SCE-SS and RCE-SS CS-2466 09/01/06
Page 2 of 4
Specifications
for SCE-SS
Normal operating voltage: 15 to 32
VDC.
Maximum current draw: 6.5 mA (LED
on).
Average operating current: 375 µA
group poll (SmartScan™ mode) with
LED flashing.
External supply voltage (between
Terminals T3 and T4): maximum 80
volts (RMS or DC).
Drain on external supply: 2 mA maxi-
mum (using internal EOL relay).
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F
(0°C to 49°C).
Humidity range: 10% to 93% non-
condensing.
Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.
Specifications
for RCE-SS
Normal operating voltage: 15 to 32
VDC.
Maximum current draw: 6.5 mA (LED
on).
Average operating current: 255 µA
group poll (SmartScan™ mode) with
LED flashing.
EOL resistance: not used.
Temperature range: 32°F to 120°F
(0°C to 49°C).
Humidity range: 10% to 93% non-
condensing.
Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.
Normal operating voltage: 15 to 32
VDC.
Maximum current draw: 6.5 mA (LED
on).
Average operating current: 255 µA
group poll (SmartScan™ mode) with
LED flashing.
EOL resistance: not used.
Temperature range: 32°F to 120°F
(0°C to 49°C).
Humidity range: 10% to 93% non-
condensing.
Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.
Product Line Information
SCE-SS
Intelligent Addressable Control Module.
RCE-SS
Intelligent Addressable Relay Module.
A2143-20
Capacitor, required for Class A (Style Z) operation of speakers.
SMB500
Optional Surface-Mount Backbox.
CB500
Control Module Barrier — required by UL for separating power-limited
and non-power-limited wiring in the same junction box as SCE-SS-1.
Relay Contact Ratings
for both SCE-SS and RCE-SS models
Mounting Diagrams
Note CB500 Module Barrier,
which creates isolated quadrant.
Load Description
Application
Maxim um
Voltage
Current
Rating
Resistive
Non-coded
30 VDC
3.0 A
Resistive
Coded
30 VDC
2.0 A
Resistive
Non-coded
110 VDC
0.9 A
Resistive
Non-coded
125 VAC
0.9 A
Inductive (L/R = 5 ms)
Coded
30 VDC
0.5 A
Inductive (L/R = 2 ms)
Coded
30 VDC
1.0 A
Inductive (PF = 0.35)
Non-coded
125 VAC
0.5 A
6724mt2.wmf