 2. SPECIFICATIONS 

 

 Supply voltage  

MD-2, MD-4   - 230V AC, 50Hz (allowed voltage fluctuations: +10%,-14%) 
MD-2.A, MD-4.A  - 12V DC ( allowed: 10.5V ÷ 13.8V=) 

 Power consumption  

max. 15W   (MD-...A : max 12W) 

 Operating temperature 

 +5

C to 35

C

 

recommended optimal,

 -10

to 

+40

allowed constantly

-15

 C to 45

C

 

allowed periodically (<2h/24h) 

 Number of measurement  
 channels  

2

, two-threshold detectors

 

( MD-2... )

 

4

, two-threshold detectors

 

( MD-4... ) 

 Alarm thresholds 

two:

  warning - 

ALARM 1

 ( 

A1 

),  alarm - 

ALARM 2 

A2 

 Alarm memory  

for each channel and each level - optical, joint acoustic, 

output signal memory 

of

 

each level – optical (possibility to deactivate 

with W2 function switch „BEZ PAM.”) 

 Memory resetting  

using button on front plate (accessible when cover lifted) 

 Signal interlock  

inputs: approx. 

60 

s, after turning the power on; 

outputs: approx. 

20

 s (delay), possibility of permanent interlock (service 

mode) using W2 function switch „SERWIS” 

 Optical indication (for each 
 detector and output) 

A1 

– red LED – 1st gas concentration threshold exceeded  

A2 

- red LED – 2

nd

 gas concentration threshold exceeded 

 Acoustic indication  

internal piezoceramic siren (intermittent signal = module requires 
servicing), volume: approx. 60dB/1m; 
possibility of shutting down (using W2 function button „CISZA”) 

 Supplying power to sensors  9V DC, short-circuit- and overcurrent-protected 200mA 
 Failure indication 

yellow LED   

 Detector power on indicator  green LED (separate for each detector), overload indication 
 Quick release of output  
 signals  

manual, using „TEST” button under terminal strip cover, simultaneous for 
both thresholds  

 Unit powering control  

 green LED; indicates also heating state  

 Contact outputs 

NC and NO for 

A1, A2

, voltage-free; 

current-carrying capacity:  max. 4A (with resistance load) or max. 2A (with 
inductive load -motors) or max. 0.6A (with purely inductive load – 
fluorescent lamps); max. 250V AC or 24V DC; 
NO and NC for 

AWARIA 

(FAULT)

, voltage-free, 

current-carrying capacity:  max. 4A (with resistance load) or max. 2A (with 
inductive load); max. 30V AC or 24V DC 

 Voltage outputs  

 

12V DC , not stabilized  for A1 and A2 states, total load = max. 0.3A, for 
connection of SL..., S-3, LD... signalling devices 

 

12V DC continuous, not stabilized, for powering MDX module or other 
devices, max. load 0.2A 

 Alarm inputs 

12V DC voltage inputs (5÷ 16V, max. 20mA) for A1, A2; 
instantaneous, galvanically isolated from other MD circuits; 
for cascade connection of modules or other devices 

 Overload protections 

fuse of primary 230V AC or 12 V DC supply circuit, self-resetting fuses with 
shorting current limitation of NAP.12V outputs, electronic fuses with current 
limitation for each detector  

 Dimensions, weight 

215 x 240 x 115

 mm, (H x W x D in mounting positions); approx. 1.5kg 

 Housing 

ABS, 6 cable glands,

 IP54

,  3-point mounting 

 

MD-2(4).( A ) Control Unit, User’s Manual   edition 2U3en    

gazex’2011  v1108               

Page  

3

 /14 

 

Fig.2. Required mounting area 
 
Template for hole 
drilling is located 
on cardboard box lid. 

 

 

 

~ 2

40

min

im

um

Mounting space

198

~1

20

13

7

 

21

5

Cable mounting space

Mounting

holes

240

12

0

Top view

Содержание MD-2

Страница 1: ...ontrol Unit User s Manual edition 2U3en gazex 2011 v1108 Page 1 14 1 Application and compatibility table page 2 2 Specifications 3 3 Description and connection of MD in the system 4 4 Installation of MD 7 PROBLEM Helpful tips 10 5 Maintenance operation 10 Periodical Inspection Protocol 12 PRODUCER PRODUCER gazex 2011 All right reserved Reproducing and copying of this manual in whole or part withou...

Страница 2: ...etectors allows continuous 12V DC power supply for additional devices MDX terminal allows operation with additional modules cascade wise through alarm input galvanically isolated 12V voltage alarm outputs supply power to additional acoustic and optical signalling devices contact outputs galvanically isolated from the system control fans motors contactors and information boards EMERGENCY contact ou...

Страница 3: ... detector overload indication Quick release of output signals manual using TEST button under terminal strip cover simultaneous for both thresholds Unit powering control green LED indicates also heating state Contact outputs NC and NO for A1 A2 voltage free current carrying capacity max 4A with resistance load or max 2A with inductive load motors or max 0 6A with purely inductive load fluorescent l...

Страница 4: ...Ah or 17Ah PS 3 POWER SUPPLY 230V AC 12V DC power supply connection Other conections as above Cascade connection of units MD UNIT No n UNIT No n 1 main MD 12V WEJŚCIA ALARMOWE WYJ NAP 12V A1 A2 ALL SERIES A1 A2 UNIT No n 1 M M DETEKTORY 01 02 19 20 21 15 16 17 18 N L MD 2 A 1A PE 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 1 1 2 3 ...

Страница 5: ...ly ALARM1 and ALARM2 Output State lamps are on external alarm green ZASILANIE MODUŁU MODULE POWER and ZASILANIE POWER lamps of active detectors are on FAULT AWARIA MD power failure no power or main fuse burnt all lamps are out FAULT AWARIA Detector power failure at least one detector with blinking ZASILANIE POWER lamp and ALARM1 and ALARM2 Input State lamps on ALARM1 and ALARM2 Output State lamps ...

Страница 6: ...1 1 1 Normal A2 mem at the input temporary exceeding of A2 threshold of N detector e g detector test 0 1 0 0 1 1 0 1 0 ALARM 1 A1 alarm of N detector 0 1 1 0 1 1 0 Normal A1 mem at the output stored A1 state of N detector at the outputs 0 1 1 0 0 1 1 0 0 ALARM 1 external A1 alarm in progress 0 1 1 0 x x x Normal external A1 memory stored external A1 alarm 0 1 1 0 0 x x x ALARM 2 A2 alarm of N dete...

Страница 7: ...ductor into the round opening of the terminal as far as it goes If properly inserted the cable cannot be pulled out of the terminal The cable can be released and taken out only after prior pushing the lever 3 white or grey according to the arrow 3 1 9 10 mm 2 3 8 9 mm 1 4 2 2 B Introduction of conductor into spring loaded terminal of cage type 1 Remove insulation from exactly 5 to 6 mm long sectio...

Страница 8: ...C power supply E cable from the PS power pack with battery connected observe polarity module is secured against reverse polarity Cross sectional area of E cable conductors Length of E cable 1 5 mm2 12m 2 5 mm2 20m 4 5 1 Turn on module power supply Presence of power and proper powering of circuits are indicated by lighting of green lamps and ZASILANIE POWER of the active detectors and the blinking ...

Страница 9: ...ontrol lamps to go out 4 8 5 Procedure of control of outputs can be simplified by pressing TEST button on the module terminal board and holding it pressed for a couple of seconds Immediately after the button is pressed only two Output State control lamps should light up and corresponding control signals should be present on both outputs Upon releasing the button both Output State lamps will start ...

Страница 10: ... and ALARM2 lamps and or Input State ALARM1 or ALARM2 lamps of a specific detector are permanently lit intermittent sound emitted by the internal siren green ZASILANIE POWER lamp of the specific detector is blinking green AWARIA SYSTEMU SYSTEM FAILURE lamp is on overload above 200mA or shorting of power circuit of the specific detector remove the cause of the short circuit or the line overload tur...

Страница 11: ...r the system configuration etc 5 2 During operation do not use mobile phones radiophones or other sources of strong electromagnetic field in direct vicinity of MD as their use may cause interference in operation of MD or false alarm states CAUTION IMPORTANT 5 3 All results of each system inspection performed according to 4 8 of this manual events when A2 state was activated including actions taken...

Страница 12: ... fill in the table before System installation DEVICE type VERSION calibration SERIAL NUMBER REMARKS location The protocol includes five numbered sheets with gazex logo on the reverse side DETECTOR SYSTEM START UP DATE of the start up Time Remarks on the system components Remarks on place or method of installation Actions taken Started up by full name Signature 01 02 MD 2 4 A Control Unit User s Ma...

Страница 13: ... Time DETECTOR No state RESPONSE OTHER symptoms valve condition Actions taken Legible signature of the inspector full name 1 2 3 4 5 6 7 8 MD 2 4 A Control Unit User s Manual edition 2U3en gazex 2011 v1108 Page 13 14 ...

Страница 14: ...MD 2 4 A Control Unit User s Manual edition 2U3en gazex 2011 v1108 Page 14 14 ...

Отзывы: