Output Operation: 

Current or Voltage 0-20mA, 4-20mA, 0-5V, 0-10V Configuration: 

This output will generate a current or voltage output reflecting the full scale of the sensor. This output is 
factory set and calibrated to the user’s specified requirements at point of purchase. 
If an output type was not specified by the user at time of purchase the default setup is set and calibrated 
to 4-20mA. This is user adjustable out in field but will not be as accurate to what it was originally 
calibrated to from factory.  
The 4-20ma will drive into a maximum of 680Ω load impedance (line and input impedance) at 24V. 

Be cautious when handling the GDA 3160 as there are delicate components that can easily be damaged 

by static discharge. Always observe anti static precautions. 

To change the output option:  
1. Isolate the GDA 3160 by removing the incoming power source connector (P1) from the rear of the 
board  
2. Adjust jumper pins to the desired output configuration (see Table below) 
3. Ensure output is configured for the changed output option 
4. Revert to normal operation 
 
 

 

 

 

 

 

 

 

 

Output Type 

P2 Jumper Configuration 

P2 Jumper location  

Sen 

Pwr 

MCU 

Pwr 

HS/FS 

 

0/4-

20mA 

V Out 

 

Reset 

 

4-20 mA (Default) 

IN 

IN 

IN 

IN 

OUT 

OUT 

0-20 mA 

IN 

IN 

IN 

OUT 

OUT 

OUT 

0-5 V 

IN 

IN 

OUT 

OUT 

IN 

OUT 

0-10 V 

IN 

IN 

IN 

OUT 

IN 

OUT 

P2 

P4 

P2 Jumper 
Description

 

P1 

1 2 3 4 5 6 

Содержание GDA 3160

Страница 1: ...GDA 3160 3100 V5 5 HARDWARE AND ABOVE Refrigerant Gas Detector Operating Manual Copyright Gas Detection Australia Pty Ltd Dec 2017...

Страница 2: ...f cable run Screen must be connected to the Earth connection on the connector P1 Power Consumption 300mW average Output Types 4 20mA Standard 0 20mA 0 5v 0 10v User Specified Target Gas Refrigerant R2...

Страница 3: ...he further from the potential leeks the more the gas will be diluted Take into account drafts and air movements when mounting the sensor IT IS VERY IMPORTANT THAT THE GDA 3160 IS INSTALLED IN THE MOST...

Страница 4: ...rrying capability to suit the length of cable run Screen must be connected to the Earth connection on the connector P1 The Protection Cover Plate is used to protect the main PCB from most cases of sta...

Страница 5: ...at this does not affect external equipment LED STATE FUNTION ON Power is present OFF Power is not present LEDs CHASE Sensor is in its initialisation period approx 30 secs but in some sensors this can...

Страница 6: ...ve into a maximum of 680 load impedance line and input impedance at 24V Be cautious when handling the GDA 3160 as there are delicate components that can easily be damaged by static discharge Always ob...

Страница 7: ...JP6 The alarm enable jumper has been factory set to on for ver 5 5 If the MUTE link Purple is in it will mute the on board buzzer If the optional mute button is installed the on board buzzer can be m...

Страница 8: ...in service if the sensor falls below a minimum working standard the o p current will fall to 3 00mA which will be detected at the control unit has a sensor fault Zero point Calibration A manual zeroi...

Страница 9: ...Zero 0 5 sec Alternate Blinking at once per second for 4 sec Zero Successful 0 1 sec Fast Blink for 2 sec Zero Failed Solid for 2 sec Manual Calibration Mode Add a jumper to pins 1 and 3 of P3 P4 LED...

Страница 10: ...Gas Detection Australia Pty Ltd Page 10 of 12 M 3160 003 1 05 12 2017 Thank You For Supporting Australian Manufactured Products...

Страница 11: ...Gas Detection Australia Pty Ltd Page 11 of 12 M 3160 003 1 05 12 2017 Notes...

Страница 12: ...Gas Detection Australia Pty Ltd Page 12 of 12 M 3160 003 1 05 12 2017...

Отзывы: