RTxxx LED lighting controllers - User Manual
Clear any Errors
GR
If Ethernet messages are not enabled, the last event or error
number can be read by this command. Any error displayed on
the unit is cleared, so if there was a lighting error, the RTxxx
resumes auto-sensing on that channel.
The reply is in the same form as the
GT
command above. If there
are no outstanding events or errors, then only the prompt
>
is
returned.
Set/Clear the Webpage Password
EY
EY asc1, asc2, asc3, asc4, asc5, asc6
This command sets the password required to access the
webpages. If
EY
is entered on its own then the password is
cleared. There are six optional parameters, which are decimal
ASCII values for a password from one to six letters. A value of 65
is ‘A’, 66 is ‘B’, and so on, to 90 is ‘Z’.
You can set an unlock code. This can be used as a low-security
way of allowing trusted users to unlock the keypad. Ethernet
commands and the web pages still work. The setting of this
command is restored after a power cycle.
12.3.2
Lighting channel commands
Set the rating of a light
This command sets the current or voltage rating for a light. If a
current rating is being set, then the voltage rating value should
be 0.
VLo,v,c
Where:
o
= output channel (1 to 2, 4 or 8, depending on model)
v
= voltage rating (0 or 12 to 36)
c
= current rating (0 or 10mA to 3A)
Set automatic sensing of lighting characteristics
This command sets the maximum brightness to be used when
automatically sensing the characteristics of the light connected.
PQc,0
PQc,m
—
60
—