GASMAX EC Operation & Maintenance Manual, Revision 3.5
Page 32
Figure 7-8: DIAGNOSTICS MENU
OUTPUT SIM ULATION
allows setting the 4-20mA output to virtually any desired value. This is useful
for checking responses of devices receiving the GASMAX EC’s 4-20mA output.
RELAY TEST
is not supported on a GASMAX EC.
WARNING
:
GAS MONITORING AND ALARM PROCESSING ARE NOT PERFORMED WHILE USING THE
DIAGNOSTICS MENUS. ACCESS REQUIRES A SPECIAL KEY SEQUENCE OF FOUR CONSECUTIVE UP
KEYSTROKES.
SYSTEM SECURITY Page
The System Security menu offers two levels of protection against operation by unauthorized personnel or
those with malicious intent.
Figure 7-9: SYSTEM SECURITY MENU
CONTACT NAM E
is a 12 character ASCII field available for displaying a phone # or name of personal who
knows the Pass Code. Lost Pass Codes may be recovered by entering the locked security menu and
holding the UP key for 5 seconds. The 4-digit code appears near the bottom of the screen.
SECURE LEVEL
sets LOW, HIGH or OFF modes. A LOW level allows CAL MODE sensor calibrations but
requires the 4-digit Pass Code prior to altering menus. HIGH level locks the entire menu database and the
CAL Mode until the correct Pass Code is entered. LOW and HIGH security levels always allow static
viewing of configuration menus.
* * * WA R N I N G * * *
A l a r m p r o c e s s i n g w i l l
b e h a l t e d d u r i n g
d i a g n o s t i c mo d e !
E D I T t o c o n t i n u e .
A n y o t h e r k e y t o e x i t .
D I A G N OS T I C S
O u t p u t S t i mu l a t i o n
R e l a y T e s t
OU T P U T S T I MU L A T O R
Ou t p u t 4 . 0 mA
E D I T t o c h a n g e .
N e x t t o e x i t .
EDIT
A C T I V A T E R E L A Y S
R e l a y 1 OF F
R e l a y 2 O F F
R e l a y 3 O F F
S Y S T E M S E C U R I T Y
C o n t a c t N a me
S e c u r e L e v e l L OW
P a s s C o d e
U n l o c k e d