6.5.2. PROGRAM MODE
- When "FUNC" S/W is pushed, Program Mode is entered into.
- When "RESET" S/W is pushed, the display state of gas concentration is entered into.
- The first function in setting functions for program data is setting for the position of decimal point.
- When "FUNC" S/W is pushed, the setting function for decimal point is entered into.
- When "RESET" S/W is pushed, Program Mode is returned to.
- When it is necessary to change the decimal point according to the measurement range.
-
When setting the decimal point position, use "UP" S/W or Each time "DOWN" S/W is pushed,
-
the decimal point position is changed as shown on the left. (Basic value 100)
- Ex)100, 10.0, 1.00, 0.100
- Press "FUNC" S/W when the desired decimal position is displayed, to set the decimal position
-
and enter the next item.
- Press RESET" S/W to return to Program Mode.
- Setting function for High scale as a function for setting of the maximum value in gas
-
concentration display.
- High Scale value is set for the range specified by domestic regulations upon product shipment.
- When "FUNC" S/W is pushed, the setting function for High scale is entered into
- When "RESET" S/W is pushed, Program Mode is returned to.
- High scale value is the function where the setting values are changed according to measuring
-
range, and the scale value is increased or decreased whenever UP" S/W or "DOWN" S/W is
-
pushed (Basic value100)
- If "FUNC" S/W is pushed when the desired High scale value is displayed, the High scale value
-
is set and the next item is entered into.
- When "RESET" S/W is pushed, Program Mode is returned to.
- The present setting mode is set for the same measuring range as gas detector upon factory
-
shipment.
-
Ex) When Range was set for 100,
-
Upon outputting of 4 mA/DC….. 0 Display
-
Upon outputting of 20 mA/DC….. 100 Display
- Setting function for SAD value as a function to compensate errors for measured values
-
occurring in detection unit.
- When "FUNC" S/W is pushed, the setting function for SAD value is entered into.
- When "RESET" S/W is pushed, Program Mode is returned to.
- Function for setting of SAD value. SAD value is increased or decreased whenever "UP" S/W or
-
"DOWN" S/W is pushed, and "-" sign is added above the first figure for display when it is
-
a negative value. (Basic value 0)
- If "FUNC" S/W is pushed when the desired SAD value is displayed, the SAD value is set, and
-
the next item is entered into.
- When "RESET" S/W is pushed, Program Mode is returned to.
-
(Ex) When the error of output in detector is -2, Display shows 0 by calibration of SAD setting
-
value 2 although the actual Display should indicate -2.
- Setting function for Password.
- When "FUNC" S/W is pushed, the setting function for Password is entered into.
- When "RESET" S/W is pushed, Program Mode is returned to.
- The value of Password is increased or decreased whenever "UP" S/W or "DOWN" S/W is
-
pushed. (Basic value P00)
- If "FUNC" S/W is pushed when the desired Password No. is displayed, the Password No value
-
is set and the next item is entered into.
- When "RESET" S/W is pushed, Program Mode is returned to.
▼ ▲
▼ ▲
▼ ▲
6. How to operate