13-21-615 v01 Page 60
Discharge
Temperature
AEON 4000
Change Interval
AEON 9000SP
Change Interval
Up to 180
F (82
C)
4000 hrs.
8000 hrs.
180
F to 190
F (82
C to 88
C)
3000 hrs.
6000 hrs.
190
F to 200
F (88
C to 93
C)
2000 hrs.
4000 hrs.
200
F+ (93
C)
1000 hrs.
2000 hrs.
Figure 5-6 OIL CHANGE INTERVAL
Figure 5-7
– OIL SAMPLING VALVE LOCATION