D-Guard² Instruction Manual
Item Number 201018
17
15.2 Attach the calibration gas to the D-Guard²
The D-Guard² is a normally aspirated gas detector that operates at normal
atmospheric pressure. A calibration plug is provided to make sure that gas is applied
directly to the sensor.
Step 1.
Remove the Splash Guard.
Step 2.
Fit the calibration plug.
Step 3
. Attach tubing to the calibration plug.
Step 4
. Use a 1L / min fixed flow regulator.