13-21-611 Page 18
2-7
AFTERCOOLER
Water Temperature to Heat
Exchanger
Gallons/minute
(Minimum)
Maximum Water
Flow
Gallons/minute *
Approximate Water
Pressure Drop @ 90
F
Water Temperature PSI
HP
Model
60
F
70
F
80
F
90
F
75
SAV75-100G2A
2.2
2.5
2.9
3.6
26
Less than 1 PSI for any
flow rate shown in the table
100
SAV75-100G2A
2.9
3.3
3.9
4.7
26
75
ST75-100G2A
2.2
2.5
2.9
3.6
26
100
ST75-100G2A
2.9
3.3
3.9
4.7
26
* Flows exceeding "Maximum Water Flow" will cause severe erosion and will void unit warranty.
Figure-2-6
– AFTERCOOLER APPROXIMATE WATER FLOW
WATER PIPING (Water-Cooled Heat Exchanger Models Only)
- On machines equipped with water-
cooled heat exchangers, the water inlet and outlet connections are located in the unit enclosure flange on
the end of the unit opposite the control box.
It is mandatory that any water cooled unit be installed in a shelter heated to
temperatures above freezing (32
F., 0
C).
The water source should be capable of supplying up to the maximum flow shown in Figure 2-5, Page 17,
and
, page18, at a minimum pressure of 40 psig (2.8 bar); maximum allowable water pressure is
150 psig (10.3 bar). The water flow rates shown are approximate and a guide to sizing piping, cooling
tower and other water system equipment.
Содержание ELECTRA-SAVER G2
Страница 11: ...13 21 611 Page 10 1 3 Figure 1 4 COMPRESSOR MOTOR SIDE Figure 1 5 COOLER RESERVOIR SIDE 309EBD797 B Ref Drawing...
Страница 12: ...13 21 611 Page 11 1 4 Figure 1 6 AIR OIL FLOW DIAGRAM 307EBD797 B Ref Drawing...
Страница 41: ...4 10 THIS PAGE INTENTIONALLY LEFT BLANK 13 21 611 Page 40...
Страница 42: ...4 10 FIGURE 4 6 COMPRESSOR PACKAGE P ID 13 21 611 Page 41 300EBF797 02 Ref Drawing...
Страница 70: ...13 21 611 Page 69 5 4 Figure 5 3 FLOW DIAGRAM AIR OIL SYSTEM 300EBF797 02 Ref Drawing...
Страница 71: ...5 5 13 21 611 Page 70 Figure 5 4 OIL FLOW DIAGRAM REMOTE MOUNTED COOLER 318EBD797 00 Ref Drawing...
Страница 74: ...13 21 611 Page 73 5 8 THIS PAGE INTENTIONALLY LEFT BLANK...