9.6.3
L132 + L132e, 50 Hz, air-cooled "[A]", water-cooled "W"
L132 + L132e
50Hz, air-cooled "A” + water-
cooled "W"
L132 + L132e
Maximum operating pressure
[bar]
7.5
10
13
Maximum operating pressure (ver-
sion e)
[bar]
7.5
10
Minimum operating pressure
[bar]
5.0
Ambient temperature
[°C]
1 / 45
Volume flow
*)
[m
3
/min]
24.45 21.51 18.69
Aftercooler outlet temperature above
ambient temperature
"A" = [°C]
"W" = [°C]
8
9
8
8
7
7
Sound pressure level (ISO 2151)
**)
"A" [dB(A)]
"W" [dB(A)]
76
76
Rated speed of drive motor
[kW]
132
Total current consumption during load
operation (400V)
"A" [A]
"W" [A]
286
276
Total current consumption during load
operation (400V) (version e)
"A" [A]
"W" [A]
282
271
Electric motor
IP55 (IE3) - IEC 60034-2-1 ECA Qualifying
Electric motor (version e)
IP55 (IE4) - IEC 60034-2-1 ECA Qualifying
Rated speed of drive motor
[rpm]
3000
Rated speed of fan motor
"A" [kW]
W" [kW]
5.0
0.37
Recommended cable cross-section
(400V)
"A" [mm
2
]
"W" [mm
2
]
2 x 3 x 70 PE35
2 x 3 x 50 PE25
Recommended fuse rating (time-
delayed)
[A]
2 x 3 x 200
Cooling air volume flow
"A" [m
3
/min]
273
Cooling air volume flow
"W" [m
3
/min]
100
Cooling air outlet temperature above
ambient temperature
"A" [°C]
29
Residual pressure at ambient temper-
ature
"A" [Pa]
130 / 90
[35 °C / 45 °C]
Cooling water quantity
"W" [l/min]
170
@ ΔT = 12K
@ Δp = 2.1 bar
Cooling water inlet temperature
"W" [°C]
min. 5 / max. 35
Cooling water outlet temperature
"W" [°C]
max. 55
Cooling water pressure
"W" [bar]
max. 10
Chart 9-5: Technical data; L132 + L132e, 50 Hz, air-cooled "[A]", water-cooled "W"