Special application modes
In W0202 module simple applications have been built which can be used to control building
devices. The applications make logic between signal from Special Input and control Digital
Output state. Relation between Inputs and Outputs is shown in the table below and it cannot be
changed.
Special Input
Digital Output
SI1
DO1
SI2
DO2
Table 26 Built in application relation between input and output
The Special Inputs can be set to work in different modes. There are dedicated registers for
operation mode (40176, 40180), time parameters (40177, 40181), setpoints for heating/cooling
modes (40178, 40182), and for differential value in heating/cooling modes (40179, 40183).
Register
Description
40176
Input S1 OPERATION MODE
40177
Input S1 TIME VALUE
40178
Input S1 SETPOINT
40179
Input S1 DIFFERENTIAL
40180
Input S2 OPERATION MODE
40181
Input S2 TIME VALUE
40182
Input S2 SETPOINT
40183
Input S2 DIFFERENTIAL
Table 27 List of registers dedicated for special application mode