Ventilation Into a Room For Combustion Air is an Essential Requirement. 
Any apertures provided for this purpose must not be restricted or blocked. 
 
Flues Without a Flue Draft Stabiliser 2.5kW-5kW Output 

 
When installing without a flue draft stabiliser into houses built before 2008, no 
additional permanent ventilation will be required.*  Houses built after this date will 
require additional means of permanent ventilation direct to outside of at least 4400 
mm

2

.   

* Note: Installers must verify adequate draw and install ventilation if required.  See Appendix F of 

Building Regulations Approved Document J.

 

 

5kW-8kW Output 

- If you are intending to burn the stove above the independently 

tested 5kW output, then a permanently open air vent into the room where the stove is 
situated will be required.  For house built before 2008, the vent must have a free area of 
at least 1650mm

2

.  For house built after 2008, the vent must have a free area of at least 

4400mm

2

 

Flues With a Flue Draft Stabiliser 2.5kW-5kW Output 

 
When installing with a flue draft stabiliser into houses built before 2008, at least 
1500mm

2

 additional means of permanent ventilation direct to outside is required.  

Houses built after this date will require additional means of permanent ventilation direct 
to outside of at least 6800 mm

2

.   

 

5kW-8kW Output 

- If you are intending to burn the stove above the independently 

tested 5kW output, then a permanently open air vent into the room where the stove is 
situated will be required.  For house built before 2008, the vent must have a free area of 
at least 4050mm

2

.  For house built after 2008, the vent must have a free area of at least 

6800mm

2

 

Top or Rear Flue 

 
Remove the collar and accessory pack from the stove.  The 
stove will arrive with the blanking plate fitted to the rear.  
This can be removed if required allowing the collar to be 
fitted for rear flue installations.  The circular cut out in the 
rear heat shield must be removed to enable this style of 
connection – see image. 
Remove the panel from the stove by unscrewing the four 
screws and then remove the circular cut out for rear flue 
installations.  Replace the rear heat shield.  Remember to fit 
the blanking plate to the unused flue position if it has been 
removed. 

SCREWS 

Содержание ECO Series

Страница 1: ...STOVES MUST BE FITTED BY APPROVED QUALIFIED AND COMPETENT INSTALLERS PLEASE LEAVE THIS BOOKLET WITH THE HOUSEHOLDER Stoves operate at very high temperatures All persons including children and the infi...

Страница 2: ...DIMENSIONS OUTPUT EFFICIENCY PAGE 04 INSTALLATION PAGE 05 OPERATION PAGE 11 GENERAL MAINTENANCE PAGE 17 SAFETY NOTES TROUBLESHOOTING PAGE 19 STOVE ACCESSORIES PAGE 22 COMPONENT PARTS PAGE 23 TECHNICA...

Страница 3: ...carried out at SGS Environmental Services in the Netherlands Variations may occur due to installation atmospheric conditions and fuel quality WOOD ANTHRACITE EFFICIENCY 84 71 5 FLUE GAS TEMPERATURE 2...

Страница 4: ...SUPPLIERS ACCEPT NO RESPONSIBILITY IF THIS ADVICE IS NOT FOLLOWED THIS APPLIANCE HAS BEEN EXTENSIVELY TESTED FOR SAFETY AND EFFICIENCY DO NOT ATTEMPT TO MODIFY IT ALWAYS USE GENUINE REPLACEMENT PARTS...

Страница 5: ...and not more that 230mm If any of these requirements are not met the chimney should be lined by a suitable method A 125mm flue liner may be used in accordance with the Building Regulations The chimney...

Страница 6: ...on remove the baffle plates bricks and door Place in a secure place to avoid damage Refit after installation Upon completion of installation the appliance should be checked under fire for soundness of...

Страница 7: ...ight and check that all internal components are correctly positioned Clearances If the stoves are to be installed adjacent to materials that can catch fire like wood then the following clearances must...

Страница 8: ...uld be taken to level the stove and secure the hearth If existing floors do not have adequate load bearing capacity then suitable modifications must be adopted When the stove is in the desired positio...

Страница 9: ...ing with a flue draft stabiliser into houses built before 2008 at least 1500mm 2 additional means of permanent ventilation direct to outside is required Houses built after this date will require addit...

Страница 10: ...ood fire is established for the best efficiency Primary Air Slide Control Slide right to open and left to close Open this when you start a fire and to regulate anthracite fires It should be closed whe...

Страница 11: ...ure and to temper your cast iron stove We recommend this running in procedure after long shutdowns to preserve the life of stove During the curing of the paint you may notice an unpleasant smell It is...

Страница 12: ...ot exceed a load of 2kg of good quality dry wood per 45 minute period with the air controls in the same position as noted above Of course best burning depends on the quality of wood draft and stove se...

Страница 13: ...shows signs of more air reaching un burnt fuel Do not force this mechanism if it becomes very hard to move there may be some debris caught in the grate if this is the case carefully open the stove an...

Страница 14: ...the front bar rearwards over fuelling can cause excess smoke and produce temperatures beyond the designed rating of the appliance causing damage to internal parts This stove is designed to be operate...

Страница 15: ...rally occurring smokeless fuel and is the test fuel normally used and recommended Ecoal 50 Homefire Homefire ovals Phurnacite Taybrite and Multiheat Refuelling Onto a Low Fire Bed If the fire bed is n...

Страница 16: ...ge of the plate can be re positioned on top of the rear fire brick Sweeping the Chimney Your chimney should be cleaned each year before starting to use your stove for the winter Birds may have nested...

Страница 17: ...lass from your supplier Ensure you use new glass fibre seal around its edge and use the steel frame clips and screws to retain it in position Seasonal Maintenance If your stove is be unused for any le...

Страница 18: ...ordingly Never leave the stove unattended for long periods without adjusting the controls to a safe setting careful air supply control should be exercised at all times and only add the recommended qua...

Страница 19: ...or more often when poor quality fuels that are not recommended are burnt Poor Heat Output The stove may be too small for room Seek advice from a qualified heating engineer as to kW output required fo...

Страница 20: ...er from your supplier only use glass cleaner on cold glass DO NOT USE abrasives or scrapers these will scratch the glass making tar build up harder to remove NEVER spray aerosols near the appliance wh...

Страница 21: ...e to supply Matching graphite high temperature paint Stove Glass Cleaner Spare Rope Rope Seal Adhesive CO Detector Stove Fan Stove Thermometer Wood Moisture Meter Spare Glove Permanent Ventilators Pur...

Страница 22: ...3 18 Stove bottom panel FFVE8002 5 Secondary air control plate FFVE2023 19 Ash Pan FFVE2014 6 Flue collar FFVE008CE 20 Primary air slide plate FFVE8020 7 Baffle plate FFVE3007 21 Stove tool FFVE029 8...

Страница 23: ...E2014 Secondary air control plate WW FFVE5023BSC 6 Flue collar BLACK FFVE008 20 Primary air slide plate FFVE2020 Flue collar WW FFVE008CE 7 Baffle plate FFVE3007 21 Stove tool FFVE029 8 Heat shield FF...

Страница 24: ...HEAT OUTPUT N A 6 ENERGY EFFICIENCY INDEX 112 0 7 ENERGY EFFICIENCY AT NOMINAL HEAT OUTPUT 84 0 8 SPECIFIC PRECAUTIONS SEE MANUAL For North of England Sales please contact Percy Doughty Co Imperial Po...

Отзывы: