burner size. Model 99270 have 0.84
MBTU burner. Model 99273
has a 1.0 MBTU burner and model
99275 has a 1.5 MBTU burner.
The gas pipe connection size for the
model 99270 will be 1” and for the
models 99273 and 99275 will be 1 1/4”.
A drip leg or trap at the inlet of the gas
manifold is provided.
WARNING: PIPING MUST BE
ADDED IN ORDER TO INSURE
GAS TRAIN VENT IS PIPED TO
THE OUTSIDE OF BUILDING.
FAILURE TO DO SO WILL CAUSE
GAS TO VENT INTO THE
BUILDING AROUND THE
MANIFOLD.
WARNING: ALL COMPONENTS
OF THE GAS SUPPLY SYSTEM
MUST BE LEAK TESTED PRIOR
TO PLACING EQUIPMENT INTO
OPERATION.
ELECTRICAL:
WARNING: SPARK TESTING OR
SHORTING OF THE CONTROL
WIRES BY ANY MEANS WILL
DAMAGE THE CONTROL PANEL
AND VOID THE WARRANTY
.
All electrical wiring and connections,
including electrical grounding, should be
made in accordance with the National
Electric Code ANSI/NFPA 70 current
addition.
Although the Garmat
®
USA, Inc. air
make up units are for use in most
commercial heating applications, the
main application of the unit is for use
with a paint spray booth. The use of two
120 volt 20 ampere circuits for lighting
will need to be supplied to the unit when
used in conjunction with a paint spray
booth.
The motor requirements are as follows:
for 3 PH, 10 HP units, 208 volt AC
requires 30.8 Full Load Amperage
“FLA”, 230 volt AC requires 28 FLA
and 460 volt requires 14 FLA. For
single phase, 10 HP motors 230 volt AC
requires 50 FLA. The single phase
motors are not available and a roto-phase
inverter or buck booster is required and
not provided by Garmat USA®.
For Three Phase 15 HP units, 208 volt
AC requires 46.2 FLA., 230 volt AC
requires 42 FLA., 460 volt AC requires
21 FLA. The single phase motors are not
available.
For control voltage a transformer is
provided to convert the motor voltage to
the proper control voltage/s.
NOTE: ALL MOTOR AMPERAGE
FIGURES ARE BASED ON NEC.
LOCAL REQUIREMENTS MAY
VARY.
WARNING: ELECTRICAL AND
IGNITION SYSTEMS MUST BE
PROTECTED FROM DRIPPING
WATER. IMPROPER
INSTALLATION, ADJUSTMENT,
ALTERATION, SETRVICE, OR
MAINTENANCE CAN CAUSE
PROPERTY DAMAGE, INJURY OR
DEATH. READ THE
INSTALLATION, OPERATING
AND MAINTENANCE
INSTRUCTIONS THOROUGHLY
BEFORE INSTALLING OR
SERVICING THIS EQUIPMENT.
SAFETY SYSTEM
4