I. Overview

handheld 1000A AC clamp meters, designed in

accordance to EN61010-2010 and CAT III 600V/CAT II 1000V,

with full-featured protection ensuring users a safe and reliable 

measurement experience. These meters have multiple 

functions such as basic electric measurement, inrush current 

measurement , high-accuracy current measurement, etc. 

G9204-II is ideal measurement tools in electric fields. 

II. Features

1) Lightweight and compact.

2) Full-featured false detection protection for up to 600V (30kVA) 

    energy surge, overvoltage and overcurrent alarm functions.

3) Auto ranges for current include 60A, 600A, 1000A, frequency 

    response is up to 45Hz~1kHz, G9204-II has inrush current 

    measurement function.

4) Large capacitance measurement (60nF~60mF), fast ADC 

    (3 times/s), response time for capacitance measurement: 

    less than 6s for 

1mF; about 8s for 

60mF.

5) Overvoltage and overcurrent alarm function.

6) The circuit has an automatic power saving function, the 

    consumption in sleep state is <20uA, which effectively extends 

    the battery life to 200 hours.

Warning: Before using the meter, please read the Safety 

Information carefully.

III. Accessories

Open the package box and take out the meter. Please double 

check whether the following items are missing or damaged.
1. User manual ----------------------------- 1 pc

2. Test leads

1 pair

 --------------------------------- 

3. K-type temperature probe

1 pc

 ------------ 

4. Carrying bag

1 pc

 ----------------------------- 

If any of the above is missing or damaged, please contact your 

supplier immediately.

IV. Safety Information

The meter is designed in accordance with IEC/EN61010-1, 

61010-2-032 and electromagnetic radiation protection EN 61326-

1 safety standards, and conforms to CAT III 600V, CAT II 1000V, 

double insulation and pollution grade II. In case the meter is 

not used according to the operating instructions, the protection 

provided by the meter may be compromised or lost.

1. Before use, please check if there is any item which is damaged 

    or behaving abnormally. If any abnormal item (such as bare 

    test lead, damaged meter casing, broken LCD, etc.) is found, 

    or if the meter is considered to be malfunctioning, please do 

    not use the meter. 

2. Do not use the meter if the rear cover or the battery cover is 

    not covered up, or it will pose a shock hazard!

3. When using the meter, your fingers must be placed behind 

    the finger guard ring of the test leads. During measurement, 

    do not touch exposed wires, connectors, unused inputs, or 

    circuits being measured to prevent electric shock.

4. The function switch should be placed in the correct position 

    before measurement. It is forbidden to change the position 

    during measurement to avoid damage to the meter!

5. Do not apply voltage over 1000V between any meter terminal 

    and earth ground to prevent electric shock or damage to the 

    meter.

6. Be cautious when the measured voltage is higher than 60V 

    (DC) or 30Vrms (AC) to avoid electric shock!

7. Never input voltage or current which exceeds the specified 

    limit. If the range of the measured value is unknown, the 

    maximum range should be selected. Before measuring the 

    resistance, diode and continuity online, switch off the power 

    supply of the circuit, and fully discharge all capacitors to avoid 

    inaccurate measurement.

8. When the “      ” symbol appears on the LCD, please replace 

    the batteries in time to ensure measurement accuracy. If the 

    meter is not in use for a long time, please remove the batteries.

9. Do not change the internal circuit of the meter to avoid damage 

    to the meter and user!

10. Do not use or store the meter in high temperature, high 

      humidity, flammable, explosive and strong magnetic field 

      environments.

11. Clean the meter casing with a soft cloth and mild detergent. 

      Do not use abrasives or solvents!

V.Electrical Symbols

Description

Description

High voltage hazard

AC
DC

Double insulated
Grounding
Warning

Symbol

Symbol

VI. General Specifications

1. Max display: 6099

2. Polarity display: Auto

3. Overload display: “OL” or “-OL”

4. Low battery indication: The “       ” symbol is displayed.

5. Low battery shutdown prompt:  The “Lo.bt” interface appears on 

    the LCD and lasts for about 10s, the buzzer beeps three times, 

    and the meter automatically shuts down.

6. Test position error: If the source under test is not placed at the 

    center of the clamp jaws when measuring current, ±2.0% additional 

    error in reading will be produced.

7. Drop protection: 1m

8. The maximum size of jaw opening: 48mm in diameter

9. The maximum size of conductor to be measured: 45mm in diameter

10. Battery: AAA battery 1.5V×2

11. Auto power off: If there is no operation of the function switch or 

      any button for 15 minutes, the meter will automatically power off. 

      This function can be turned off as needed.

12. Dimension: 242mm×76.5mm×52mm

13. Weight: About 235g (including batteries)

14. Altitude: 2000m

15. Operating temperature and humidity: 0°C~30°C (

80%RH), 

      30°C~40°C (

75%RH), 40°C~50°C (

45%RH)

16. Storage temperature and humidity: -20°C~60°C (

80%RH) 

17. Electromagnetic compatibility:

RF=1V/m, overall accuracy=specified a5% of range

RF>1V/m, no specified calculation

VII.External Structure

1. NCV sensing end
2. Clamp jaws
3. Hand guard
4. Jaw opening trigger
5. Function switch
6. LCD display
7. Function buttons
8. Positive (+) input jack
9. COM (negative -) input jack

VIII.Button Description

1. SELECT Button

In the composite function position, press this button to switch between 

the corresponding measurement functions; in current measurement

 function position, long press this button (about 2s) to enter INRUSH 

measurement function, short press to refresh the current reading, 

long press again to exit INRUSH measurement function.

2. HOLD/LIGHT Button

a). Short press this button to enter or exit the data hold mode.

b). Long press this button (about 2s) to turn on/off the light, the light 

     will automatically turn off after 5 minutes.

3. MAX/MIN Button

Short press this button to enter the maximum/minimum measurement 

mode and long press this button to exit (only valid for AC/DC voltage, 

AC current). The meter will consecutively make beep sounds twice 

if this button is pressed in other inapplicable function positions.

4. REL/BACKLIGHT Button

1) In the voltage, current, capacitance and resistance positions, 

    press this button to store the current reading as a reference for 

    future readings. When the LCD display value is reset to zero, the 

    stored reading will be substracted from the future readings. Press 

    this button again to exit the relative value mode. The meter will 

    consecutively make beep sounds twice if this button is pressed in 

    other inapplicable function positions.2) Long press for about 1~2 

    seconds to turn on/off the backlight, the backlight will automatically 

    turn off after the backlight is on for about 1 minute.3) Long press 

    for about 3 seconds to enable the backlight to enter always-on 

    mode, long press for 

3 seconds to exit the mode.

IX.Operating Instructions

1. AC Current/Motor Inrush Current Measurement (Figure 2 & 3)

1) Select the AC current range, the meter will automatically switch 

    corresponding range (60.00A/600.0A/1000A) according to the 

    input amplitude during measurement.

2) Press the trigger to open the clamp jaws, and fully enclose one 

    conductor.

3) Only one conductor can be measured at a time, otherwise the 

    measurement method and reading will be wrong. 

Inrush current is the true 

RMS of current within 

100ms from the start of 

triggering point, the 

triggering value of inrush 

current in 600A range is 

about 6A, used to detect 

the cranking current of 

motor.

RMS (INRUSH)

AC current

Cycle

PEAK

A area

   

Warning:

 

Short circuit is not easy to occur between the clamp jaw and 

 

the measured object, but when measuring uninsulated 

 

conductor, please be careful not to cause short circuit 

 

between the uninsulated conductor and the clamp jaws.

 

The measurement is sensitive to mechanical stress to some 

 

extent, so please do not release the trigger suddenly when 

 

it is pressed, otherwise the impact will affect the reading in 

 

a short time.

 

To ensure measurement accuracy, the measured conductor 

 

must be centered in the clamp jaws (A area), if is deviated 

 

from center area (in B or C areas), ±2.0% additional error in 

 

reading will be produced.

 

When the measured current is >1000A, the meter will 

 

automatically sound an alarm.

2. AC/DC Voltage and Frequency Measurement 

1) Insert the red test lead into the signal input terminal, and the 

    black test lead into “COM” terminal.

2) Turn the function switch to AC voltage position, and connect 

    the test leads with the measured load or power supply in 

    parallel.

 

Warning:

 

Do not input voltage above 1000V (AC). Although it is possible 

 

to measure higher voltage, it may damage the meter.

 

Be cautious to avoid electric shock when measuring high 

 

voltage.           

 

When the measured voltage is >30V/AC, the LCD will display 

 

the high voltage alarm prompt “    ”.

3. Resistance, Continuity, Capacitance and Diode 

    Measurement 

1) Insert the red test lead into the signal input terminal, and the 

    black test lead into “COM” terminal.

2) Turn the function switch to the “

Ω

” position, press the SELECT 

    button to select resistance measurement, and connect the 

    test leads with both ends of the measured resistance in 

    parallel.

Capacitance
Continuity
Diode
Resistance

Red

Black

 

If the measured resistor is open or the resistance exceeds 

 

the maximum range, the LCD will display “OL”.

 

Before measuring the resistance online, switch off the power 

 

supply of the circuit, and fully discharge all capacitors to avoid 

 

inaccurate measurement.

 

If the resistance is not less than 0.5Ω when the test leads are 

 

short-circuited, please check the test leads for looseness or 

 

other abnormalities.

 

For continuity measurement, if measured resistance is <30Ω, 

 

the circuit is in good conduction status and the buzzer beeps 

 

continuously; if measured resistance is 30Ω~50Ω, the buzzer 

 

may make sounds or make no sound; if measured resistance 

 

is >51Ω, the buzzer makes no sound certainly

 

For diode measurement, “     ” polarity is needed to be 

 

distinguished, read the approximate forward PN junction 

 

voltage of measured diode directly from the display . For the 

 

silicon PN junction, the normal value is generally about 

 

500~800mV.

 

Before measuring capacitance “      ”, it is recommended to 

 

use “REL” measurement mode for capacitance 

100nF. 

 

For capacitance above uF, short-circuit the electrode of the 

 

capacitor and fully discharge all capacitors (especially for 

 

capacitors with high voltage) to avoid damage to the meter and 

 

user.

 

Do not input voltage over AC/DC 30V to avoid personal injury.

4. Temperature Measurement

1) Insert the positive pole of the temperature probe into the 

    signal input terminal and negative pole into “COM” terminal. 

2) Turn the function switch to “°C/°F” position and the LCD will 

    display room temperature.

3) Fix the temperature probe on the object to be tested, and 

    read the temperature value of the tested object directly from 

    the display after a few seconds.

Figure 1 

Figure 4

Figure 5

Figure 2

Figure 3

Red

Black

G9204 - II

1000A Digital Clamp Meter

User Manual

P/N:

G9204-II is