DB9 Direction DB9...

Страница 26: ...e unlocked when prompted during the initial start up procedure 4 2 Configuration of 2000 series panels Use the panel DIP switch located on the host power supply board to set the system protocol mode a...

Страница 27: ...6 7 8 Language group 0 to 5 and languages 0 1 2 3 4 5 OFF OFF OFF English English English English English English OFF OFF ON Dutch Holland Polish Danish Lithuanian Italian Romanian OFF ON OFF Dutch B...

Страница 28: ...on 5 1 2 Quarterly The following tasks should be performed each quarter Check the log book entries and that any necessary action has been taken Check the state of the batteries and corresponding conne...

Страница 29: ...re Panels Repeaters and Emulators Interconnection and Wiring Guide 29 5 2 Contacting technical support For assistance installing operating maintaining and troubleshooting this product please contact y...

Страница 30: ...x Class B LC1502 2 x Class A 4 x Class B With the following exceptions FP1200 00 2 x Class A 4 x Class B or 4 x Class A 4 x Class B FP1200 01 2 x Class A 2 x Class B FP1200 02 2 x Class A 2 x Class B...

Страница 31: ...NO NC terminals The maximum supervision for all supervised outputs is 5 V Output A B FP1x00 FP1216 SD1200 card FP1216EN FP1264 2xxx FP1216N FP1264N SD2000 card A 24 V 100 mA supervised 24 V 0 8 A supe...

Страница 32: ...wer 19 27 5 VDC 100 mA max Modem 5 VDC 0 1V 75mA max Battery charge 27 6 VDC 0 2 V 25 C 300 mA max Aux Power 19 27 5 VDC 100 mA max Modem 5 VDC 0 1V 75mA max Battery charge 27 6 VDC 0 2 V 25 C 1 6 A m...

Страница 33: ...Table 6 286 mA max 200 mA max 286 mA max Extra loop current 20 x LED 4 mA 80 mA 0 mA 80 mA Sounders sounder board outputs 1 4 200 mA 0 mA 200 mA Total alarm current 566 mA 200 mA 566 mA Table 8 Normal...

Страница 34: ...ry charging current maximum battery capacity 0 A 0 A Current required by system 0 6 A 1 A Available auxiliary current 3 4 A 3 A Charging current based to charge batteries up to 80 in 24 hours at 75 ef...

Страница 35: ...1200 2000 Series Fire Panels Repeaters and Emulators Interconnection and Wiring Guide 35...

Страница 36: ......