background image

13

FORMULA G-510 is the only cleaner recommended by Gay-
lord Industries for use in the washdown system of The Gaylord
Ventilator. FORMULA G-510 is a concentrated colloid cleaner
specially formulated to remove the daily accumulation of
grease inside The Gaylord Ventilator without damaging the
rubber and synthetic parts of the detergent pumping system.
FORMULA   G-510 is biodegradable, safe for kitchen person-
nel, and has a variety of uses.

DILUTION OF FORMULA G-510 FOR
VENTILATOR CLEANING
Normal Cleaning

For ventilators covering cooking equipment such as broilers,
griddles, fryers, or any other heavy grease producing equip-
ment, fill the detergent tank with full strength FORMULA
G-510.

Light-Duty Cleaning

For ventilators covering light grease producing equipment such
as ovens, kettles, steamers and ranges, fill the detergent tank
with a mixture of one part FORMULA G-510 to one part water.

Cleaning the Ventilator Exterior

Mix one part FORMULA G-510 to twenty parts water in hand
spray bottle. Spray on and wipe off. NOTE:  Once a day, this
same solution should be used to clean the front of the fire
damper and main grease extracting baffle.

FOR OTHER CLEANING JOBS

The colloidal action of FORMULA G-510 makes it a cleaner
especially well-suited for use in kitchens. The colloids break
up dirt and grease into millions of tiny particles that constantly
repel each other. These particles cannot recombine or rede-
posit on a surface and are, therefore, easily washed away.
FORMULA G-510 is biodegradable and contains no harsh
chemicals, yet offers outstanding performance on the tough-
est cleaning jobs.

Use a mixture of one part FORMULA G-510 to twenty parts
water for:

VINYL/PLASTIC/WALLS...Removes dirt, grease, food de-
posits and fingerprints.
REFRIGERATORS...Removes dirt, spilled milk, blood,
mildew and objectionable odors.
RESTROOMS...Add a disinfectant to clean all fixtures,
walls, floors, etc.

Use a mixture of one part FORMULA G-510 to five parts water
for extremely heavy grease build-up, such as on the floor and
on equipment around deep-fryers. Spray on and rinse or wipe
off. For extremely soiled areas, gentle agitation, followed by a
soaking period, will result in more thorough cleaning.

DON’T be afraid to experiment with FORMULA G-510 because
it contains no phosphates, nitrates, enzymes, sulfates, sul-
fonates or silicates.

DETERGENT FOR THE WASH SYSTEM

LIMITED WARRANTY

G-510 CHEMICAL DIVISION warrants that FOR-
MULA G-510 will not cause cleansing agent     damage
to the rubber and synthetic parts of the injection pump
(“O” rings, diaphragms, washers, tubing, and other
such parts) used with The Gaylord Ventilator, Heat
Reclaim Unit, or Pollution Control Equipment. G-510
CHEMICAL DIVISION’S obligation under this war-
ranty and any warranties implied by law shall be
limited to repairing or replacing, at its option, any of
said parts which G-510 CHEMICAL DIVISION'S
examination shall disclose to its satisfaction to have
been damaged by the use of FORMULA G-510 for the
life of the detergent pumping system. This warranty
shall not cover damages caused by any other deter-
gent. The use of any other detergent shall void this
warranty.

All repairs and replacement parts under this warranty
shall be F.O.B. G-510 CHEMICAL DIVISION’S fac-
tory. The owner shall pay the necessary freight and
delivery charges; also      removal and installation
costs. Any federal, state or local taxes are also extra.
Requests for repairs or replacement parts should be
made to 20/10 Products Inc., PO Box 7609, Salem,
OR  97303.

This is the sole warranty with respect to FORMULA G-
510. G-510 CHEMICAL DIVISION MAKES NO OTHER
WARRANTY OF ANY KIND WHATSOEVER, EX-
PRESSED OR IMPLIED, AND ALL IMPLIED WAR-
RANTIES OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR       PURPOSE WHICH EXCEED
THE AFORESAID OBLIGATION ARE HEREBY DIS-
CLAIMED AND EXCLUDED FROM THIS AGREE-
MENT. G-510 CHEMICAL DIVISION SHALL NOT BE
RESPONSIBLE FOR INCIDENTAL OR CONSE-
QUENTIAL DAMAGES RESULTING FROM A
BREACH OF THIS WARRANTY.

IMPORTANT

If a cleansing agent other than FORMULA G-510 is used with
The Gaylord Ventilator injection pump, it is recommended that
a warranty similar to the above be obtained from the manufac-
turer of said product.

For name and address of the nearest FORMULA G-510
distributor contact:

20/10 Products Inc.
P.O. Box 7609
Salem, OR 97303
Phone: 800-286-2010
FAX:     503-363-4296
E-Mail: [email protected]

Содержание C-6000 Series

Страница 1: ...FOR THE CG3 SERIES WATER WASH VENTILATORS WITH MODEL C 6000 COMMAND CENTER 10900 S W AVERY STREET TUALATIN OREGON 97062 1149 U S A 1 800 547 9696 503 691 2010 FAX 503 692 6048 email info gaylordusa com GAYLORD INDUSTRIES EFFECTIVE DATE 04 2005 ...

Страница 2: ...ase refer to the corresponding supplementary equipment manuals If you have further questions please visit our web site at www gaylordusa com or call us toll free at 1 800 547 9696 We are more than happy to help Sincerely Gaylord Industries STREET ADDRESS 10900 S W Avery Street Tualatin Oregon 97062 8549 U S A PHONE 503 691 2010 800 547 9696 FAX 503 692 6048 email gaylord gaylordusa com www gaylord...

Страница 3: ...LCABINET 34 MODELGPC 6000 SSERIESCONTROLCABINET 35 OPTIONALCONTINUOUSCOLDWATERMIST 36 MODELC 6000ORC 6000 ASERIESCONTROL 37 MODELC 6000 BSERIESCONTROL 38 DAMPERCONTROLMOTORANDCG3 FDLWIRING 39 DETERGENTPUMP 40 MISCELLANEOUSVENTILATORPARTS 41 WIRINGDIAGRAMS 42 49 STANDARDVENTILATORMODELS 50 METRICCONVERSIONCHART 51 START UPINSPECTIONREPORT 52 LIMITEDWARRANTY Insidebackcover TABLE OF CONTENTS Patent ...

Страница 4: ...collar and there is a single thermostat toactivatethefiremodeinthecontrolcabinet and ventilator No Belimo One Thermo stat CG3 ND Inlet damper is fixed No Fire Damper at duct collar A bracket Fire Damper Lockout has been added to show that the damper will not close to the fire position No Damper motor No Thermostats Summary of CG3 Ventilators The CG3 and CG3 FDL are very similar Both have a damper ...

Страница 5: ...5 CG3 VENTILATOR DESCRIPTIONS ...

Страница 6: ...the fire mode When the Start Fan button is pushed on the control cabinet the damper opens to the exhaust mode position 1 to become the preliminary grease CG3 SERIES VENTILATOR PRINCIPLE OF OPERATION extraction baffle There is a small sloped grease collecting gutter on the back side of the damper which drains off liquefied grease preventing it from re entraining into the airstream Baffle 2 This baf...

Страница 7: ...which leads to the building drain system Spray nozzles are located on 8 to 10 centers on the wash manifold mounted on the interior back wall of the ventilator At the end of the wash cycle the water automatically shuts off and the interior of the ventilator is clean ready for the next day s operations The damper remains in the wash position until the exhaust fan is restarted This is to prevent cond...

Страница 8: ... on until the thermostat cools down below 250 F CG3 SERIES VENTILATOR PRINCIPLE OF OPERATION CAUTION In case of severe fire the thermostats located in the plenum will activate As a precautionary measure it is recommended that the thermostats be replaced FIG 4 FIRE CYCLE 7 A red light on the Command Center illuminates 8 If the Command Center is intertied with a building alarm or monitoring system a...

Страница 9: ...he break glass fire switch if used would normally be located at the exit of the kitchen When the External Fire Mode is activated the following occurs 1 The Exhaust Fan comes on immediately if it was off to help remove smoke heat etc 2 The Supply Fan shuts off immediately 3 The digital display reads Ext FireActive and alternates between Reset FireSwitch and Fan On Wash On 4 A red light on the Comma...

Страница 10: ... the digital display reads Wash On Wash 1 xxx seconds xxx is the coundown in seconds until the wash system shuts off 6 Upon completion of the wash cycle the damper stays in the closedwashpositionuntiltheexhaustfanisre started This istopreventconditionedairfromgoinguptheexhauststack during off hours N A on CG3 FDD and CG3 ND 7 The digital display now reads Fan Off 12 00 current time and Start Fan F...

Страница 11: ...monthly to remove any foreign material such as paper towels order chits etc Every Six Months 1 Exhaust fan s should be checked every six months for belt tightness belt alignment and lubrication of neces sary moving parts NOTE A blue lithium based grease is best suited for high heat and speed bearing lubrication 2 Check for proper velocity at air inlet slot Refer to Pages 21 through 23 for method o...

Страница 12: ...itial Operation To prime and operate the pump for the first time it is recom mended that water be used instead of detergent to prevent detergent from spilling in case of leaks at the system s fittings Priming The Pump The detergent pump is self priming Push the pump test switch located on the junction box of the motor and hold down until liquid climbs up the vinyl tubing and fills the pump head Th...

Страница 13: ... Spray on and rinse or wipe off For extremely soiled areas gentle agitation followed by a soaking period will result in more thorough cleaning DON TbeafraidtoexperimentwithFORMULAG 510because it contains no phosphates nitrates enzymes sulfates sul fonates or silicates DETERGENT FOR THE WASH SYSTEM LIMITEDWARRANTY G 510 CHEMICAL DIVISION warrants that FOR MULAG 510willnotcausecleansingagent damage ...

Страница 14: ...button to toggle the language displayed from English to Spanish Español or from Spanish Español to English NOTE All messages displayed by pressing the MENU F4 button only appear in English They will not appear in Spanish Español Using the Menu To Enter the Menu press the MENU button F4 To navigate the Menu Press F1 to go to the Next menu item Press F2 to go to the Previous menu item FIGURE 9 C 600...

Страница 15: ...r keep pressing F3 to cycle around if necessary Press F1 to go to the current Minute Press F3 to increase the Minute keep pressing F3 to cycle around if necessary Press F5 EXIT to return to the menu 6 AutoMode A or M Used to select M anual or A utomatic mode If A is displayed the C 6000 is set to operate in Automatic mode If M is displayed the C 6000 is set to operate in Manual mode Press F6 ENTER...

Страница 16: ...D 4 F p U 3 F f i c t e 2 h s a W t x e N o t s e o g t x e N 1 F g n i s s e r P l o r t n o c l a i t n e u q e S a s a p u t e s s i l o r t n o c f i 2 h s a W f o h t g n e L e h t t s u j d a o t 1 F s s e r P e l b a c i l p p a 5 F s s e r P T I X E u n e m e h t o t n r u t e r o t 4 e m i T y a l e D t e S o T s r a e p p a e m i T y a l e D 4 l i t n u 1 F s s e r P e m i T y a l e D 4 ...

Страница 17: ... e s U e d o m c i t a m o t u A o t t e s s r a e p p a e m i T h s a W t e S 7 l i t n u 1 F s s e r P s e m i T h s a W t e S 7 r e t n E 6 F t i x E 5 F h t i w s e l g g o T v e r P 2 F t x e N 1 F 6 F s s e r P R E T N E e m i t t r a t S e h t y a l p s i d o t y a d n u S n o n a F e h t r o f n a F n u S 4 2 4 1 n a F n u S r u o H e h t e s a e r c n i o t 3 F s s e r P s e t u n i M e h...

Страница 18: ...18 FIG 10A TYPICAL ARRANGEMENT WITH VACUUM BREAKER CHECK VALVE FOR BACKFLOW PREVENTION FIG 10B TYPICAL ARRANGEMENT WITH BUILT IN RP DEVICE FOR BACKFLOW PREVENTION ENGINEERING DATA ...

Страница 19: ...verage 1 67 GPM Lineal Ft 80 PSI Average The length of the wash cycle may be set between 3 minutes and 9 minutes The length of time is dependent upon the type of cooking equipment being used Typical settings are 3 minutes for light duty equipment 5 minutes for medium duty equipment and9minutesforheavy dutyequipment However adequate cleaning is dependent upon water pressure water temperature daily ...

Страница 20: ...ous discharge of water out the relief valve when the ventilator is not in a wash cycle do the following A Leave the inlet hand valve open and close the outlet hand valve If there is still continuous discharge it indicates that foreign material is preventing the first check valve from closing If flushing will not clear the unit remove and clean the first check valve B If there is continuous dischar...

Страница 21: ...tion efficiency are depen dentupontheproperairvelocityattheinletslotoftheventilator The Air Velocity Chart below gives the optimum inlet slot velocity and the minimum and maximum allowed velocities If the slot velocity is below or above the minimum or maximum the exhaust fan must be adjusted accordingly NOTE Theheightoftheinletslotcanvarydependinguponthe design of the ventilator It is therefore im...

Страница 22: ...nlet slot as illustrated 6 Using the 16 second averaging feature on the meter slide the sensing head along the slot back and forth for a 3 0 to 4 0 distance and record the velocity at the end of the 16 second mark Continue this process for the full length of the ventilator Imortant Note If the ventilator includes custom air baffles as illustrated in Fig 12B always take separate readings on the sec...

Страница 23: ...ONNECT TO NFPA 13 SPRINKLER SYSTEM WATER SUPPLY ONLY SERIAL NO MODEL NO HOOD MOUNTING REQUIREMENTS W G W G ENGINEERING DATA EXHAUST HOOD WITH EXHAUST DAMPER LISTED 370Y UL CG31001 THIS EXHAUST HOOD IS ALSO LISTED AS AN EXHAUST HOOD WITHOUT EXHAUST DAMPER WHEN EQUIPPED WITH FIRE DAMPER LOCKOUT PART NUMBER FDL FOR USE ONLY WITH GAYLORD INDUS TRIES LISTED SUB ASSEMBLY CONTROL CABINET MODEL NUMBER GPC...

Страница 24: ...xhaust fan opening the control cabinet door and check the water pressure gauge in the cold water loop Water flow pressure should be at 40 psi If it is not adjust the pressure regulator until 40 psi is achieved 2 Mist Nozzles Turn on the exhaust fan look into the air inlet slot and check each mist nozzle for proper spray Remove and clean the nozzle if necessary TROUBLE SHOOTING 1 If the mist nozzle...

Страница 25: ...GX2 normally closed thermostats It has 6 terminals on the TB2 terminal strip on the lower portion of the board Terminals 5 and 6 were added to the TB2 terminal strip to accommodate a 2nd Damper Positioner and the Fire Test Switch A Jumper is required from 6 from the TB2 terminal strip to 3 on the TB1 terminal strip 6000 10 B ICGL02 102 This control will drive up to 10 damper motors 10 sections of ...

Страница 26: ...a e b d l u o h s s r e v u o l e h t g n i c r o f r o g n i t c e r i D r o t a l i t n e v e h t m o r f y a w a s e t a e r c y l l a c i p y t r o t a l i t n e v e h t t a r i a p u e k a m s s o l e k o m s n i g n i t l u s e r s t f a r d s s o r c f o t n e m e c a l p e r r o f d e i l p p u s e b t s u m r i a p u e k a M t s u a h x e n e h c t i k l l a h g u o r h t d e t s u a h x ...

Страница 27: ... X G r e f e r G N I T O O H S E L B U O R T e h t n i E L C Y C E R I F o t n o i t c e s r e t r a t s c i t e n g a m e h t n o n o t t u b t e s e R e h t h s u P e h t n o n o t t u b n a F t r a t S e h t h s u p e h t d n a r e t n e c d n a m m o c c i t a m o t u a e h t o t r o t c e l e s n r u t d n a h c t i w s k c e h C n o i t i s o p r e k a e r b t i u c r i c t e s e R f i e c a...

Страница 28: ...p o n o s i e l c y c h s a w e h t e l i h W k c e h c y l l a u s i v d n a y l t h g i l s r o o d n o i t c e p s n i d e g g o l c s i e l z z o n a f I s e l z z o n f o y a r p s e r i w l l a m s a g n i n n u r y b n a e l c d n a e v o m e r t i h g u o r h t g n i t o o h s e l b u o r t r o f 2 1 e g a P o t r e f e R p m u p t n e g r e t e d y l k e e w t n e g r e t e d l l i f d n ...

Страница 29: ... c r u o s l a n r e t x e e t a g i t s e v n i s p o t s e d o m e s u a c e v o m e r d n a e h t n o t h g i l s u t a t s e t a i r p o r p p a e h t k c e h C n o t r a h c t h g i l s u t a t s C L P e h t o t r e f e R C L P e h t n o t o n s i t h g i l t u p t u o e h t f I 1 3 e g a P r o d e m m a r g o r p e r e b o t s d e e n C L P d e c a l p e r y l b i s s o p e h t n o r o t a l...

Страница 30: ... o l f e v o r e t a w e l c y c h s a w a g n i r u d f I t o l s t e l n i t u o s e m o c d n a r e t t u g e h t A B C D h c a E e t o N t e l t u o n i a r d d e g g o l C n i a r d n w o s t i s a h n o i t c e s r o t a l i t n e v t e l t u o n a h t e r o m f I d e g g o l c m e t s y s n i a r D t i g n i n i a r d t o n s i m e t s y s r o t a l i t n e v e n o s i m e t s y s n i a r d...

Страница 31: ...SCRIPTION PLC 0 On when Wash Solenoid 1 should be open 1 On during an Internal or External Fire Mode On during Cool Down Cycle 2 On when Detergent Pump should be on 3 On when Exhaust Fan should be on COM Never comes on 4 On when Supply Fan should be on COM Never comes on 5 On when damper is in Wash position or while damper is moving to Wash position Y Outputs SEQUENTIAL WASH S2 S5 DESCRIPTION EXPA...

Страница 32: ...uel Shutoff Control Closed Closed Closed Open Open FS Input from Remote Fire Switch 0 VAC 0 VAC 0 VAC 0 VAC 120 VAC 120 VAC 120 VAC 120 VAC 120 VAC 120 VAC 0 VAC 0 VAC 0 VAC 0 VAC 0 VAC GX Power for GX2 Damper Actuators 0 VAC 24 VAC 0 VAC 0 VAC 24 VAC 15 Output to Thermostat s 24 VAC 24 VAC 24 VAC 24 VAC 24 VAC 17 24 VAC Common 14 VDC 6 VDC 14 VDC 6 VDC 6VDC 24 VAC 0 VAC 24 VAC 0 VAC 0 VAC 19 Powe...

Страница 33: ...ize 1 14389 Pipe Size 1 1 4 14390 Pipe Size 1 1 2 14391 3 Detergent Tank 2 Gallon 10221 4 Pressure TemperatureGauge 10175 5 Detergent Brass Check Valve 10265 6 FS 4 Series Detergent Flow Switch Optional 16892 7 DetergentPump 120Volt 10222 220Volt 10223 8 CommandCenterModelC 6000Series Refer to Page 37 38 9 VacuumBreaker Specify Size A Vacuum Breaker Repair Kit Specify Size 10 Water Check Valve Spe...

Страница 34: ...t Pipe Size 3 4 14388 Pipe Size 1 14389 Pipe Size 1 1 4 14390 Pipe Size 1 1 2 14391 2 Detergent Tank 2 Gallon 10221 3 Pressure TemperatureGauge 10175 4 Detergent Brass Check Valve 10264 5 FS 4 Series Detergent Flow Switch Optional 16892 6 DetergentPump 120Volt 10222 220Volt 10223 7 CommandCenterModelC 6000Series Refer to Page 37 38 8 Backflow Preventer RP Device Type Specify Size 9 LineStrainer Sp...

Страница 35: ...14387 Pipe Size 3 4 14388 Pipe Size 1 14389 Pipe Size 1 1 4 14390 Pipe Size 1 1 2 14391 2 Detergent Tank 2 Gallon 10221 3 Pressure TemperatureGauge 10175 4 Brass Check Valve 10264 5 FS 4 Series Detergent Flow Switch Optional 16892 6 DetergentPump 120Volt 10222 220Volt 10223 7 CommandCenterModelC 6000Series Refer to Page 37 38 8 Backflow Preventer RP Device Type Specify Size 9 LineStrainer Specify ...

Страница 36: ...rts for the hot water loop are shown on pages 33 34 and 35 1 1 2 Ball Valve 11258 2 1 2 Solenoid Valve NC 10135 A ReplacementCoil 120Volt 10156 220Volt 10157 B Solenoid Valve Repair Kit Pipe Size 1 2 14387 3 PressureGauge 10276 4 1 2 Water Pressure Reducing Valve 10924 5 1 2 Vacuum Breaker 10177 A Vacuum Breaker Repair Kit 10178 6 1 2 Water Check Valve 10195 7 1 2 Line Strainer 10151 GAYLORD PART ...

Страница 37: ...rator Interface Cable 18868 7 Operator Interface 75636 8 100 VA Transformer 18861 9 Fuse F1 2 Amp 24VDC Power Supply 13062 BUSS AGC 2 10 Fuse F2 4 Amp PLC 120 VAC 10039 BUSS AGC 4 11 Fuse F3 1 Amp Supply Fan Mag Starter 19027 BUSS MDL 1 12 Fuse F4 1 Amp Exhaust Fan Mag Starter 19027 BUSS MDL 1 13 Expansion Module Optional used for S2 S5 18867 14 Flash Guard Not Shown 18877 MODEL C 6000 OR C 6000 A...

Страница 38: ... w p ro g ra m M y la r la b e l 7 5 8 7 1 9 O p e ra to r In te rfa c e M y la r L a b e l 1 9 0 1 0 1 0 1 0 0 V A Tra n s fo rm e r C 6 0 0 0 1 0 1 8 9 8 1 C o n tro l R e la y S P D T C R 9 E S P F ire S ig n a l 1 1 3 9 9 S o c k e t S P D T 1 1 1 2 1 3 1 4 1 7 1 8 2 0 1 1 4 1 3 C o n tro l R e la y S P D T C R 1 0 1 1 3 9 9 S o c k e t S P D T 1 1 4 1 3 C o n tro l R e la y S P D T C R 1 1 1 ...

Страница 39: ...C NO DES CRIP TION GAYLORD P ART NO 1 For C 6000 or C 6000 A Dam per Control M otor A F24 S R 24 V olt 30204 1 For C 6000 B Dam per Control M otor A F24 M FT P 10050 24 V olt or A F24 M FT S 0001 24 V olt 18979 Used in CG3 CG3 FDL and CG3 FDT only ...

