9.1.
HEAT PUMP UNIT INSTALLATION
The heat pump unit should be installed in a ventilated place, with enough space for air inlet and outlet,
while without thermal radiation or other heat source. Besides, the air outlet should not be against the
wind.
Generally, the vertical air flow type heat pump does not need anything for sheltering. The motor and
other internal components have been all waterproof. A shelter is required to avoid snow burying onto the
heat pump in heavily snowy area.
Please make sure the rated voltage 380V or 400V is stably accessible to the heat pump, otherwise
the performance would be influenced.
The foundation of the heat pump can be cement or steel structure. Anti-vibration rubber and a flat
foundation should be taken into account. The foundation structure can be flexibly designed
according to the working weight of the heat pump(Please see the technical data in this manual.)
Water drainage should be available near the installation location for draining water in an effective
way.
Do not install the heat pump in a place where there is polluting or corrosive material like oil,
flammable and explosive gas and sulfide etc. Keep it far away from sands, falling leaves and area
with high-frequency equipment.
The foundation should be heightened to avoid the water inflow in rainy season and snow burying in
winter if it is installed in the open air.
Installation in balcony or on roof-top must be accordance with the allowable stress of the building
structure.
The heat pump should be fixed firmly on the base. The bearing capability of the frame should
be as
three times of weight as the heat pump unit. Reliable measures should be taken to keep the fastener
stable. The unit base should be fixed firmly by expansion bolts to ensure the entire unit stand
erectly after installation.
The unit location should avoid typhoon and earthquake damage. The heat pump should not be
installed in the air in case of crash accident.
The installation should be carried out at the place of unobstructed ventilation of the air outlet.
(The inlet and outlet of the
air blower are illustrated in the following diagram). The installation
space should be referred as follows:
▲
An exhaust duct should be
connected to the heat pump air outlet
if there is a barrier above the air outlet.
▲
A certain distance should be kept among the heat pumps
and it should be at least 1 meter when several heat pumps
are installed side by side.
9.
INSTALLATION