4.8  COMMISSIONING AND START-UP

 

4.8.1 GENERAL RECOMMENDATIONS 

Before proceeding with commissioning of equipment, it is important always: 
 

1)  Verify if the equipment is properly installed according to the recommendations hereby described. 
2)  Close the blocking valves of inlet, outlet and by-pass, when application, of each stream. 
3)  Open the vent valve downstream the last regulator in the respective stream. 
4)  Certify that the Skid is NOT pressurized. 

 

ATENTION: 

 

* Under none hypotheses proceed with the stream pressurization where the equipment is installed by the 
valve downstream the equipment. 
* Under none hypotheses proceed with the stream pressurization where the equipment is installed by the 
valve upstream the equipment, as drain filer, for example.

 

 

5)  Verify if all connectors are properly tight before proceed with stream pressurization. 
6)  Verify if all equipment installed are adequate to the operating conditions, based on nameplate data attached in 

each equipment. 

7)  Verify if SSV (slam shut valve) is in the closed position. 

 

GASCAT  SSV  are  supplied  already  adjusted,  however,  due  of  transport  conditions  and  equipment 
handling it can be changed. 
So  that,  it  is  recommended  to  verify  the  set-point  of  SSV  using  (for  example)  external  pneumatic  source 
directly in the actuator before proceed with stream pressurization. 
 
DOMUS regulator is NOT supplied adjusted. It tends to preserve the life time of some internal parts. It 
means that the pressure regulator must be adjusted previously before operation.

 

4.8.2 COMMISSIONING 

Utilizing  as  reference  the  assembly  layout  presented  in  the  item  4.7  proceed  with  the  descriptive  indicate  for 
commissioning  of DOMUS HF pressure regulator,  considering  that the recommendations in the item  4.6.1 of this 
manual were properly observed. 
 
Such procedure considers the utilization of DOMUS with G30F pilot. 
 

1)  Close the vent valve. 

As the blocking valves of the stream are closed utilize the vent valve to simulate a low flow and proceed with 
regulator adjusting before regulating the stream.  

2)  Verify if the adjusting spring pilot is released (with no charge). 

Releasing the adjusting spring assure that the regulator will remain closed when pressurized. 

3)  Reset the SSV (slam shut valve). 
4)  Open  SLOW  AND GRADUALLY the  inlet block valve, or when  there is a  by-pass for the  inlet  valves  in the 

Skid utilize it to pressurize the stream. 

5)  At this stage, the inlet pressure will achieve the regulator inlet, therefore it will remain closed because of this 

no pressure downstream. 

6)  Adjust  the  pilot  turning  clockwise  the  adjusting  spring.  Assisted  by  the  outlet  pressure  gauge  in  the  outlet 

pressure adjust the pressure 58 psi (4 bar) above the desired set point. 
For example, if the set point is 217 psig (15 bar) the pre-regulator shall adjust 275 psi (19 bar). 

7)  Adjust the G30F/G32F pilot turning clockwise the regulating spring. Do it slowly in order to admit low pressure 

downstream the pressure regulator; utilize the pressure gauge in the pipe checking the increase in pressure 
until the desired set point. 

8)  Open the vent valve around 20%, and verify if the pressure remain in the value adjusted. 

Содержание DOMUS HF

Страница 1: ...INSTALLATION OPERATION MANUAL PRESSURE REGULATOR VALVE MODEL DOMUS HF...

Страница 2: ...3 5 VALVE WEIGHT 6 2 3 6 MAXIMUM WORKING PRESSURE 6 2 3 7 PRESSURE REGULATOR SPRING RANGE SET POINT 6 2 3 8 ACCURACY AND LOCK UP 7 2 3 10 PRESSURE REGULATOR DIMENSIONS 7 3 OPERATING PRINCIPLE 8 3 1 P...

Страница 3: ...that all users of these equipments are properly instructed and warned on their potential danger and certify yourself that the personnel responsible for installation test commissioning operation and ma...

Страница 4: ...alve can be positioned fully open Consequently when a regulator is put into operation the shutoff valves should be open slowly so that the regulator valve can assume its regulating position If the val...

Страница 5: ...at after all regulators opening during maintenance service the repair kit must be changed It is also indicated to change a complete repair kit and not only specific part example o ring shutter to have...

Страница 6: ...installation and safety of people involved in the operation 2 3 4 FLOW COEFICIENT DN KG 1 200 2 600 2 3 5 VALVE WEIGHT DN 150 PN16 NPT F 1 28 Kg 2 38 Kg 2 3 6 MAXIMUM WORKING PRESSURE 600 103 bar The...

Страница 7: ...e 19 PILOTO G 33F SPRING COLOR PART NUMBER RANGE BROWN 01 49 33 14 0 36 0 bar BLACK 01 49 59 28 0 63 0 bar 2 3 8 ACCURACY AND LOCK UP Pressure regulator AC up to 2 5 SG up to 5 2 3 10 PRESSURE REGULAT...

Страница 8: ...that is connected downstream the regulator in a connection in the own body valve has the function to relief the excess of pressure in the diaphragm upper chamber Under the shutter there is a small spr...

Страница 9: ...gh force to move the shaft downward and open the pilot In this condition the pressure in the upper chamber of main valve will be higher than the pressure under the diaphragm of main valve and allow th...

Страница 10: ...in the same level 5 All connections for sense line and discharge line requested by the model of pressure regulator are arranged in the pipeline and respect the dimensions provided by manufacturer 6 W...

Страница 11: ...ol of the regulator Care with the filter installation is essential to the perfect operation of the apparatus because particles eventually found in the piping can lodge themselves the seat and the shut...

Страница 12: ...outlet of pressure regulator at a pipe stretch free from obstruction with a pipe diameter sized to a velocity not higher than 25 m s considering the minimum pressure and the maximum flow The connectio...

Страница 13: ...TALLATION LAYOUT It is recommended for a safety installation 1 Manual On Off valve sphere or similar 6 Gauge for outlet pressure 2 Filter with drain if possible 7 Purge valve ND 3 Gauge for inlet pres...

Страница 14: ...the life time of some internal parts It means that the pressure regulator must be adjusted previously before operation 4 8 2 COMMISSIONING Utilizing as reference the assembly layout presented in the i...

Страница 15: ...equalize the reserve by pass stream with the pressure of working stream the by pass regulator will remain closed To make the regulator in the reserve by pass line assumes the regulating pressure of t...

Страница 16: ...reduced orifice Sensing line installed wrongly Verify if the sensing line is too close of main valve of near of an equipment that my cause flow turbulence Bleed valve wrongly adjusted Proced the adjus...

Страница 17: ...be interpreted or suggest performance warranty in relation to the final products or the system usage purpose nor should they serve as usage recommendation for any product or process mentioned in the...

Страница 18: ...essure Regulating Valve MI 23 Elaborado Verificado Aprovado CSQ Data Revis o P gina JJ VBL JM 15 12 17 00 18 de 19 POS DESCRIPTION QTY 1 DIAPHRAGM 1 2 SHUTTER 1 3 FILTER ELEMENT 1 4 PARBAK 1 5 O RING...

Страница 19: ...Valve MI 23 Elaborado Verificado Aprovado CSQ Data Revis o P gina JJ VBL JM 15 12 17 00 19 de 19 PRE PILOT G 31F G33F CODE 28 20 41F POS DESCRIPTION QTY 1 RELIEF 1 2 DIAPHRAGM 1 3 SHUTTER 1 4 FILTER E...

Отзывы: