Technical Data

measuring range 

humidity 

........................................ 0..100%rh

measuring element ............................................ capacitive FE09

accuracy 

at 23°C (73,4°F) ................ ±2.0%rh (40...60%rh)

 

 

at 23°C (73,4°F) ................... ±2.5%rh (otherwise)

   

 

    includes linearity and repeatability

influence of temperature ................................. 

< 0.15%rh per K

working range ............................................................. 5...95%rh

measuring medium ................. air, pressureless, non-aggressive

Response time (at calm air) ............................................... < 20 s

output

 humidity 

..............................0...10V or 0...20mA (4wire)

 

 

 

................................... or 4...20mA (2wire)

measuring range 

temperature

 

.................. 0...+50°C, -10...90°C

1)

, -30...60°C, 0...100°C

1)

 

measuring element .............................................. Pt100 class B

accuracy  

at 0...10V ..................................  ±0.2 K   ±0.36 °F

 

 

at (0)4...20mA ...........................  ±0.3 K   ±0.54 °F

working range .................................... -30...+80°C (-22...176°F)

output

 temperature 

.........................0...10V or 0...20mA (4wire)

 

 

 

................................... or 4...20mA (2wire)

0ther temperature outputs

NTC; PTC; KTY; LMx35; Pt100; Pt1000; Ni1000; AD592; LM34; 

BALKO 1kΩ; SILICON 2kΩ; 

SEMICONDUCTOR 559 mVDC @23°C (75°F)

Thermistors @ 25°C (77°F) 1,8kΩ; 2,252kΩ; 3kΩ; 5kΩ; 10kΩ; 

1,8kΩ (Type II; III, CSI); 20kΩ; 100kΩ

power supply ..................................... 15..30V DC / 24VAC± 10%

electromagnetic compatibility EMC

 

resistance to interference ............................... EN 

50 082-2

 

interference emission ................................... EN 50 081-2

max. load ...........................

(current output only) 

min load (voltage output only) ............................................ 10 k

Ω

power consumption  ....................................................... < 5 mA

permissible ambient temperature ...... -40...+80°C (-40...176°F)

                                   at the housing ....... -10....+60°C (14...140°F)

admitted air speed ........................................ 15 m/sec (50 ft/sec)

Minimum air speed (across the sensor):

output  0...10V, 2x 0...1V ................................................ 

0.5m/s

 

4...20mA, 2x 0...10V .............................................. 

1m/s

 

2x 4...20mA ........................................................ 

1.5m/s

probe length ....................................................... 200mm (7,87")

probe material ..................... aluminium, electrolytically oxidized

for channel mounting ................................ perforation in the case

mounting position ...................................................... as you like

contacting ............................ connecting terminals in the housing

connecting terminal conductor cross sections  

 

 

 

 

 

         ...... 1.5mm

2

 (0,023"

2

 )

housing .............................................................. polystyrol-ABS

protective system ............................................................... IP64

weight ..................................................... approx.  0.3 kg (0.6 lbs)

1)

 

please observe working range    

Description of the sensors

The sensors FK80J (humidity only) / TFK80J (humidity 

and temperature) measure the air humidity by means 

of  a  humidiy-dependant  condenser.  The  capacitive 

humidity measuring element, produced using thinfilm 

technology,  consists  of  a  base  plate,  on  which  the 

electrodes are housed and a hygroscopic polymer 

layer avove it. The hygroscopic polymer layer absorbs 

water molecules from the medium to be measured (air) 

or releases them, thereby altering the capacity of the 

condenser. In a tandem-arranged electronic device, the 

change in capacity is processed via integrated signal 

preprocessing into signals 

0..20mA or 0..10VDC or 

4..20mA.

The measuring element is protected by a protective 

guard.  The  sensors  are  designed  for  pressureless 

systems - the measuring medium is non-corrosive air.

The TFK80J sensors also contain a semi-conductor 

temperature  sensor  for  simultaneous  temperature 

measurement. Its measured  values are likewise con

-

verted into standardised signals

 0..20mA  or 0..10VDC 

or 4..20mA

The temperature coefficient as well as the self-heating 

of the electronic may vary according to the location and 

the application (especially with sensors where electronic 

and measuring system are integrated in one housing.

Maintenance - Application instructions -

Influence of dirt

In a clean environment, the measuring element is main

-

tenance-free. 

Depending on their type and concentra-

tion, aggressive media containing solvents can cause 

incorrect readings or cause the sensor to fail.

 Direct 

sunlight should be avoided. 

Substances deposited on 

the sensor element (e. g. resin aerosols, paint aerosols, 

smoke  deposits  etc.)  are  harmful  as  they  eventually 

form a water-repellent film (

this applies to all humidity 

sensors with hygroscopic measuring elements).

Please consult "

application instructions for the 

sensing elements"

  (product  info  sheet  no.  A  1)  or 

check  with  the  manufacturer  for  further  information 

which you need to bear in mind when using humidity 

sensors with capacitive sensing elements.

This information is based on current knowledge and is intended to provide details of our products and their possible applications. It does not, therefore, act as a guarantee of specific 

properties of the products described or of their suitability for a particular application. It is our experience that the equipment may be used across a broad spectrum of applications under 

the most varied conditions and loads. We cannot appraise every individual case. Purchasers and/or users are responsible for checking the equipment for suitability for any particular 

application. Any existing industrial rights of protection must be observed. The perfect quality of our products is guaranteed under our General Conditions of Sale. Issue : November 

2014 FK80_E. Subject to modifications.

supply  - 10 VDC

0.02 amps

R

L

(

) =                                 

Gall

tec

 Mess- und Regeltechnik GmbH 

MELA

 Sensortechnik GmbH

D-71145 Bondorf 

.

  Germany  

D-07987 Mohlsdorf-Teichwolframsdorf 

.

 Germany 

Tel. +49 (0)7457-9453-0 

.

 Fax +49 (0)7457-3758  

Tel. +49(0)3661-62704-0 

.

 Fax +49(0)3661-62704-20

E-Mail: [email protected] 

.

 Internet:www.galltec-mela.de 

E-mail:[email protected] 

.

 Internet: www.galltec-mela.de

Содержание FK80J

Страница 1: ... device the change in capacity is processed via integrated signal preprocessing into signals 0 20mA or 0 10VDC or 4 20mA The measuring element is protected by a protective guard The sensors are designed for pressureless systems the measuring medium is non corrosive air The TFK80J sensors also contain a semi conductor temperature sensor for simultaneous temperature measurement Its measured values a...

Страница 2: ...0V DC 3 4 wire 58543030 Speciality FK80JPt100 0 20 mA Pt100 Resistance 15 30V DC 3 4 wire 58703050 0 10V DC Pt100 Resistance 15 30V DC 3 4 wire 58704650 4 20 mA Pt100 Resistance 15 30V DC 2wire 58704850 FK80J AC version 0 100 rh 0 10V DC 15 30V DC 24 V AC 3 4 wire 58014700 0 100 rh 0 20 mA 24 V AC 4 wire 58014200 TFK80J 0 100 rh 0 10V DC 0 50 C 0 10V DC 15 30V DC 24 V AC 3 4 wire 58524747 0 100 rh...

Страница 3: ...ill be re gained as soon as the measuring element has been dried completely Dry dust can simply be blown off the measuring element Don t use com pressed air for this purpose Contact with the inner parts nulli fies the guarantee Console for wall mounting item no 20 009 Ventilated sensor tube for improved air flow item no 20 022 Accessories Working range 30 20 10 0 10 20 30 40 50 60 70 80 90 100 110...

Страница 4: ...l process is described in detail in DIN 50 008 IEC Publikation 260 ISO R 483 1966 In the air space above an aqueous saturated saline solutaion an ambient climate is formed whose air humidity is dependant on the water vapour pressure of the saline solution The Galltec Mela sensor checks are designed so that a foil permeable to vapour is positioned between the saline solution and the air space space...

Отзывы: