background image

T E C H N O L O G I E S

E:

 [email protected]   

T: 

0113 286 0166   

F:

 0113 287 8178 

GDS TECHNOLOGIES LTD 

|

 FUSION POINT 

|

 ASH LANE 

|

 GARFORTH 

|

 LEEDS 

|

 LS25 2GA  

|

 UK

 

www.gds-technologies.co.uk

This document is not contractual and the equipment specification may be modified at any time without prior notice.

Note:  EOL (End of Line Resistor - 3K9)
 

CLR (Current Limiting Resistor -1K5)

For addressable sensors use 4~20mA input sensors 171-400 / 168-400 / 170-400

Technical Sheet

ref C1694A

+ve In

+ve Out

_ve In/Out

Fit EOL Resistor 4K7

W

Y

P

+

Sig

0v

Fit CLR1K5 

Direct sensor 

input terminals

Fit reset switch for the sensor

24v DC

+ve Out

_ve In/Out

Fit EOL Resistor 4K7

+ve Out

_ve In/Out

+ve Out

_ve In/Out

+ve Out

_ve In/Out

+ve In

+ve In

+ve In

+ve In

Last sensor

Connecting more than one sensor

Fit CLR1K5 

W

Y

P

+

Sig

0v

SENSOR SPECIFICATION CSD-2

Operating Voltage Range  .................................................................................... 9 - 30 VDC (Nom.12/24VDC)
Average current consumption in quiescent state ..................................................... < 50μA
Alarm state current............................................................................................... 18 mA / 9V; 29mA / 12V; 32mA/ 15V
Class (for the heat part, in accordance with EN54-5/7) .......................................... A1/R
Protected area (in accordance with EN54-5/7)....................................................... up 120m²
Installation height (in accordance with EN54-5/7) .................................................. up 16m
Output in alarm state at terminal RI 

(Towards terIN /+OUT/)

 .................... 20mA (max)/ -3.3V

Degree of protection ............................................................................................ IP30
Wire Gauge for terminals ..................................................................................... 0.4mm2 ё 2.0mm2
Operational temperature range ............................................................................ -10 C ё +60 C
Relative humidity resistance .................................................................................. (93 ± 3)% @ 40 C
Dimensions (incl. base) ........................................................................................ ø102mm, h 48mm
Weight (incl. base) ............................................................................................... 160g

CONNECTION DETAIL FOR GDS ALARM PANELS

Отзывы: