© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page
12
of
24
1. Repeat the procedure of recording and checking supply temperatures. (The same type of measuring
equipment should be used).
2. If the temperature has changed significantly from the previously recorded valves, the following should be
checked:
a. All in-line or integral valve filters are clear of obstruction.
b. All in-line or integral check valves are clean and working properly to prevent backflow.
c. Any isolating valves are fully open.
d. The thermostat is free of debris.
3.
When satisfied with the mixed outlet temperatures re-record the temperatures.
10.2
GENERAL SERVICING
General Servicing of the CliniMix® CMV2 Wall Mounted Hands Free Point Of Use Thermostatic Mixers
10.2.1 STRAINER AND NON-RETURN VALVES
1. Activate the
‘Temp r ry ff’ fun t n f r the sens r
(See section 7.2 Sensor Setting Instructions).
Disassemble spout and faceplate (reverse steps 6
and 7 in section 7.0 Installation. Disconnect the
sensors cables.
INSTALLATION7.2 SENSOR SETTING INSTRUCTIONS
2. Turn the isolating ball valves to the
‘C O E’ p s t n
3. Unscrew and remove service cartridges using metric
spanner 22mm. Remove non-return valves.
4. The strainers and non-return valves should be
cleaned with a dilute water solution of suitable de-
scaling solvent (such as CLR), checked for physical
damage, and then thoroughly rinsed with clean
water. Replace the service cartridges if damaged or
faulty non-return valves.
Strainers
Non-return valves
Service cartridges
Spout
Locking nut
Flange
Faceplate
Sensor