16/36
EN
14. TECHNICAL DATA
CONNECTION VALUE
Power supply
220-250V AC. 50 Hz, 5 VA
Fuse
315 mA carrier
i
Defect fuses are only allowed to be replaced by the
manufacturer.
INPUTS
Signalling
potential free, mechanic contacts according to DIn 19234
(NAMUR)
Effective direction
NC (see Chapter 3)
Connection technique
2 wire
Supply of the signalling
10 V Max. through the instrument, 10mA Max. (short-circuit
proof)
OUTPUT (COLLECTED ALARM)
Alarm output
2* relay output (1 changing contact)
Max. contact load AC
230 V -, 50 Hz, 100 VA
Max. contact load DC
48 V, 1A
Buzzer
85 dB/0,1 m, 2,3 khz
INTERN ALARM EQUIPMENT
Luminous alarm
LED red, green 5 mm Ø
Acoustic alarm
signalling device, f = 3,3 kHz
ENVIROMENT CONDITIONS
Environment temperature
40° C - C Max.
Humidity
0 - 95% relative humidity, not condensated
EXECUTION
Housing
polystyrene, colour similar to RAL 7035 (grey)
Protection type
IP 54
Dimension
200 x 160 x 60 mm (w x h x d)
Installation position
upright, out of ex-range
Connection cross-section
2,5 mm
2
Max.
Cable screws
4 items PG11
Содержание DGM-SK02