![GDZX ZX2670A Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/gdzx/zx2670a/zx2670a_manual_571831006.webp)
- 5 -
3. The interface of remote control and PLC
The series of tests can be equipped with remote control stick,as long as received
(CONTROL)port,can realize the machine startup or reset control;and can also connected to the
button through the corresponding terminal of the PLC interface on the machine,it can realize the
machine startup or reset control.
4. High voltage warning lamp function
This series of safety tester using a bright red LED indicator to ensure the safety of the
operator.This indicating lamp isn’t bright when the tester start testing but the output voltage is lower
than the settled voltage,the indicating lamp will bright when the output voltage is higher than the
settled voltage,even if the tester in stop state,if the the output voltage of high voltage output port is
greater than the set voltage the indicator light will be lit,to warn of a high pressure,it should not
touch any objects of the H.V output port,to prevent electric shock.
Ⅲ、
Technical Parameters
1. Model function comparison table
ZX2670A The maximum output voltage of AC withstand voltage tester is 5kV,The maximum
testing current of AC withstand voltage tester is 20mA
ZX2671A The maximum output voltage of AC and DC withstand voltage tester is 10kV,The
maximum testing AC current is 20mA ,DC current is 10mA
ZX2671B The maximum output voltage of AC and DC withstand voltage tester is 10kV,The
maximum testing AC current is 50mA ,DC current is 20mA
ZX2671C The maximum output voltage of AC and DC withstand voltage tester is 10kV,The
maximum testing AC current is 100mA ,DC current is 20mA
ZX2672A The maximum output voltage of AC and DC withstand voltage tester is 5kV, The
maximum testing AC current is 20mA ,DC current is 10mA
ZX2672B The maximum output voltage of AC withstand voltage tester is 5kV, The
maximum testing current of AC withstand voltage tester is 100mA
ZX2672C The maximum output voltage of AC and DC withstand voltage tester is 5kV,The
maximum testing AC current is 100mA ,DC current is 20mA
ZX2672D The maximum output voltage of AC and DC withstand voltage tester is 5kV,The
maximum testing AC current is 200mA ,DC current is 20mA
ZX2674A The maximum output voltage of AC and DC withstand voltage tester is 20kV,The
maximum testing AC current is 20mA ,DC current is 10mA
2. Model parameter comparison table