background image

BD-SS and BDT-SS   CS-2516   09/01/06

Page 3 of 4

Specifications

Environmental Specifications

Temperature

–22°F to 131°F (–30°C to 55°C).

Humidity

10 – 93% RH noncondensing.

Electrical Specifications

Voltage

15 to 32 VDC.

Average standby current

24 VDC: 2 mA maximum (LED flashing,

SLC @ 24 V).

LED current

6.5 mA maximum.

Remote annunciator current

11.2 mA maximum.

Average current during testing

500 mA maximum.

Alarm current

24 VDC; 8.5 mA maximum (LED on).

Trouble/fault current

24 VDC; 4.5 mA maximum (LED on).

Fault condition current

Add to standby current; 100 mA

maximum.

Alignment mode current

24 VDC; 20 mA maximum.

External supply 

(BDT-SS only)

Voltage:

 15 to 32 VDC.

Current:

 0.5 A maximum.

Remote output (alarm)

Voltage:

 15 to 32 VDC. 

NOTE: Output

voltage is the same as device input voltage.
Current:

 15 mA maximum, 6 mA

minimum. 

NOTE: Output current is limited

by 2.2K ohm resistor.

Heater kit BEAMHK

Voltage:

 15 to 32 V. 

Current:

 92 mA

maximum @ 32 V (heater only).

Power consumption:

 nominal 1.6 W

@ 24 V; maximum 3.0 W @ 32 V.

Heater kit BEAMHKR

Voltage:

 15 to 32 V. 

Current:

 450 mA

maximum @ 32 V (per reflector). 

Power

consumption (per reflector):

 nominal 7.7

W @ 24 V; maximum 15.0 W @ 32 V.

Mechanical Specifications

Detector dimensions

10.0" H x 7.5" W x 3.3" D

(254 mm H x 191 mm W x 84 mm D).

Reflector dimensions

For 16' to 230' (5 to 70 m) applications:

7.9" x 9.1" (200 x 230 mm).

For applications beyond 230'/70 m:

15.7" x 18.1" (400 x 460 mm).

Switch

Locations

Wiring

Diagram

Wiring Diagram 

(with RTS451/KEY)

g2516w1.wmf

6985swlo.wmf