Страница 40: ...40 DETERGENT PUMP ...

Страница 41: ...H G I L T N E C S E D N A C N I r e n i a t e R s n e L t h g i L d e s s e c e R 2 1 x 2 1 E M A R F S N E L T H G I L T N E C S E R O U L F 0 1 2 3 1 r e n i a t e R s n e L t h g i L d e s s e c e R t F 2 1 1 1 0 1 r e n i a t e R s n e L t h g i L d e s s e c e R t F 3 2 1 1 0 1 r e n i a t e R s n e L t h g i L d e s s e c e R t F 4 S T A T S O M R E H T T C U D T S U A H X E 5 6 4 8 1 F 0 5 ...

Страница 42: ...42 WIRING DIAGRAM FOR MODEL C 6000 10 120 VOLT ...

Страница 43: ...43 WIRING DIAGRAM FOR MODEL C 6000 10 220 VOLT ...

Страница 44: ...44 WIRING DIAGRAM FOR MODEL C 6000 10 A 120 VOLT ...

Страница 45: ...45 WIRING DIAGRAM FOR MODEL C 6000 10 A 220 VOLT ...

Страница 46: ...46 WIRING DIAGRAM FOR MODEL C 6000 10 B 120 VOLT ...

Страница 47: ...47 WIRING DIAGRAM FOR MODEL C 6000 20 B 120 VOLT ...

Страница 48: ...48 WIRING DIAGRAM FOR MODEL C 6000 10 B 220 VOLT ...

Страница 49: ...49 WIRING DIAGRAM FOR MODEL C 6000 20 B 220 VOLT ...

Страница 50: ...This method of introducing make up air into the kitchen is flexible and has many advantages Make up air is discharged through stainless steel perforated panels as illustrated MAW Series or optional registers Typical supply volume is 80 of the exhaust or more depending on air bal ance desired Supply air temperatures should range from 60 to 65 F 16 to 18 C but may be as low as 50 F 10 C depending on...

Страница 51: ...ters L s liters per second N Newtons dm decimeters Kpa 1000 Pascals N m2 Newtons per square meter CFM cubic feet per minute psi pounds per square inch C degrees Celsius m3 s cubic meters per second kg m2 kilograms per square meter BAR one atmospheric pressure meter L Liters F degreesFahrenheit 1000 millibars 14 7 psi WATERFLOW VOLUME TOCONVERT TO MULTIPLYBY U S ounce Liters 02958 U S gal Liters 3 ...

Страница 52: ..._______ FIRE MODETEST CAUTION Before any fire tests are performed check with building superintendent to see if Gaylord control cabinet is tied into building alarm monitoring system and or Fire Department THERMOSTAT TEST For CG3 CG3 FDL and CG3 FDT With the exhaust fan on open electrical compartment on Control Cabinet and push and hold for 20 seconds the Fire Test Switch The following should occur ...

Страница 53: ...nufacturer or its authorized representative SuchlaborshallonlybeprovidedMondaysthroughFridaysduringthehoursbetween 8 a m and 4 p m Requests for repairs or replacement parts should be made to GAYLORD INDUSTRIES P O Box1149 Tualatin Oregon97062 1149 Outside the United States all replacement parts furnished under this warranty shall be F O B GaylordIndustries Inc Tualatin OregonU S A Theownershallpay...

Страница 54: ...ENCY VISIT OUR WEB SITE WWW GAYLORDUSA COM OR CONTACT US AT GAYLORD INDUSTRIES 10900 S W AVERY STREET TUALATIN OREGON 97062 1149 U S A Phone 503 691 2010 1 800 547 9696 Fax 503 692 6048 email info gaylordusa com LOCAL SERVICE AGENCY FORM NO TM CG3 0304 30507 COPYRIGHT 2005 GAYLORD INDUSTRIES LITHO IN U S A ...

Отзывы: