F-Guard IR3-H2 User Manual
76-M-6010-02-02
T
ABLE
2:
D
ETECTOR
C
ONFIGURATION
O
PTIONS
Function
Options
Default Setting
Sensitivity
Very low, Low, Medium, High, Extreme Medium
Ultra-fast detection
Disabled, Enabled
Disabled
Alarm Delay
0, 5, 10, 20 or 30 seconds
0 seconds (no delay)
Alarm Latch
Disabled, Enabled
Disabled
Enable Pre-Alarm 0-20mA
Disabled, Enabled
Disabled
Enable dirty window warning 0-
20mA
Disabled, Enabled
Disabled
Aux. Relay
Alarm, Pre-Alarm, Dirty Window
Warning
Alarm
Window Heater
Disabled, Enabled
Enabled
Modbus address
1 – 247
1
Manual BIT – Alarm Output Test
Disabled, Enabled
Disabled
•
Note:
Medium, Default, sensitivity setting allows detection of a 32-in Plume hydrogen
flame at a distance of 66ft (20m).