Operating instructions

The gas detector GS-300.A/GS-300.N has the following operation modes:

1.Initial stabilisation

Preheating and initial testing of gas sensing element.
Indication: Green LED is flashing quickly. 
 

2.Working mode

In this mode sensor is ready to detect gas concentration.
Indication: Green LED is flashing slowly. 

3.Alarm 1

First alarm level is reached. 
Indication: Red LED is flashing slowly. 

4.Alarm 2

Second alarm level is reached.
Indication: Red LED is flashing quickly. 

5.Alarm 3

Third alarm level is reached.
Indication: Red LED lights permanently. 

6.FAULT

Sensor element fault. 
Indication: Orange LED is flashing. 

Sensor calibration

Gas detectors must to be calibrated and periodically checked to ensure detector accuracy and system 
integrity. It is important to install stationary gas detectors at locations where the calibration can be 
performed easily. The intervals between calibration can be different from sensor to sensor. However, it is 
good general practice to check the detector during the first 30 days after installation. During this period, it 
is possible to observe how well the detector is adapting to its new environment. If the detector functions 
properly for 30 continuous days, this provides a good degree of confidence about the installation. Any 
possible problems can be identified and corrected during this time. Experience indicates that a detector 
surviving 30 days after the initial installation will have a good chance of performing its function for the 
duration expected. Most problems such as an inappropriate detector location, interference from other 
gases, or the loss of sensitivity will arise during this time. Afterward, a maintenance schedule, including 
calibration intervals, should be established.

Normally, a 6-monthly calibration period is adequate to ensure the effectiveness and sensibility of each 
sensor. This check will also afford you the opportunity to maintain the system’s accuracy.

CALIBRATION PROCEDURE

Calibration of the gas detector includes two steps. First the “zero” must be set and then the “span” must 
be calibrated.

1.To initiate calibration pres and hold the tactile button on the PCB or place the magnetic gas calibration 
cup.
2.After 5sec all LED’s will flash.

Содержание GS-300.A

Страница 1: ...GS 300 A GS 300 N GAS DETECTORS Operation Manual Revision A 2...

Страница 2: ...the express written consent of Invest Electronics is strictly prohibited Due to ongoing research and development the specifications of this product may be changed at any time without notice INVEST ELE...

Страница 3: ...Installation and wiring 9 1 Mounting the sensor 9 2 Mechanical mounting 9 3 Electrical connection 9 4 Analogue gas detector GS 300 A 9 5 Addressable gas detector GS 300 N 10 Operating instructions 10...

Страница 4: ...facturer reserves the right to modify the technical characteristics of its equipment without notice to improve product performance This user manual and its contents are the inalienable property of Inv...

Страница 5: ...ation Limitation of liability Neither Invest Electronics Ltd nor any other affiliated organization shall be held liable under any circumstances for any damage whatsoever including without limitations...

Страница 6: ...uring method The following mesuring methods are used 1 Cathalityc sensors for mesurement of explosive gases 2 Electrochemical sensors for toxic gases 3 Infrared sensors for CO2 4 Semiconductor sensors...

Страница 7: ...Front view gas detector GS 300 A Front view gas detector GS 300 N...

Страница 8: ...Inside view gas detector GS 300 A Inside view gas detector GS 300 N...

Страница 9: ...and maintenance Mechanical mounting Gas detector is attached to the wall via 4 mounting screws Sensor opening to be placed downwards Drill 4 holes according to the Drilling diagramme Drilling diagramm...

Страница 10: ...must be connected using shielded cable with twisted pair for communication A and B terminals and another pair for the power supply of gas detectors The end of line resistor must be connected in the la...

Страница 11: ...e first 30 days after installation During this period it is possible to observe how well the detector is adapting to its new environment If the detector functions properly for 30 continuous days this...

Страница 12: ...exterior of the enclosure with a damp cloth Do not use alcohol or ammonia based liquids to clean the detector Servicing We recommend the user to periodically inspect the proper triggering of alarm an...

Страница 13: ...el ordering code Detected gas Gas concentration GS 300 A AMM 2000 Ammonia 0 2000 ppm GS 300 A 134A 2000 R 134a 0 2000 ppm GS 300 A 404A 2000 R 404a 0 2000 ppm GS 300 A 407C 2000 R 407c 0 2000 ppm GS 3...

Страница 14: ...dering code Detected gas Gas concentration GS 300 N AMM 2000 Ammonia 0 2000 ppm GS 300 N 134A 2000 R 134a 0 2000 ppm GS 300 N 404A 2000 R 404a 0 2000 ppm GS 300 N 407C 2000 R 407c 0 2000 ppm GS 300 N...

Отзывы: