![Gantner e.bloxx A5CR Скачать руководство пользователя страница 16](http://html2.mh-extra.com/html/gantner/e-bloxx-a5cr/e-bloxx-a5cr_manual_5057997016.webp)
e.bloxx A5-1CR
MOUNTING e.bloxx AND CONNECTING WIRES
14
HB_EBLOXX-A5CR_E_V11.doc
Gantner Instruments Test & Measurement GMBH
Picture 3.2.
- Bus Connection of an e.bloxx A5-1CR to the RS 485 Fieldbus with Derivation
Picture 3.3.
- Bus Connection of an e.bloxx A5-1CR to the RS 485 Fieldbus via Stub Cable
The stub-cable should be as short as possible, not longer than 30 cm.
Notice:
The terminal designations A and B of all modules of the e.bloxx series
are exchanged compared with the
PROFIBUS-definitions. Consequently, in multi-vendor systems the bus lines A and B have to be exchanged
when connecting them to the e.bloxx.
Bus Structure
The bus structure is a line structure where each bus segment will be terminated with an characteristic impedance on
both ends. Branches can be set up by means of a bi-directional signal amplifier, so-called repeaters. Other types of
branches are not permitted (no tree topology). The max. stub-length to a user may not exceed 30 cm.
The following figures show a few examples of possible bus topology structures. The meanings of the symbols are as
follows: