Programming Using the HFSS Software Suite
Programming Overview
5.3.4 Mapping LED Points
Figure 5.6 is a simple example showing how LED points are mapped to zones and Output Groups. Typically you would create two Output
Groups for each zone, one for alarms and one for troubles. (LED points are available when Model 5880 is used with the system)..
5.4 Programming Using the HFSS Software Suite
You can use the HFSS Honeywell Fire Software Suite to program the control panel on-site (the personnel will need to be on-site during the
upload or download process). HFSS is a software package that lets you easily program the control panel using a Windows-based computer.
HFSS is needed for mapping. When you use HFSS, you can set up the programming options for the panel, save the options in a file, then
download the file to the panel. You can connect directly to the control panel using the onboard USB or Ethernet port. Updates are available
at www.gamewell-fci.com.
5.5 Programming Using an Annunciator
You can program the control panel from a system annunciator, using either the control panel’s onboard annunciator or RA-1000/R remote
annunciator.
Zone 3
Offices
3rd floor
Zone 2
Storage
2nd floor
Zone 1
Show Room
1st floor
Group 3
3rd floor
notification
Group 2
2nd floor
notification
Group 1
1st floor
notification
supervisory
detector alarm
manual pull
constant
ANSI 3.41
ANSI 3.41
Zone 3
Offices
3rd floor
Zone 2
Storage
2nd floor
Zone 1
Show Room
1st floor
Group 3
3rd floor
notification
Group 2
2nd floor
notification
Group 1
1st floor
notification
supervisory
detector alarm
manual pull
constant
ANSI 3.41
ANSI 3.41
same floor
floor above
floor below
Figure 5.5 Example of Zone Events Mapped to Output Groups and Patterns
Zone 1
manual pull alarm
Zone 1
detector alarm
Zone 1
trouble
Output group 1
red LED 1
alarm outputs
(horns, strobes, etc.)
An alarm in Zone1 will activate red
LED1 and any other required outputs.
Output group 2
yellow LED 2
maintenance room
sounder
A trouble in Zone1 will activate yellow
LED2 plus any other needed outputs.
(In this example, it activates a sounder in
the maintenance room.)
Output group 3
red LED 3
alarm outputs
(horns, strobes, etc.)
An alarm in Zone2 will activate red
LED3 and any other required outputs.
Output group 2
yellow LED4
A trouble in Zone2 will activate yellow LED4.
Zone 2
manual pull alarm
Zone 2
detector alarm
Zone 2
trouble
Mapping LEDs to Zones and Output Groups
Figure 5.6 Example of LED Points Mapped to Output Groups (applies to Model 5880)