background image

Notification by Pager

11

3.

To turn Silent Arming:

q

on, press

 2

 + 

ƒ

. No system status beeps will 

sound while arming.

q

off, press

 1

 + 

ƒ

. System status beeps will 

sound from touchpad while arming.

4.

Press 

 + 

4

 + 

ƒ

 to exit the programming menus.

Adjusting the Touchpad Beeps

The frequency or pitch of chime and trouble beeps from 
each fixed display touchpad can be adjusted individually 
to a more desirable or distinct tone.

Chime and trouble beep tones sound using the default fre-
quency during, or within 15 seconds of, any button activity 
at that specific touchpad.

To change status tone pitch:

1.

Press and hold the 

 and 

0

 until you hear a steady 

tone, then release the buttons.

2.

Press and hold 

1

 to lower the pitch or press and hold 

2

 to raise the pitch.

3.

Release the button when the desired pitch is heard.

After about 10 seconds of no touchpad activity, the steady 
tone stops sounding.

Adjusting the Touchpad Display 
Brightness

You may want to change the brightness of a touchpad dis-
play based on its location in a building or room. For exam-
ple, dim the touchpad display in a bedroom or enhance a 
display near a window.

Changing the touchpad display affects only the touchpad 
currently being used.

To change touchpad display brightness:

1.

Enter the programming menus by pressing 

9

 + System Master Code.

2.

Press 

2

 + 

2

.

3.

Select a brightness level:

q

0

 + 

ƒ 

Off

q

1

 + 

ƒ 

Low

q

2

 + 

ƒ 

Medium 

q

3

 + 

ƒ 

High

4.

Press 

 + 

4

 + 

ƒ

 to exit the programming menus.

After dimming the display, pressing any button momen-
tarily returns the display to full brightness. After 15 sec-
onds without touchpad activity, the display returns to the 
set dimmed level. If an alarm occurs while the display is 
dimmed, it automatically returns to the full brightness 
level and stays that way until you disarm your system.

Notification by Pager

Your system can notify up to three different pager phone 
numbers to report system events. The installer can pro-
gram any pager to receive pages for one or more of the fol-
lowing groups:

‰

High Level Reports, which includes the following 
reports:

– Sensor alarms

– Bus failures

– Sensor Tamper

– No activity alarm

– Sensor Restores

– Fire panic

– Phone test

– Police panic

– Receiver failure

– Auxiliary panic

– Receiver jam

– Duress alarm

– Touchpad tamper

‰

Low Level Reports, which includes the following 
reports:

– Bypass sensors

– AC power fail

– Sensor Low battery

– CPU low battery

– Sensor Supervisory

– Auto phone test

– Sensor Trouble

– CPU back in service

– Phone test

– Phone Failure

– Touchpad supervisory

– Event buffer full

– Touchpad low battery
– Force armed(reports when a user bypasses sensors 
while arming system)

‰

Opening and Closing reports

‰

Latchkey Paging

Pager Messages

When an event is reported on a numeric pager, the follow-
ing information is included:

Although all three types of information can be reported on 
your pager, your pager service determines how the infor-
mation will actually appear.

S e n s o r   n u m b e r   o r   u s e r   n u m b e r

E v e n t   c o d e

L a s t   f o u r   d i g i t s   o f   c e n t r a l

s t a t i o n   a c c o u n t   n u m b e r

Содержание CONCORD Express

Страница 1: ...and Date 10 Adjusting System Sounds and Touchpad Brightness 10 Arming Your System Silently 10 Adjusting the Touchpad Beeps 11 Adjusting the Touchpad Display Brightness 11 Notification by Pager 11 Pag...

Страница 2: ...twork must comply with the applicable FCC Part 68 rules and require ments as adopted by ACTA A compliant telephone cord and modular plug is provided with this product It is designed to be connected to...

Страница 3: ...at riel l utilisateur doit s assurer qu il est permis de le raccorder aux installations de l enterprise locale de t l communication Le mat riel doit galement etre install en suivant une m thod accept...

Страница 4: ...IARY buttons for 2 seconds Send a fire alarm Press and hold both FIRE buttons for 2 seconds Arm system with No Delay 2 Code 4 or 3 Code 4 Arm system to send a Latchkey page 2 Code 6 or 3 Code 6 Bypass...

Страница 5: ...r e s s b o t h L i g h t s S y s t e m A w a y P a g e r O f f N o D e l a y p r e s s b o t h p r e s s b o t h T e s t S y s t e m W e e k l y S i l e n t S t a y D 7 0 8 B A 4 1 5 6 2 3 B y p a s...

Страница 6: ...sound the system makes dur ing a sensor test to indicate that a sensor was tested properly Status beeps are described in more detail throughout the manual Pager Notification Your system can dial the...

Страница 7: ...alarm See the section on Pre venting Accidental Alarms if you would like to be able to leave quickly when the system is armed To stop sirens and cancel an alarm When an alarm condition occurs disarmin...

Страница 8: ...rm to 2 STAY Using the Chime Feature Turning on the Chime feature is like having bells on every protected door and window When this feature is on sirens and speakers sound 2 beeps whenever anyone open...

Страница 9: ...won t set off an alarm Likewise upon returning to your home or business you ll need enough time to open the door and get to a touchpad to disarm the system The Exit Delay is a period of time long enou...

Страница 10: ...order to do this Arming to Level 2 or 3 with No Delay 1 Close all perimeter doors and windows 2 Exit the premises if arming to Level 3 AWAY 3 Enter 2 Code or 3 Code The system sounds two or three sho...

Страница 11: ...entered a valid access code and a valid sensor number i You cannot bypass sensors directly using a keychain touchpad Bypassing a Sensor Indirectly Use this method if you are arming the system and woul...

Страница 12: ...ither by a sensor or panic button activation Each type of alarm sounds and reacts differently when activated as described in the fol lowing table Panic Alarms Panic alarms are easily activated from an...

Страница 13: ...odes confidential and delete extra codes as soon as they are no longer needed We recommend that you avoid using obvious code patterns such as 1234 or 1111 2222 etc Using the Programming Menus Some sys...

Страница 14: ...e as 6 digits mm dd yy then press 4 Press 4 to exit the programming menus Adjusting System Sounds and Touchpad Brightness Arming Your System Silently Use the Silent Arming feature to arm your system w...

Страница 15: ...ming menus After dimming the display pressing any button momen tarily returns the display to full brightness After 15 sec onds without touchpad activity the display returns to the set dimmed level If...

Страница 16: ...ime a user arms the sys tem 222 for Level 2 or 333 for Level 3 and the user code entered See Notification by Pager for more information on pag ing reports Latchkey Paging The Latchkey paging feature a...

Страница 17: ...the No Activity feature is currently available to you and the dura tion of the No Activity setting If the feature is not cur rently available to you contact your installer Using the Panel Download Fea...

Страница 18: ...ST OK or ZONES ALL TESTED 6 Disarm to Level 1 to exit Test Mode Phone Communication Test The purpose of this weekly test is to verify that the con nection between the central monitoring station and yo...

Страница 19: ...sor Open the secured door or window q Zones nn OK q SENSOR nn OK Smoke detector Press and hold the test button until the system sounds transmission beeps q Zones nn OK q SENSOR nn OK Motion detector A...

Страница 20: ...rected trouble beeps and messages start again 4 to 10 hours later To stop trouble beeps Perform a system status check by pressing on a touchpad Change the arming level Table 2 describes the conditions...

Страница 21: ...sor as described in Sensor Test 2 If testing the sensor does not clear the trouble condition call your security dealer for service SENSOR XX LOW BATTERY A sensor has a low battery 1 Disarm the system...

Страница 22: ...r it is a hardwired sensor HW wireless sensor WL or touchpad TP User Codes The tables below provide space for you to record user codes and the attributes of each If you would like the Latchkey attribu...

Страница 23: ...L o c k k e y t o I n c r e a s e t h e a r m i n g l e v e l A r m t h e s y s t e m t o L e v e l 3 w i t h n o E x i t o r E n t r y d e l a y P r e s s b o t h a t o n e t i m e t o C r e a t e a...

Страница 24: ...nd a No Activity report to the Central Station q No My system setup does not include this fea ture System Information Door Door Location Entry Dela y Exit Dela y 1 2 3 4 5 Feature My system features i...

Страница 25: ...from their installed location Sensors may not warn in time when fires are caused by smoking in bed explo sions improper storage of flammables overloaded electrical circuits or other hazardous conditi...

Страница 26: ...s no substitute for insurance 7 Security systems and devices cannot compensate you for life or property losses If Your System Needs Service If you have any questions about your security system or if i...

Страница 27: ...when the touchpad displays REG CODE 02 5 Enter the new code and press 6 Press B BYPASS on off appears q Press 1 to turn the option off for this user code q Press 2 to turn the option on for this user...

Страница 28: ...eature is on Allows dealer to make changes to the system from off site System Tests A user attribute that when on allows the user to enter test mode by pressing code Phone Test code Sensor Test Direct...

Страница 29: ...ode Direct Bypassing for User 00 1 0 0 0 1 1 Off or 2 On System Tests for User 00 1 0 0 0 2 Change User code 01 1 0 0 1 0 4 digit code Direct Bypassing for User 01 1 0 0 1 1 1 Off or 2 On System Tests...

Страница 30: ...0 1 2 1 1 Off or 2 On System Tests for User 12 1 0 1 2 2 Change User code 13 1 0 1 3 0 4 digit code Direct Bypassing for User 13 1 0 1 3 1 1 Off or 2 On System Tests for User 13 1 0 1 3 2 Change User...

Страница 31: ...3 4 5 6 16 20 Lights i M Memory failure 17 N No Activity Feature 13 20 No delay i 6 O opening doors or windows 1 4 6 13 P Pager Notification 2 11 12 20 Panic alarms 1 8 15 Phone Communication Test i 1...

Страница 32: ...Notes 28 Notes...

Отзывы: