Page 10
Adjusting the DIP switches:
1. Unscrew the four screws in the top of the Gassonic MM0100, and remove the lid.
2. Unscrew the six screws on the metalplate located under the lid and remove the plate. The dipswitches,
illustrated below, are now visible.
3. Using a small, flat-blade screwdriver, change the positions of the dipswitches to suit your measuring
site requirements.
4. Replace the plate and secure it with the six screws.
5. Replace the lid and secure the four screws using an Allen-key.
6. operatInG tHe eqUIpMent
6.1. Trip Output Data
The only output from the device is a trip output. This has two states:
Normal: 1.28k
Ω
±1%
Alarm: 10k
Ω
±1% (No power or an ultra sound level above the preset trigger level)