Wiring and Features

Limit Switch Inputs:  

The receiver has provisions for two normally closed limit switches (not included with the remote control 

system). The provision on the receiver terminal block are labeled LIMIT UP and LIMIT DOWN. The receiver must see a +12V 
signal on these lines to operate with the remote control or the manual switch in the UP or DOWN direction. 

You will need to c12VDC to the common terminal on your limit switches and connect the normally closed terminal on 
your limit switches to the terminal block positions labeled LIMIT UP and LIMIT DOWN. Wiring your limit switches this way will 
provide a cont12VDC signal to the receiver when the switch is not activated. 

When a limit switch is activated the +12VDC connection to the receiver is opened. If the receiver does not see a +12VDC signal 
on the LIMIT UP or LIMIT DOWN terminal the MOTOR OUTPUT will not function when the UP or DOWN operation is activated 
on the remote control or the manual switch.

Manual Switch Inputs:  

The receiver includes inputs for a manual switch to control the polarity reversing output.  The manual 

control inputs to the receiver are labeled “

Down Manual

” and “

UP Manual

”.  The manual switch inputs are Normally-Open (NO), 

and +12 Volts DC is applied to each input to activate the output.  A single-pole, double-throw 3-Position momentary-ON, OFF, 
momentary-ON switch should be used to control the manual switch inputs.  Note: The manual switch inputs when activated will 
take priority over the RF transmitter.

Output Current Sensing:  

The current sensing circuit will monitor the output current and turn off the output and reset the output 

for 5-seconds when the output current exceeds the current trip setting of the switch.  The output current sensing is adjustable 
from 5-Amperes to 35-Amperes.  There is a 0.5-second delay in the current sensing to allow for motor inrush.  

NOTE: IF LIMIT SWITCHES ARE NOT USED FOR ONE OR BOTH DIRECTIONS, YOU MUST SUPPLY A CONSTANT 
+12VDC SIGNAL TO THE “LIMIT UP” OR “LIMIT DOWN” POSITION ON THE TERMINAL BLOCK FOR THE MOTOR 
OUTPUT TO FUNCTION.

WWW.GAMAINC.COM

RF12V1PR-LS

Instruction Manual