7100 Series Installation/Operating Manual —
P/N 9000-0447:J 08/28/08
65
Automatic Configuration
Power Up Procedure
6.3.1 7100 Series Device Types and Functions
Table 6.3.1 lists the 7100 Series control panel device types and functions.
#
Device Type
Physical
Response
Action in Alarm Condition
1
Ion Sensor
Ion
Smoke
Alarm
Trips ALARM LED and
ALARM Relay
Trips other output per
Day Alarm or Night
Alarm Response, or by
group
Smoke Alarm may be
verified or PAS:
Manual Alarm may be
PAS.
Alarm condition latches,
trouble condition is
restorable
2
Ion Duct Sensor
3
Photo Sensor
Photo
4
Photo Duct Sensor
5
Photo/Thermal
6
Thermal
Thermal
Alarm
7
8
Smoke Det
AMM
9
Manual Station
Manual Alarm
10
Plenum Det
Alarm
11
N.O. Contact
12
Heat Det
13
SubLoop
14
Waterflow Silenceable
15
Beam Det
16 Duct Det
17
FACP Alarm
18
Remote Zone
19
Smoke/Heat
20
Supervisory Switch
(Non Latching)
AMM
Supervisory NL Trips general supervisory
outputs, SUPERVISORY
LED TROUBLE Relay.
Alarms and Troubles
restore.
21
Tamper Switch (Latching)
Supervisory L
Alarms latch,
Trouble restore.
22
Waterflow NonSilenceable
AMM
Waterflow NS
Same as ALARM but inihibits panel silence.
23
Non-Reporting Actuator Latch
AMM
Non-Report
Activates group, but
produces no other
response
Alarm latch
24
Non-Reporting Actuator Nonlatch
Alarms restore
25
Non-Reporting Ion Non latch
Ion
26
Non-Reporting Photo Non latch
Photo
27
Ion Multilevel
Ion
Multilevel
Produces “Alert,” “Action,” or “Alarm” response
depending on global %-of-alarm settings
28
Photo Multilevel
Photo
29
Signal Silence
AMM
Silence
Non-latching
Produces the specified function
30
Reset
Reset
31
Drill
Fire Drill
32
Alarm Acknowledge
Alrm Ack
33
Trouble/Supv Acknowledge
Trbl/Supv Ack
34
Aux
Aux
Table 6.3.1 7100 Series Device Types and Functions