CENTRIC 3x480, User Guide, rel. 1.7
Register
Variable name
GET Values
Remarks
260 4x0260 Output Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
261 4x0261 Output Current Line 2
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
262 4x0262 Output Power Line 2
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
263 4x0263 Output Apparent Power Line 2
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
264 4x0264 Output Power Factor Line 2
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
265 4x0265 Output Load Line 2
%
266 4x0266 Output Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
267 4x0267 Output Current Line 3
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
268 4x0268 Output Power Line 3
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
269 4x0269 Output Apparent Power Line 3
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
270 4x0270 Output Power Factor Line 3
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
271 4x0271 Output Load Line 3
%
272 4x0272 Bypass Frequency
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
273 4x0273 Bypass Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
274 4x0274 Bypass Current Line 1
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
275 4x0275 Bypass Apparent Power Line 1
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
276 4x0276 Bypass Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
277 4x0277 Bypass Current Line 2
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
278 4x0278 Bypass Apparent Power Line 2
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
279 4x0279 Bypass Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
280 4x0280 Bypass Current Line 3
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
281 4x0281 Bypass Apparent Power Line 3
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
282 4x0282 Active Alarms Count
Active alarms, except for the ones marked "ignored" or "for log only" in the controller
configuration
Register
Variable name
GET Values
Remarks
301 4x0301 General Fault
0: Alarm off
1: Alarm on
Any active alarm exists, except for the ones marked "ignored" or "for log only" in the
controller configuration