For more information & Technical support:
38
F-Guard UV-IR User Manual
Doc. No. F110V0020.06
Medium Sensitivity
Fuel
Size
Distance Feet (m)
Average Response
Time (Seconds)
N-Heptane
1 x 1 ft
49 (15)
1.4
Gasoline
1 x 1 ft
49 (15)
2.7
Methane
32-in Plume
30 (9)
0.9
LPG
32-in Plume
33 (10)
1.3
Diesel
1 x 1 ft
36 (11)
1.6
JP5
1 x 1 ft
36 (11)
1.5
Kerosene
1 x 1 ft
36 (11)
1.4
Methanol
1 x 1 ft
30 (9)
1.3
Ethanol
1 x 1 ft
31 (9.5)
1.2
Isopropanol
1 x 1 ft
36 (11)
1.4
Polypropylene
1 x 1 ft
23 (7)
1.7
Paper
1 x 1 ft
23 (7)
2.0
Syngas*
32-in Plume
33 (10)
1.2
Low Sensitivity
Fuel
Size
Distance Feet
(m)
Average Response
Time (Seconds)
N-Heptane
1 x 1 ft
16 (5)
0.9
LPG
32-in Plume
13 (4)
1.0
JP5
1 x 1 ft
16 (5)
2.6
Methanol
1 x 1 ft
10 (3)
1.1