CHV Mini VRF 50/60Hz
4. Error Code Table
Fault Code
Fault Contents
Remarks
E1
Outdoor unit phase sequence fault
E2
Communication fault between indoor unit and outdoor unit
20-minute break at first or 2-minute break later
E4
T4 ambient temperature sensor fault
E6
T3 condenser pipe temperature sensor fault (outlet)
E8
TP exhaust temperature sensor fault
E9
AC over-voltage / under-voltageprotection
E10
EEPROM fault
EA
T3B condenser temperature sensor fault (middle)
Eb
Reserved
EC
T7/TS refrigerant cooling pipe inlet temperature sensor fault
E.E
Model error(there is no dialing model in the EEOPROM)
H0
Communication fault between master chip and DSP
H4
Display P6 (IPM module protection) for 3 times within 30 minutes
H5
Display P2 (Low pressure protection) for 3 times within 30 minutes
20-minute break at first or 2-minute break later
H6
Display P4 (TP Exhaust temperature protection)
for 3 times within 100minutes
Only restore after power on again
H7
The decrease in quantity of indoor unit
Indoor units are lost for more than 3 minutes. It
can't be restored until quantity of indoor units
are restored.
H9
Display P9 (DC fan protection) for 2 times within 10 minutes
Only restore after power on again
H10
Display P3 (Overcurrent protection) for 3 times within 60 minutes
Only restore after power on again
H11
Display P13 protection for 2 times within 10 minutes
Only restore after power on again
H12
Display Pb protection for 3 times within 60 minutes
P1
High pressure protection
P2
Low pressure protection
P3
Overcurrent protection
P4
Exhaust overheating protection
P5
T3 or T3B condenser pipe overheating protection
P6
IPM protection
P9
DC fan fault
P10
Anti-typhoon protection
P11
T2 high temperature protection when in heating mode
P12
T3 overheating protection
P13
Current detection error protection
Effective for 12.5, 14,16, 18kW; no such fault for 8
and 10kW
L0
DC compressor module fault
L1
DC low voltage protection
L2
DC high voltage protection
L4
MCE fault / synchronous / closed loop
L5
Zero speed protection
L6
Reserved
L7
Compressor phase loss protection
L8
Protection when the speed change at the previous moment and the
latter moment is greater than or equal to 15Hz
L9
Protection when the difference of set speed and actual operation
speed is greater than or equal to 15Hz
Pb
Refrigerant cooling module temperature is too high
Содержание CHV Mini Series
Страница 1: ...Commercial AirConditioners Service Manual R410A Series...
Страница 3: ...CHV Mini VRF 50 60Hz 2 202105 CHV Mini Series ServiceManual...
Страница 13: ...CHV Mini VRF 50 60Hz 12 202105 CHV Mini Series ServiceManual...
Страница 109: ...108 202105 CHV Mini Series ServiceManual CHV Mini VRF 50 60Hz 1 ExplodedViews...