background image

SCE-SS and RCE-SS  CS-2466  09/01/06

Page 2 of 4

Specifications 

for SCE-SS

Normal operating voltage: 15 to 32
VDC.

Maximum current draw: 6.5 mA (LED
on).

Average operating current: 375 µA
group poll (SmartScan™ mode) with
LED flashing.

External supply voltage  (between
Terminals T3 and T4):
 maximum 80
volts (RMS or DC).

Drain on external supply: 2 mA maxi-
mum (using internal EOL relay).

EOL resistance: 47K ohms.

Temperature range: 32°F to 120°F
(0°C to 49°C).

Humidity range: 10% to 93% non-
condensing.

Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.

Specifications 

for RCE-SS

Normal operating voltage: 15 to 32
VDC.

Maximum current draw: 6.5 mA (LED
on).

Average operating current: 255 µA
group poll (SmartScan™ mode) with
LED flashing.

EOL resistance: not used.

Temperature range: 32°F to 120°F
(0°C to 49°C).

Humidity range: 10% to 93% non-
condensing.

Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.

Normal operating voltage: 15 to 32
VDC.

Maximum current draw: 6.5 mA (LED
on).

Average operating current: 255 µA
group poll (SmartScan™ mode) with
LED flashing.

EOL resistance: not used.

Temperature range: 32°F to 120°F
(0°C to 49°C).

Humidity range: 10% to 93% non-
condensing.

Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.

Product Line Information

SCE-SS

Intelligent Addressable Control Module.

RCE-SS

Intelligent Addressable Relay Module.

A2143-20

Capacitor, required for Class A (Style Z) operation of speakers.

SMB500

Optional Surface-Mount Backbox.

CB500

Control Module Barrier — required by UL for separating power-limited
and non-power-limited wiring in the same junction box as SCE-SS-1.

Relay Contact Ratings

 

for both SCE-SS and RCE-SS models

Mounting Diagrams

Note CB500 Module Barrier,

which creates isolated quadrant.

Load Description

Application

Maxim um

Voltage

Current

Rating

Resistive

Non-coded

30 VDC

3.0 A

Resistive

Coded

30 VDC

2.0 A

Resistive

Non-coded

110 VDC

0.9 A

Resistive

Non-coded

125 VAC

0.9 A

Inductive (L/R = 5 ms)

Coded

30 VDC

0.5 A

Inductive (L/R = 2 ms)

Coded

30 VDC

1.0 A

Inductive (PF = 0.35)

Non-coded

125 VAC

0.5 A

6724mt2.wmf

6724mt1.wmf

Отзывы: