Gamma DIGITEL MPCq Скачать руководство пользователя страница 18

Page 18 of 28

Gamma Vacuum DIGITEL MPCq Users Manual

Document 900034, Rev B

14.2 Gamma Protocol Response Packet Structure Over Serial Connection

The response packet is made up of at least five fields and contains information to let the controlling computer know the command requested 
was either recognized and accepted (STATUS = “OK”), or an error condition occurred (STATUS = “ER”). The minimum packet also contains 
a RESPONSE CODE that is used either to pass an error code (if STATUS = “ER”), or is available for each unit to use as needed for a STATUS 
return of “OK”. The minimum response packet (simple acknowledgment with no data) would consist of the following fields, and would be 12 
bytes long.

Table 5.  Response Packet Structure Over Serial Connection

ADDRESS

space

STATUS

space

RESPONSE 

CODE

space

RESPONSE 

DATA

space

CHECKSUM

TERMINATOR

2 bytes

1 byte

2 bytes

1 byte

2 bytes

1 byte

(variable)

1 byte

2 bytes

1 byte

5.1 Field

5.2 Size

5.3 Comment

1. ADDRESS

2 ASCII hex characters

Range 00 through FF

This field is filled in with the hexadecimal representation of the integer address of the unit. The range provides 255 unique addresses. The 
controlling computer will use this field to determine that the correct remote unit is responding.
2. STATUS 

2 ASCII hex characters

Either OK or ER

This field is made up of two ASCII characters and is either OK or ER. OK indicates success in recognizing the command. ER indicates an 
error condition followed by an error code. (See “Table 6. Response Code Error Codes” on page 18.)
3. RESPONSE CODE

2 ASCII hex characters

Range 00 through FF

For an error condition with an incoming command, this field returns an error number to the controlling computer. For non-error conditions, 
this field returns a status byte/word to the controlling computer. (See “Table 6. Response Code Error Codes” on page 18)

NOTE: 

If there is not an applicable error code, a “00” will be transmitted.

4. RESPONSE DATA

As needed

ACSII printable characters only

Data field(s) are used to respond to commands requesting data. For example, a command requesting the current voltage setting in a unit 
would have the reading placed in a data field. Data must be in ASCII printable format. There is no limit on the number or size of data fields. 
Data is not required for all responses.

NOTE: 

Optional, only required if the command code requires it.

5. CHECKSUM

2 ASCII hex characters

Computed checksum of packet

Checksum contains a simple computed checksum of the command packet. The value must be in ASCII hexadecimal notation. The checksum 
is calculated by adding the decimal value of all characters in this packet (including the space before the checksum field) and then dividing 
the result by 256 (base 10). The integer remainder converted to two ASCII hex digits is the packet checksum. When the controlling computer 
receives a response packet, the passed checksum is converted from the hex value to a binary integer and compared with a computed 
checksum. If they are not the same, considers it an error, and repeats the last command. 
6. TERMINATOR

1 ASCII hex characters

ASCII carriage return

ASCII value of carriage return character placed at the end of a packet. There is not a space between the checksum and terminator field.

Table 6.  Response Code Error Codes

6.1 Code

6.2 Description

00

Command executed successfuly.

01

Bad command format. Returned is command syntax is not valid.

02

Bad command code. Returned in command code is not valid.

03

Bad checksum. Returned if checksum is not valid.

04

Timeout. Returned if complete command packet was not received within 2 seconds from receiving the tilde start character.

06

Unknown error. Used for internal purpose.

07

Communication error. Returned if null character 0x00 is received or if buffer overflow occurred. 

08

Bad parameter. Returned if command parameters are not valid.

Содержание DIGITEL MPCq

Страница 1: ...DIGITEL MPCq CONTROLLER USERS MANUAL Document 900034 Rev B ISO 9001 2015 Certified...

Страница 2: ...able 7 Command CRC Checksum 19 Table 8 Response CRC Checksum 19 Table 9 Gamma Protocol Commands 20 Table 10 Command Packet Struct Over Ethernet Connection 24 FIGURES Figure 1 MPCq Front Panel 6 Figure...

Страница 3: ...OCEDER AL SERVICIO DE REPARACI N MANTENIMIENTO O REVISION INTERNA ACHTUNG GEFAHR ELEKTRISCHER SCHL GE VERLETZUNGS ODER LEBENSGEFAHR TRENNEN SIE ALLE ELEKTRISCHEN ANSCHL SSE VON DER SPANNUNGSVERSORGUNG...

Страница 4: ...nect the high voltage cable with the power on After turning the power off allow at least one minute before disconnecting electrical equipment 5 Do not operate the controller without a proper electrica...

Страница 5: ...le 8 HV CONTROL ION PUMP OPERATION 8 1 Prior to using an ion pump Confirm following Rough pump down to 1x10 4 Torr or less the lower the better 1x10 6 Torr is recommended See Rough Pump user manual fo...

