13-17-621 Page 53
Figure 66: Hours Left to Service
To reset all the parameters use the
Select All
button to reset all parameters at the same time. Then hit the
Reset
button on the next screen.
4.1.1.1 Set Intervals:
While the bar graph shows how much time is left for the next service, the rectangular box on the right end
of each bar is the service interval time setting. The
Air Filter
interval shown below,
“2000 hours 6 Mon 0
Days”, is the time set for the service interval. This can be changed by selecting the box, the
Set Interval
screen will come up as shown in below Figure 67. The values for hours and calendar time may not exceed
the factory default values for the machine. In certain circumstances it may desirable to set the interval below
the factory default. For example, in a very dusty environment it may be necessary to change the air filter at
a shorter interval. Once the interval has been set, it will be used every time the maintenance timer is reset.
Figure 67: Set Intervals
To change the hours, touch the input box next to
Hours
. Similarly,
Date
can be set with the combination of
month and days settings. Figure 68 below shows editing the hours for the
Air Filter
.