Страница 6: ...11 4 Supply Setup on page 8 S Configured pump size in l s See 11 4 Supply Setup on page 8 10 FRONT PANEL Figure 1 MPCq Front Panel 10 1 Description Front panel containts Main power on off rocker type...

Страница 7: ...tches home screen to TSP view Button is available only if Remote TSP Controller is connected to the MPCq Controller Menu Invokes main menu Exit Clears screen hides control buttons Turn On Off Turns HV...

Страница 8: ...bration zeroing process 11 5 Display Setup Figure 8 Display Setup Screen Available setup Brigtness Level Configures screen brightness level 1 10 Screensaver Configures screen saver on off state Turnin...

Страница 9: ...iply current log value in step 1 by 1 Step 3 Add the offset value 7 7 8 0 3 Volts The analog output pin will read 0 3V Logarithmic Pressure Example Pressure 1x10 9 Torr Offset 11 Output state Normal S...

Страница 10: ...t digital output is asserted OFF Pressure When pressure value gets above this point digital output is deasserted HV Error Function Digital output is asserted when supply error is detected HV Output St...

Страница 11: ...gister map is available on Gamma Vacuum website under download section 11 12 Profibus Setup Figure 15 Profibus Setup Screen For Profibus information reference Profibus user manual document 900033 avai...

Страница 12: ...f TSP cannot continue because Pressure Window is set but supply is off TSP Armed Outside the pressure window TSP cannot continue because Pressure Window is set but pump pressure is outside the pressur...

Страница 13: ...s between each sublimation cycle Advance Options Configure Invokes TSP advance options window TSP1 TSP2 Selects TSP for which above parameters are configured 11 17 TSP Pressure Window Setup Figure 20...

Страница 14: ...ymore In comparison Active indicates error was detected and still active at this time Addition user intervention is required to clear the error Table 1 Error Status Codes 1 1 Error Status Code 1 2 Des...

Страница 15: ...request 13 3 Connector J115 NET Profibus optional Standard Sub D 9 pin female connector Connection to Profibus interface For Profibus information reference Profibus user manual document 900033 availa...

Страница 16: ...connected 28 Not connected 29 Reserved do not use ground 30 ANALOG OUT 1 output analog range 0 to 10VDC 31 Ground 32 ANALOG OUT 2 output analog range 0 to 10VDC 33 Ground 34 ANALOG OUT 3 output analo...

Страница 17: ...e same serial port due to hardware loading limitations NOTE Must be supplied even when running RS 232 3 COMMAND CODE 2 ASCII hex characters Range 00 through FF See Table 9 Gamma Protocol Commands on p...

Страница 18: ...ror Codes on page 18 NOTE If there is not an applicable error code a 00 will be transmitted 4 RESPONSE DATA As needed ACSII printable characters only Data field s are used to respond to commands reque...

Страница 19: ...fy checksum for the response perform similar calculations Table 8 Response CRC Checksum 8 1 Characters 8 2 Value Decimal 8 3 Value Hex 0 48 0x30 1 49 0x31 space 32 0x20 O 79 0x4F K 75 0x4B space 32 0x...

Страница 20: ...fied the current name is returned S TEXT TEXT Where S is supply 1 2 TEXT is string up to 15 characters FF SYS RESET Restarts the system N Where N is the reboot mode 0 Reboot 1 Reboot and start boot lo...

Страница 21: ...Relay TTL output de energized Off Pressure must be at least 20 greater than On Pressure If not controller will automatically set Off Pressure to 20 greater than On Pressure 58 HV GET SET DIGITAL INPU...

Страница 22: ...RE Reads upper TSP pressure See pressure window option R Z Ze ZZ Where R is TSP 1 2 Z Ze ZZ is the upper pressure 72 TSP GET ONTIME Reads TSP sublimation on time R D Where R is TSP 1 2 D is the on tim...

Страница 23: ...e R is TSP 1 2 X is option Currently option 0 is only supported YY is a two digit status code 00 for TSP Initializing 01 for TSP Off 02 for TSP Armed Running 03 for TSP Armed Waiting pressure window s...

Страница 24: ...if the first digit is a zero 4 DATA As needed ACSII printable characters only Data field s are for any commands that have a data value Not all commands require data field If command has more than one...

Страница 25: ...er request SAFECONN Connector HV Interlock SMB with SHV 10 output connector or Mini Banana with Fisher output connector Display Controls 7 TFT WVGA 800x480 Color LCD 16 9 aspect ration Touchscreen Com...

Страница 26: ...ma Vacuum free from defects in material and workmanship As Buyer s sole exclusive remedy under this warranty Gamma Vacuum agrees to either repair or replace at Gamma Vacuum s option and free of parts...

Страница 27: ...on can be provided Original Purchase Order Number Gamma Vacuum Sales Order Number Product Order Number and or Product Description Product Serial Number All products received for repair or replacement...

Страница 28: ...rimental to the operation of UHV products Hazardous substance means a chemical or substance or mixture of chemicals or substances which is regulated by the Federal Occupational Safety and Health Admin...

Отзывы: